Functioning of the Channel Telephone Dialler
When a va lid event oc curs:
1.
The Te le com Mo du le will use the te lep ho ne line to which it is con nec ted (ter mi -
nals L.E.), iso la ting all te lep ho ne de vi ces con nec ted downstre am (ter mi nals L.I.).
2.
If Ena bled , the Te le com Mo du le con trols whet her it co uld ob ta in a
Dial ling Tone
, if it
co uld ob ta in it move to the next step, ot her wi se it will con si der the pho ne call to have
fa i led, hook up and re vert to step no. 1.
3.
The Te le com Mo du le dials the first Te lep ho ne Num ber which has been pro gram -
med for the event which has oc cur red.
4.
If the
Start pla ying af ter Se lec tion
op tion has been se lec ted, the Te le com Mo -
du le will move on di rectly to the next step, ot her wi se,
if the
Start pla ying af ter Vo i ce-on-line
op tion has been se lec ted, the Te le com Mo du le
will wait for the an swer from the dial led num ber for 30 se conds, if it does not ob ta in it, it
will con si der the pho ne call to have fa i led, hook up and re vert to step no. 1, ot her wi se,
if the
Start pla ying af ter De lay
op tion has been se lec ted, the Te le com Mo du le will wait
for the De lay which has been pro gram med be fo re mo ving to the next step.
5.
The Te le com Mo du le di splays the
He a der Mes sa ge
, then the
Sta tus Mes sa ge
, de -
pen ding on the kind of event which has gi ven rise to the call, then the pro gram med
Ge ne ral Mes sa ge
pro gram med for the event which has gi ven rise to the call.
6.
If the
Con firm Call Re sult
op tion is di se na bled, the Te le com Mo du le will give aga in the
se quen ce of mes sa ges ac cor ding to the num ber of
Re pe ti tions
it has been pro gram med
for, then it will con si der the pho ne call to have fa i led, hook up and re vert to step no. 1;
If the
Con firm Call Re sult
op tion is ena bled the Te le com Mo du le will hook up as
soon as the
*
key is pres sed on the cal led te lep ho ne line, will con si der the pho ne
call to have gone thro ugh and will re vert to step no. 1; if the
*
key is not pres sed af -
ter the num ber of pro gram med Re pe ti tions, it will hook up, con si der the pho ne call to
have fa i led and re vert to step no. 1.
If the
Call all vo i ce mes sa ges num bers
op tion is ena bled, the Te le com Mo du le will call
all pro gram med num bers for the event which has oc cur red, un til all pho ne calls fully suc -
ce ed ac cor ding to the num ber of
Call Attempts
which have been pro gram med.
If the
Call all vo i ce mes sa ges num bers
op tion is di se na bled, the Te le com Mo du le
will in ter rupt the calls as soon as it suc ce eds fi ni shing its calls.
n
Telemonitoring
The Te le com Mo du le sup ple ments a Di gi tal Com mu ni ca tor which al lows the im ple -
men ta tion of the Te le mo ni to ring fun ction in the FC500 se ries con trol pa nels. This
fun ction al lows or ga ni za tions which are equip ped with su i ta ble de vi ces, to "mo ni tor"
from a di stan ce the sta tus of the fire de tec tion sys tem.
The Te le mo ni to ring fun ction sends cer ta in Event Co des, to a se ries of pro gram ma -
ble Te lep ho ne Num bers, whe ne ver spe ci fic Events oc cur.
To send the se data, cer ta in Pro to cols are used which esta blish how the se sho uld be
for mat ted and the data sent.
The Te le com Mo du le sup ports the two most wi de spre ad com mu ni ca tion pro to cols in
the field of the te le mo ni to ring: Con tact ID and SIA.
Events
The events which co uld send an event code are the same as tho se of the
Te lep ho ne Dial ler.
Telephone Numbers
For the Te lep ho ne Num bers which co uld be cal led by the
Te le mo ni to ring fun ction, the same re marks shall apply as tho se made for the fun -
ction of Chan nel Te lep ho ne Dial ler.
Contact ID
The Con tact ID pro to col re lays the fol lo wing in for ma tion (see the
CONTACT ID co lumns in Ta ble 2).
