TESTING

1)

All the alarm sig nal ser vices, re leas ing de vice and ex tin guisher sys tem
should be dis en gaged dur ing the test pe riod and must be re-en gaged
im me di ately  at  the  con clu sion  of  test ing.

2)

Af ter  en er giz ing  the  de tec tor  head  for  ap prox i mately  one  min ute,  check
to see the in di ca tor red LED flash ing once ev ery 4-6 sec onds. If red LED
fails to flash, it in di cates the non-func tion ing of the de tec tor or faulty wir -
ing. Re-check the wir ing or re place the de tec tor if nec es sary.

CAUTIONS

This  heat  de tec tor  is  par tic u larly  de signed  to

  ini ti ate  and  ac ti vate

 emer -

gency ac tion, but will do so only when it is used in con junc tion with an au tho -
rized fire alarm sys tem.

The pur pose of de sign of heat de tec tors is meant to pro tect prop erty,

not life

. The heat de tec tors do not pro vide early warn ing of fire and can not de -

tect smoke, gas, com bus tion par ti cles, or flame. They will alarm when tem per -
a ture at the heat de tec tor reach 57°C (135°F) or above. Given the rapid
growth of cer tain types of fires, heat de tec tors can not be ex pected to pro vide
ad e quate warn ing of fires re sult ing from smok ing in bed, in ad e quate fire pro -
tec tion  prac tices,  vi o lent  ex plo sions,  es cap ing  gas,  and  im proper  stor age  of
flam ma ble liq uids like clean ing sol vents, other safety haz ards, or ar son.

SPECIFICHE

http:www.ben tel se cu rity.com 

Heat de tec tors do not al ways de tect fires be cause the fire may be a

slow-smol der ing, low-heat type (pro duc ing smoke), or be cause they may not

be mean where the fire oc curs, or be cause the heat of the fire may by pass

them

. Heat de tec tors will not de tect smoke, gas, flames, or com bus tion par ti cles.

Heat de tec tors are com po nents in pro fes sion ally in stalled fire alarm sys -
tems. 

They will not func tion if they have been im prop erly wired into the 

fire alarm sys tem or if power to them is dis con nected for any rea son.

Heat de tec tors can not last for ever

. They should be tested and main tained 

fol low ing the in struc tions in this man ual. To be safe, they should be re placed 
af ter they have been in stalled for ten years.

+

CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE
FACTORY SEALED HEAT DETECTOR. THIS ASSEMBLY IS
SEALED FOR YOUR PROTECTION AND IS NOT INTENDED TO BE
OPENED FOR SERVICING BY USERS. TO OPEN THE DETECTOR
HEAD WILL VOID THE WARRANTY.

RECYCLING INFORMATION

BENTEL SECURITY rec om mends that cus tom ers dis pose of their used
equipments (pan els, de tec tors, si rens, and other de vices) in an en vi ron -
men tally sound man ner. Po ten tial meth ods in clude re use of parts or whole
prod ucts  and  re cy cling  of  prod ucts,  com po nents,  and/or  ma te ri als.

For  spe cific  in for ma tion  see 
www.bentelsecurity.com/en/en vi ron ment.htm

WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)

DIRECTIVE

In the Eu ro pean Un ion, this la bel in di cates that this prod uct
should NOT be dis posed of with house hold waste. It should be 
de pos ited  at  an  ap pro pri ate  fa cil ity  to  en able  re cov ery  and  re -
cy cling.

For  spe cific  in for ma tion  see 
www.bentelsecurity.com/en/en vi ron ment.htm

BENTEL SECURITY s.r.l. re ser ves the right to chan ge the tec hni cal spe ci fi -
ca tions of this pro duct wit ho ut prior no ti ce.

HEAT SENSOR

 

RELAY 

 

LED

 

POSITION 
SETTING 

 

FIG. 3

 Sche matic of De tec tor  With Front Cover Open

Model

2/4 wire

Voltage DC

Standby

Current

(Max.)

Alarm

Current

(Max.)

Surge

Current

(Max.)

Start-Up

Time

(Max.)

Permissible

Current

(Max.)

Frequency

Alarm contact

ZT100H

2

10~35 V

55 

µ

A

50 mA

150 

µ

A

60 s

80 mA

4-6 s

ZT100HL

2

10~35 V

55  

µ

A

50 mA

150 

µ

A

60 s

80 mA

4-6 s

ZT100HR1

4

10~15 V

55  

µ

A

50 mA

150 

µ

A

60 s

80 mA

4-6 s

Form A

ZT100HR2

4

21~27 V

55  

µ

A

50 mA

150 

µ

A

60 s

80 mA

4-6 s

Form A

®