119
Timed Overload Select
AFN 22
AFN: TOL Select
22 Std Ind 60s
7 - PARAMETER DESCRIPTION
LCD Display
Range
Options
Trip Time
Motor Type
Motor Class
Std Ind Shp (Shearpin)
0 sec
Standard Induction
N/A
Std Ind 30s
30 sec
Standard Induction
1
Std Ind 60s
(Default)
60 sec
Standard Induction
2
Std Ind 5mn
300 sec
Standard Induction
10
In Duty Shp (Shearpin)
0 sec
Inverter Duty
N/A
In Duty 30s
30 sec
Inverter Duty
1
In Duty 60s
60 sec
Inverter Duty
2
In Duty 5mn
300 sec
Inverter Duty
10
Description
Two parameters in the S4 work together to configure how the motor timed overload operates:
DRV 01 - Nom Mtr Amps and AFN 22 - TOL Select.
DRV 01 (Nom Mtr Amps) should be configured to the value on the nameplate of the motor. This value is
used in calculating the percentage of load on the motor.
AFN 22 - TOL Select determines the graph of Trip (Fault) time vs. Percent Current that is used by the
Motor TOL functionality. This protective feature is speed-dependent to handle standard induction motors
whose cooling is limited by the shaft-mounted fan. Blower cooled motors and most inverter duty motors
do not have this limitation.
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...