background image

T M

Document NAE1038020   

•   

10.2012   

•   

©  Bender Inc.   

•   

Page 1/1   

•   

Side 2/2

Bender Inc.   

•   

USA: 800.356.4266  /  610.383.9200  /  [email protected]   

•   

Canada: 800.243.2438  /  905.602.9990  /  [email protected]   

•   

www.bender.org

VMD420

Installation Bulletin / Reference Guide

Figure 5 - Changing Time Delays

Four separate time delays are available:

• 

t

on1

 - Response delay, prewarning

• 

t

on2

 - Response delay, main alarm

• 

t - Startup delay

• 

t

off

 - Delay on release

= Flashing Symbol

T

R

t

on

1 Adjustment

0...10 seconds

> 1.5 sec

< 1.5 sec

< 1.5 sec

< 1.5 sec

R

Press:
1 x for t

on

2

2 x for t

0...10 sec

3 x for t

off

0...99 sec

       

OR

R

Press Twice

> 1.5 sec

> 1.5 sec

Figure 6 - Latching behavior (fault memory)

Changing this setting to “ON” will cause the VMD420 to latch in the event of an alarm, and 
require a manual reset if the alarm clears. Changing this setting to “OFF” will cause the VMD420 
to automatically reset if the alarm clears.

= Flashing Symbol

T

R

> 1.5 sec

Press Once

Fault Memory

ON/OFF Select

> 1.5 sec

> 1.5 sec

< 1.5 sec

< 1.5 sec

< 1.5 sec

R

= Flashing Symbol

T

R

Failsafe

ON/OFF Select

> 1.5 sec

Press Once

R

Press Once

R

> 1.5 sec

> 1.5 sec

< 1.5 sec

< 1.5 sec

< 1.5 sec

Figure 7 - Contact operation

Use this option to change the behavior of the contacts between normally deenergized (non-
failsafe) mode and normally energized (failsafe) mode. The two SPDT contacts may be changed 
individually. Note that the VMD420 labels normally deenergized operation as “N/O” and nor-
mally energized operation as “N/C”; utilzing a normally open or normally closed contact only 
depends on which contact output is wired.

= Flashing Symbol

> 1.5 sec

< 1.5 sec

< 1.5 sec

Press nothing for

undervoltage (<)

     6 ... 300 V

otherwise:

R

1x for overvoltage (>)

     6 ... 300 V

3x for asymmetry

     5 ... 30%

4x for underfrequency

    10 ... 500 Hz

5x for underfrequency

    10 ... 500 Hz

7x for phase sequence

    ON / OFF

< 1.5 sec

T

R

Setpoint Adjustment

< 1.5 sec

> 1.5 sec

To quit

R

OR

To repeat

for more

alarms

x 2

Figure 4 - Setting alarm trip values

The VMD420 may be set to trip on undervoltage, overvoltage, overfrequency, underfrequency, 
asymmetry, or phase sequence. Any combination of these alarms may be set. Use the chart 
below for configuring trip values. Repeat or skip steps for the types of alarms you would like 
to use. Actual enabling and disabling of alarms may be configured using “Figure 8 - Relay Con-
figuration.”

Figure 8 - Relay Configuration

The two relay contacts K1 and K2 may be configured to trip on any combination of alarm 
types.  For example, K1 may be set to overvoltage and overfrequency, and K2 may be set to 
undervoltage and underfrequency. For each contact, each alarm type is turned on or off. The 
factory default is set to undervoltage only for K2, and overvoltage only for K1.

= Flashing Symbol

T

R

ON/OFF Select

> 1.5 sec

Press Once

R

Press 3x

R

< 1.5 sec

< 1.5 sec

< 1.5 sec

Press nothing for

Device error (Err)

otherwise:

R

1x for undervoltage (<  U)

2x for overvoltage (>  U)

3x for asymmetry (Asy)

4x for underfrequency (<  Hz)

5x for underfrequency (>  Hz)

6x for phase sequence (Phs)

< 1.5 sec

> 1.5 sec

To quit

R

OR

To repeat

for more

alarms

> 1.5 sec

To quit

R

OR

To repeat

for relay 2

x 2

Technical Data

Refer to VMD420 series user manual (document TGH1396en) or VMD420 series datasheet (doc-
ument NAE1032010) for detailed technical information.

Reviews: