Connecting The Keypad To The RSi SX Drive
2.4
Connecting the Keypad to the RSi SX Drive
The enhanced keypad is connected to the RSi SX drive with the six-foot
interconnection cable (part number RSiEKPCABLE6). This cable has RJ45
connectors on each end. (If you require a longer cable, Figure 11 provides the
pin-out information to construct a custom cable.)
Plug one end of the cable into the port on the enhanced keypad. (For
panel-mounted keypads, the port should be accessible through the larger, center
hole drilled in the enclosure.)
Plug the other end into the port found on the RSi SX control board just above the
TB4 terminal group. (See RSi SX Parameter Configuration manuals for further
information.)
Enabling Start/Stop & Reference Control
2.5
Enabling Start/Stop & Reference Control
Enter the direct parameter mode as described on page 10. Select parameter 875.
The valid settings are:
SKP - Drive can be monitored and stopped from the enhanced keypad. No start or
reference control.
Both - The standard keypad and the enhanced keypad may be used to start/stop
the drive and change the reference frequency. If communication is lost with
either keypad, the drive will stop and fault.
Both NoFlt - Same as "Both", but if communication is lost with either keypad, a
fault will not be generated.
z
Note:
Please see the RSi SX Parameter Configuration manual for details on
the configuration of the control and reference pathways.
18
2 - INSTALLATION
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8
Plug (male)
Jack (female)
Straight-thru
Connection
Pin 1: +24 Vdc
Pin 3: SIO+
Pin 6: SIO-
Pin 8: Common
Figure 11: Pin Connection for RJ45 Connection