Summary of Contents for JETSTREME 4+

Page 1: ...f S BENSON j INSTRUCTIONS Installation Commissioning Service and Maintenance User Manual to be retained by the user J _ _J I...

Page 2: ...al configurations for the installation of the terminal The Jetstreme 4 range of both Conventional and Balanced Flue Appliances are designed to operate on Kerosene fuel oil 28 sec The Conventional Flue...

Page 3: ...llation of Gas Fired Hot Water Boilers of Rated input not exceeding 60 kW BS 7593 1992 Code of practice for the treatment of water in domestic hot water central heating systems Jetstreme 4 Installatio...

Page 4: ...l Connection 3 8 BSP Compression 3 8 BSP Compression 3 8 BSP Compression 3 8 BSP Compression 3 8 BSP Compression Water Resistance 11 C Diff 300mm 12 in 300mm 12 in 300mm 12 in 300mm 12 in 300mm 12 in...

Page 5: ...are given in BS 6798 1987 Specification for the installation of Gas Fired Hot Water Boilers of Rated Input not exceeding 60 kW Conventional Flue If the flue is on the outside of the building then the...

Page 6: ...suitable for situations where the only route for the discharge is through a flat or shallow pitched roof The terminal guard basket supplied with the balanced flue kit must always be fitted even at hi...

Page 7: ...c filter element must be fitted in the oil supply line A valve must not be fitted on the oil return pipe if this pipe should become blocked it may cause the pump to faiL The installer MUST supply and...

Page 8: ...not exceed 0 4 bar 30cm Hg If this is not observed then dissolved gas will be released from the oil resulting in oil starvation to the burner and repeated boiler lockouts A filter of the metal bowl ty...

Page 9: ...0 Table 5 Note In all cases the tank should be positioned so that it slopes away from the outlet by 20mm per metre of length of tank 1 4 inch per foot length This is to ensure that any impurities do n...

Page 10: ...m2 226 6cm2 room Out Nil Nil Nil Nil Nil Boiler in a compartment ventilationIn Out 16 72cm2 83 6cm2 225 6cm2 112 8cm2 290Acm2 I45 2cm2 387 2cm2 I93 6cm2 453 2cm2 226 6cm2 Boiler in a vent to In 83 6cm...

Page 11: ...ramic rope and fire cement Brackets should be fitted to help support the flue as it is being built It is recommended that the boiler be covered to prevent masonry falling into the boiler when making a...

Page 12: ...opening airbrick window etc K From vertical sanitary pipework A B C D E F G H I J K Building Regulations England and Wales 1990 600 600 600 Scotland 1990 Balanced 600 600 600 600 600 600 600 600 600...

Page 13: ...ixing holes on the outlet of the boiler Ensure that the gasket is correctly fitted between the two faces The spigot should then be placed in position face down again with a gasket in place The four fa...

Page 14: ...mum efficiency and with clean combustion It is strongly recommended that an OFTEC Oil Firing Technical Association for the Petroleum Industry registered engineer is used for this purpose If difficulty...

Page 15: ...peated several times before getting ignition particularly with two pipe systems Once the flame has been established allow the burner to continue to run for approximately 10 minutes before turning off...

Page 16: ...R ON I BLACK I LOCKOUT I I I I I I 0 J I ov At SlA I Y I I I I 1 ll rf fH I l i I I I PlMR ON INDICATIIR L t 9 U 1 i i I _____L_ BURNER Fig 7 s EARTH BIlILER LIMn I External Wiring Diagram ROOM T STAT...

Page 17: ...PIIVtR ON INDICIITlR 2 JJ l i BURNER ____ L L l zzz X THERMOSTAT H RKlSTAT H 4 r fXlIBMN ylRHa fUS SA 241111 K SU PI Y I I I I r tt j l I I LOCKOUT Fig 10 External Wiring Diagrams RO lH THERH lSTAT 0...

Page 18: ...10 1 8 2 JUNCTION BOX 1 2 3 10 6 3 5 r J I IPTlrtlAL H ___ __ ___ J 0 0 0 UN2E345678910 JETSTREME CONTROL PANEL Fig 12 FULLY PUMPED SYSTEM WITH MID POSmON DIVERTER VALYES MID POSITION KII CYLINOCR C...

