2 PEM353

 

Connection

Comm.

Pulse

PEM353

LINETRAXX®

No.

Element

Description

1

LED Pulse (red)

Indication of energy pulsing

2

LED Comm. (green)

Indication of communication activity

3

Display

LCD graphic display

4

Button 1

The function of the buttons varies depending on the context. The meaning 
of the buttons is always shown on the display above the corresponding 
button.

5

Button 2

6

Button 3

7

Button 4

2

3

1

7

6

5

4

Overview of the terminals: The connections 

are located on the back of the device.

• l11

 

l12

 

l22

 l32

• l21

• l31

L1

L2

L3

N A1/+ A2/–

D+ D– DIC

DI

4

DI

3

DI

2

DI

1

DO

a

DO

b

DO

d

DO

c

• l41

NC I42

DO

a

DO

b

DO

d

DO

c

PEM353(-N) DO13 DO14 DO23 DO24

E1+

E1-

E2+

E2-

PEM353-P

L1 L2 L3 N

Measuring voltage inputs: The measuring leads should be protected with 2 A fuses.

A1/+ A2/-

Supply voltage: Power protection by a 6 A fuse, quick response.
If being supplied from an IT system, both lines have to be protected by a fuse.

.I41 NC I42

Measuring current inputs I4 (PEM353-N only)

D+ D-

RS-485 bus connection; Up to 32 devices can be connected to the bus.
The maximum cable length for the bus connection of all devices is 1200 m.

DIC DI1…4

4 Digital inputs, galvanically isolated, 24 V;
An external circuit providing at least a current 

I

min

 of 1 mA is required for triggering the inputs.

DOa…d 

Digital outputs

PEM353(-N) features 2 configurable outputs (N/O relay)

PEM353-P features 2 pulse outputs ("Solid State Relay")

DO13

DO14

DO23

DO24

DO

 

E1+/E2+

E1- /E2-

.I11 I12 

.I21 I22  

.I31 I32

Measuring current inputs 

I

1…3

Current measurement inputs must not be "protected" by fuses. Provide a shorting block for each current measurement input as described in 
IEC 60364-5-55 (edition 2.2) chapter 557.5.3 (wiring diagrams: disconnect terminal of the measuring current transformers "Y"). The current 
measurement inputs must not be earthed in low-voltage applications.

Operating elements

PEM353_D00335_01_XXEN / 09.2022

PEM353

Summary of Contents for PEM353

Page 1: ...guide for the following devices Type Art No PEM353 B93100355 PEM353 P B93100354 PEM353 N B93100353 Mounting in a front panel Mounting opening 92 mm x 92 mm max 92 8 x 92 8 mm 1 Mount the rubber seal on the back of the device 2 Insert the device into the mounting opening of the front panel 3 Place the four retaining clips over the device corners from behind 4 Push the retaining clips tightly agains...

Page 2: ...ng supplied from an IT system both lines have to be protected by a fuse I41 NC I42 Measuring current inputs I4 PEM353 N only D D RS 485 bus connection Up to 32 devices can be connected to the bus The maximum cable length for the bus connection of all devices is 1200 m DIC DI1 4 4 Digital inputs galvanically isolated 24V An external circuit providing at least a current Imin of 1 mA is required for ...

Page 3: ...u overview Browse View configuration Browse Enter Password Setpoints Comm Display Information Timeout Contrast Language Delimiter Main 1 4 Setpoint LCD Alarm Group 1 9 Type Parameter OverLimit UnderLimit ActiveDelay InactiveDelay Trigger 1 2 Clock Maintenance Basic Wiring Mode PT Primary PT Secondary CT Primary CT Secondary I4 Primary I4 Secondary PF convention kVA calculation CT1 3 polarity THD c...

Page 4: ...for PEM353 P E1 E1 Overvoltage category Rated voltage III 50 V Output circuit 2 IC5 for PEM353 N and PEM353 DO23 DO24 Overvoltage category Rated voltage III 300 V Output circuit 2 IC5 for PEM353 P E2 E2 Overvoltage category Rated voltage III 50 V Control circuit 1 IC6 DIC DI1 DI2 DI3 DI4 Overvoltage category Rated voltage III 50 V Control circuit 2 RS485 IC7 D D Overvoltage category Rated voltage ...

Reviews: