01/ 2019
BENNING PV 3
11
5.4 Activating/deactivating the radio transmission of the BENNING SUN 2
+
To activate/deactivate the radio transmission, press and hold
the -key of the BENNING SUN 2 and simultaneously press
the -key.
A flashing triangle above the -key shows that the radio
transmission has been enabled.
Note
:
The automatic switch-off ("APO”) is enabled.
5.5 Measurements on the PV generator
1. Connect the BENNING PV 3 to the PV gen-
erator by means of the included measuring
leads.
2. The PV open-circuit voltage is measured auto-
matically if a DC voltage is applied.
3. In case of reversed polarity of the DC voltage,
the polarity indication is flashing and the “
”
symbol is shown on the display
1
.
4. As soon as a voltage of > 30 V is applied,
the
warning symbol is flashing. Attention!
Dangerous voltage
1
!
5. Press the -key
6
to start the automatic
measurement.
6. The measured values will be shown on the
display
1
for approx. 20 seconds or until a
key is pressed.
Note:
If the DC voltage is applied with reversed polarity or
outside the measuring range (< 5 V or > 1500 V), the
measurement is blocked.
Max.
Uo/c ≤ 1500 V
Is/c ≤ 40 A
P ≤ 45 kW
PV 3
Speichern
Store
Aufrufen
Recall
Senden
Transmit
Max.
1500 V DC
40 A DC
45 kW
ON/OFF
press 2 sec.
Vor dem Öffnen sind alle Messleitungen zu entfernen!
Remove all connections before opening!
5
%
NULL
5.6 Storing measured values
Press the key
2
to store the displayed measured values to
the next free storage location. The BENNING PV 3 can store
up to 999 display indications.
Successful storage will be confirmed by the “STORE” symbol.
If there is no more storage location available, an acoustic
signal is emitted.