Page 19: ...t Tube to Nozzle 43mm 43mm 43mm 43mm 43mm BLAST TUBE PL 10 5 16 8 10 5 16 8 6 7 19 10 10 8 6 19 10 10 8 1 0 6 19 10 _ NOZZLE Danfoss 0 4580 S 0 6080 H 0 8580 H 1 0 60 S 1 10 60 S OIL Bar 7 6 7 6 7 6 9...

Page 20: ...to Nozzle 43mm 43mm 43mm 43mm 43mm BLAST TUBE PL 10 5 16 8 10 5 16 8 6 7 19 10 10 8 6 19 10 10 8 10 6 19 10 NOZZLE OIL PRESSURE Danfoss Bar P S I 0 4580 5 7 6 110 0 6080o H 7 6 110 0 85800 H 7 6 110...

Page 21: ...zzle 43mm 43mm 43mm 43mm 43mm BLAST TUBE PL 10 5 16 8 10 5 16 8 6 7 19 10 10 8 6 19 10 10 8 10 6 19 10 NOZZLE OIL PRESSURE Danfoss Bar P S I 0 40800 H 10 4 150 0 50800 H 10 4 150 0 6060 5 11 0 160 0 7...

Page 22: ...e assembled in an incorrect manner damage may occur and the warranty may be invalidated UPPER BAFFLE MID BAFFLE LOWER BAFFLE BAFFLE CONFIGURATION Fig 14 FRONT OF BOILER All damaged components should b...

Page 23: ...lease the Lockout Reset Button The light will go out and should remain so 6 Turn the boiler thermostat to the required setting The ignition cycle should then automatically commence If the appliance is...

Page 24: ...oil taps and valves are open 2 An adequate supply is in the oil storage tank 3 Mains isolation switch is ON 4 Room thermostat is set at the required setting 5 Cylinder thermostat is set at the require...

Page 25: ...not be run for long periods with the boiler thermostat set at the low end of the range This creates condensation within the combustion chamber which over time will damage the interior surface For the...

Page 26: ...ut Reset If the boiler goes to lockout condition this is indicated by the illumination of the RED NEON on the control panel To reset the burner the following procedure should be followed 1 Remove the...

Page 27: ...carried out by a competent Engineer who is OFTEC registered or is registered under one of the oil companies maintenance schemes Programmer OFF I OFF TIMED TIMED ONCE ONCE ON ON H W C W ADV SET ADV Fi...

Page 28: ...i 0 0 E lll i i r I I pl IJ IJ_ c Fig 17 Set the Clock a Switch on the mains supply to the boiler b Press release the button marked SET The question SET CLOCK will appear in the display Press release...

Page 29: ...ppear in the display Press release YES button c The display will now show the question SET CH MON FR1 Press release YES if a change to the Central Heating times are required Or Press release SET if no...

Page 30: ...urned at the next switching time Helpful hints for setting the programmer and its use When using the or buttons to set the time If they are pressed released the display will change at the rate of 10 m...

Page 31: ...t l l s Jetstreme 4 MODEL 70 90 CONVENTIONAL FLUE ILLUSTRATED BALANCED FLUE SHOWN INSETS 1 and 2 1 1 I c J I I 1 Cd I I I I I I I I L _______J Fig 18 30...

Page 32: ...955020 Top Front Boiler Insulation 3932110 3952113 3972116 Top Rear Boiler Insulation 3942112 3962115 3972118 Limit Thermostat 2860022 Boiler Thermostat 2816041 Bezel and Knob 2816042 Green Indicator...

Page 33: ...ne Number of Commissioning Engineer Fuel Type 28 second 35 second Nozzle size At commissioning C02 Smoke Number Efficiency Service Details It is recommended that this appliance should be serviced at l...

Page 34: ...nt parts provided the faulty component is returned to our Knighton Factory carriage paid In addition provided the attached commissioning card has been completed in full and returned to the Service Dep...

Page 35: ...on Powys LD71LP I Telephone 01547528534 Facsimile 01547520399 Telex 35323 Customer Services Hotline For Sales Service and Spares Telephone 01547529245 Benson Environmental Limited Printed by Leominste...