Ø
Cu sto mer Code
: 4 di gits from 0 to F for the iden ti fi ca tion of the system; the Te le -
com Mo du le al lows the de fi ni tion of a Client Code for each Te lep ho ne num ber.
Ø
Qua li fier
: 1 = a new event; 3 = re-ena ble ment of an event.
Ø
Class Code
(co lumn CL.): iden tify the type of event (Alarm, Fa ult, etc.); in the fol lo wing
ta ble the pre-de fi ned Class Co des are shown; the Class Co des co uld be chan ged.
Ø
Event Code
(co lumn COD.) : iden ti fies the event; in the fol lo wing ta ble the
pre-de fi ned Event Co des are shown; the Event Co des co uld be chan ged.
Ø
Gro up num ber
(co lumn GROUP) : 2 di gits for the iden ti fi ca tion of the con trol pa nel.
Ø
Zone num ber
(co lumn ZONE): 3 di gits of the Sof twa re Zone; 000 for Con trol Pa -
nel Events; 999 for the Con ven tio nal Zone.
SIA
The SIA pro to col re lays the fol lo wing in for ma tion (see the SIA co lumns in Ta ble 2).
Ø
Client Code
: 4 di gits from 0 to 9 for the iden ti fi ca tion of the system; the Te le com
Mo du le al lows the de fi ni tion of a Client Code for each Te lep ho ne num ber.
Ø
Fun ction Code
: N = New Event; O = Re-ena bling Event .
Ø
Date
: month, day and year in which the event has oc cur red.
Ø
Time
: hour, mi nu tes and se conds in which the event has oc cur red.
Ø
Event Type
(TYPE co lumn): it iden ti fies the event; the fol lo wing ta ble shows the
pre-de ter mi ned Event Types; the Event Types co uld be chan ged.
Ø
Pe rip he ral ID
(PI co lumn) : 2 di gits for the iden ti fi ca tion of the con trol pa nel.
Ø
Area ID
(RI co lumn) : 4 di gits for the iden ti fi ca tion of the Sof twa re Zone; 0000 for
Con trol pa nel Events; 9999 for the Con ven tio nal Zone.
10
Modulo Telecom FC500PSTN
CONTACT ID
SIA
EVENT
CL.
COD.
GROUP
ZONES
TYPE
PI
RI
Software Zone Alarm
1
10
Panel no.
zone no.
FA
Panel no.
zone no.
Conventional Zone
Alarm
1
10
Panel no.
999
FA
Panel no.
9999
Control Panel Alarm
1
10
Panel no.
000
FA
Panel no.
0000
Software Zone Warning
1
200
Panel no.
zone no.
FS
Panel no.
zone no.
Control Panel Warning
1
200
Panel no.
000
FS
Panel no.
0000
Software Zone Fault
3
00
Panel no.
zone no.
FT
Panel no.
zone no.
Conventional Zone
Fault
3
00
Panel no.
999
FT
Panel no.
9999
Control Panel Fault
3
00
Panel no.
000
FT
Panel no.
0000
Software Zone Test
6
04
Panel no.
zone no.
FX
Panel no.
zone no.
Control Panel Test
6
04
Panel no.
000
FX
Panel no.
0000
Loop Fault*
3
31
Panel no.
000
FT
Panel no.
0000
Network fault (230 V)
3
01
Panel no.
000
AT
Panel no.
0000
Low Battery
3
02
Panel no.
000
YT
Panel no.
0000
Missing Battery
3
11
Panel no.
000
YM
Panel no.
0000
Earth fault
3
10
Panel no.
000
FT
Panel no.
0000
Control Panel Output
Fault**
3
20
Panel no.
000
YA
Panel no.
0000
Network fault (RS485)
***
7
51
Panel no.
000
NT
Panel no.
0000
Control Panel
Pre-Alarm
7
118
Panel no.
000
FG
Panel no.
0000
Software Zone
Pre-Alarm
7
118
Panel no.
zone no.
FG
Panel no.
zone no.
Conventional Zone
Pre-Alarm
7
118
Panel no.
999
FG
Panel no.
9999
Ta ble 2
Fac tory Event Co des: *) Open or short loop. **) NAC or OS Out puts, open or short. ***)....