Troubleshooting 

The following table gives an overview of the most common errors and the possible causes. 

 

No. 

Symptom 

Cause 

LED "Power" (green left) is 
not lit 

a) Power supply (ground at pin 4 of X1, +15 to +75V at pin 5 of X1, 
right) not connected or wrongly polarized. 

b) Short circuit between switch signals (X3) and ground 

LED "Network Carrier" 
(green, left) is not lit 

a) Network cable is not connected, switch is switched off 

b) wrong cable (crossover?) 

LED "Network Traffic" 
(yellow, right) does not flash 
or flashes irregularly  

a) Software not started or running in demo mode 

b) wrong module selected (if several modules are in the network) 

LED "Ready" (green right) 
does not light up 

a) ChargePump signal not assigned, or module is not connected 

b) Software not started or running in demo mode 

LED "Drive Fault" (red left) 
lights up 

Not all power amplifiers are connected or not all are supplied with 
voltage. 

LED "E-Stop" (red right) 
lights up 

a) The emergency stop switch (X2 Pin 5 and 6) is not connected or 
pressed. 

b) The power supply is not sufficient or the 12V output is overloaded 
(maybe fans with too high power consumption connected?) 

Relays do not switch 

a) yellow LEDs light up, but relays do not switch: see 6a 

b) yellow LEDs do not light up: Pin assignment of the outputs in the 
software not configured correctly 

Motors do not turn 

a) green LED "ChargePump" is not lit: see 4 

b) Power amplifiers are not connected correctly 

only  for  leadshine  power 
amplifiers: 

Motors  have  no  holding 
torque at standstill or start up 
jerkily 

Current reduction signal is not required and must be cancelled 

 

Summary of Contents for Beamicon2 IoExt1

Page 1: ...ll known limitations of step frequency and timing problems are a thing of the past The board can be adjusted to many different configurations Depending on the selected configuration additional functio...

Page 2: ...afety measures may be required such as door interlocks and standstill monitoring As a rule such safety functions must be implemented purely electromechanically with external circuits not included in t...

Page 3: ...input Power supply 5 pole terminal X1 top right No Description 1 5V output max 150mA 2 Ground 0V 3 12V output max 0 3A 4 Ground 0V 5 24V input 15 75V Relay outputs 6 pole terminal X4 bottom right No D...

Page 4: ...re reliable operation however the following rules must be observed The breakout board must be connected either directly to the PC or to the first switch after the PC A further switch may only be added...

Page 5: ...and jumpers 10 11 must be plugged in see also Chapter 4 Configuration If the power stage is to remain active during an emergency stop recommended shorter braking distance jumpers 7 11 must remain open...

Page 6: ...against payment Relay outputs The relay outputs 1 and 2 can be used to switch 230V consumers such as spindle motor coolant pump or chip extractor The current consumption must not exceed 8A per relay o...

Page 7: ...ith old thyristor controllers whose speed input is partially connected to the mains voltage These must not be used If in doubt please refer to the data sheet of the frequency inverter or speed control...

Page 8: ...Breakout Board Installation Guide Nicolas Benezan Stauffenbergstr 26 72108 Rottenburg Phone 49 0 7457 946365 0 benezan electronics de Page Netbob1 installation docx22 09 2020 No Description Power Rea...

Page 9: ...d in detail in the Beamicon2 software manuals Therefore only the special features of the breakout board will be discussed here The easiest way to configure the software is to select the default parame...

Page 10: ...tep signals are disabled When using stepper motor output stages the current reduction signal must be applied to the enable pin if they have a current reduction input This is always active when all dri...

Page 11: ...ent at the relay outputs X4 8 Aeff Voltage at relay Holding brake 30 V Current at relay holding brake 5 Aeff Electrical connection values Parameters min max Unit Operating voltage nominal 24V 15 75 V...

Page 12: ...ifiers are used jumper JP4 4 5 must be plugged in If less than 3 power amplifiers are connected a dummy plug with a bridge between pin 7 and 8 must be inserted for the missing axes Is the emergency st...

Page 13: ...ule selected if several modules are in the network 4 LED Ready green right does not light up a ChargePump signal not assigned or module is not connected b Software not started or running in demo mode...

Reviews: