3. Measurements
3.1 Resistance/ continuity testing
Set function
b
Select
sub-function
c
Set parameters and limits
- LowΩ (RLOW)
- Continuity
- Before performing
LowΩ measurement
compensate test leads
resistance, if nec. (see
instruction manual)!
- High limit resistance
[*Ω sets limit off,
0.1 Ω - 20.0 Ω]
d
Connection diagram
LowΩ (testing current: ≥ 200 mA)
Continuity (testing current: max. 8.5 mA)
e
Press the
key
Press the
key to start.
Press the
key again to stop measurement.
f
View results
Displayed results:
R:
Main LowΩ resistance result
R+:
LowΩ resistance sub-result with positive
voltage at L terminal
R-:
LowΩ resistance sub-result with positive
voltage at N terminal
Displayed results:
R:
Continuity resistance
Measurements
Resistance/ continuity testing