11

TBP202007deen / 10.2012

MK2418

Standards

DIN VDE 0100-710 (VDE 0100 Part 710): 2002-11

ÖVE-EN7/1991, ÖVE-EN7a/1994

ÖVE/ÖNORM E8007/A1: 2001-02-01

ÖVE/ÖNORM E8007/A2: 2002-11-01

IEC 60364-7-710: 2002-11

DIN EN 60439-1 (VDE 0660 Part 500): 2000-08

Technical Data

Insulation coordination acc. to IEC 60664-1

Rated insulation voltage...................................................................................................... AC 250 V
Rated impulse withstand voltage/contamination level ........................................................ 4 kV/3

Voltage ranges

Supply voltage U

s

.........................................................................................................DC or AC 24 V

Operating range of U

s

......................................................................................................20 … 28 V

Frequency range of U

s

...................................................................................................40 … 60 Hz

Power consumption ...............................................................................................................  

 3 W

Indicating and operating elements

Display (illuminated)......................................................................................................... LC Display
Number of characters / height.................................................................................2 x 16 / 4.5 mm
LEDs.............................................................................................................................. 2 (Alarm, ON)
Buttons.............................................................................................................................................. 3

Inputs/ outputs

Digital inputs (only MK2418-11) ............................................................................. 8 (IN1 … IN8)
All digital inputs with electrical isolation
Voltage range (high) .......................................................................................15 V … 30 V AC/DC
Voltage range (low) ............................................................................................. 0 V … 2 V AC/DC
Analog inputs (only MK2418-11) ..................................................................................1 (M+/M-)
Cable length, inputs ............................................................................................................ 

 500 m

Contact circuit for test button (only MK2418-11) .............................................................. PT1/PT2

Interfaces

Interface / protocol..........................................................................................................RS485/BMS
Cable length......................................................................................................................  

 1200 m

Recommended cable (screened, screen on one side to PE) ................................... J-Y(St)Y 2 x 0,6
Terminating resistor  ...............................................................................................120 

Ω

 (0.25 W)

Device address BMS bus....................................................................................................... 1 … 30

Switching elements 

Switching elements................................................................ 1 relay with one changeover contact
Rated contact voltage....................................................................................................AC/DC 150 V
Electrical endurance (AC 220V /60 Hz) .............................................. 12 000 switching operations
Contact class ......................................................................................................IIB (IEC60255-0-20)
Making capacity AC/DC ................................................................................................................5 A
Breaking capacity at AC 230 V, cos phi 0.4...................................................................................2 A
Breaking capacity at DC 24 V, L/R=0 s......................................................................................0.2 A
Operating mode .......................................................................................................... N/C operation

General data

EMC immunity................................................................................................. acc. to EN 61000-6-2
EMC emission  ................................................................................................. acc. to EN 61000-6-4
Shock resistance IEC60068-2-27 (device in operation)................................................. 15 g/11 ms
Bumping IEC60068-2-29 (during transport) .................................................................. 40 g/6 ms
Vibration resistance IEC 60068-2-6 (device in operation) ............................... 1 g / 10 … 150 Hz
Vibration resistance IEC 60068-2-6 (during transport)  ................................... 2 g / 10 … 150 Hz
Ambient temperature (during operation) ........................................................... -5 °C … +55 °C
Storage temperature range .................................................................................-25 °C … +60 °C
Climatic class acc. to DIN IEC60721-3-3 .....................................................................................3K5
Operating mode .............................................................................................. continuous operation
Mounting .......................................................................................................................  any position
Connection .................................................................................screw terminals/plug-in terminals

Normen

DIN VDE 0100-710 (VDE 0100 Teil 710): 2002-11

ÖVE-EN7/1991, ÖVE-EN7a/1994

ÖVE/ÖNORM E8007/A1: 2001-02-01

ÖVE/ÖNORM E8007/A2: 2002-11-01

IEC 60364-7-710: 2002-11

DIN EN 60439-1 (VDE 0660 Teil 500): 2000-08

Technische Daten

Isolationskoordination nach IEC 60664-1 

Bemessungsspannung ........................................................................................................AC 250 V
Bemessungs-Stoßspannung/Verschmutzungsgrad .............................................................. 4 kV/3

Spannungsbereiche

Versorgungsspannung U

s

........................................................................................ DC oder AC 24 V

Arbeitsbereich von U

s

......................................................................................................20 … 28 V

Frequenzbereich von U

s

................................................................................................ 40 … 60 Hz

Eigenverbrauch.......................................................................................................................  

 3 W

Anzeigen/Bedienelemente

Anzeige (beleuchtet)........................................................................................................ LC-Display
Anzahl Zeichen / Höhe .............................................................................................2 x 16 / 4,5 mm
LEDs..............................................................................................................................2 (Alarm, ON)
Tasten................................................................................................................................................3

Eingänge/ Ausgänge

Digitale Eingänge (nur MK2418-11) ..........................................................................8 (IN1…IN8)
Alle Digitaleingänge mit galvanischer Trennung
Spannungsbereich (high).................................................................................15 V … 30 V AC/DC
Spannungsbereich (low)......................................................................................0 V … 2 V AC/DC
Analogeingänge (nur MK2418-11)............................................................................... 1 (M+/M-)
Leitungslänge Eingänge.....................................................................................................  

 500 m

Kontaktkreis für Prüftaste (nur MK2418-11).......................................................................PT1/PT2

Schnittstellen

Schnittstelle / Protokoll.................................................................................................. RS485/BMS
Leitungslänge ...................................................................................................................  

 1200 m

Empfohlene Leitung (geschirmt, Schirm einseitig an PE)....................................... J-Y(St)Y 2 x 0,6
Abschlusswiderstand.............................................................................................. 120 

Ω

 (0,25 W)

Geräteadresse BMS-Bus .......................................................................................................1 … 30

Schaltglieder

Schaltelemente.............................................................................................1 Relais mit 1 Wechsler
Kontaktbemessungsspannung......................................................................................AC/DC 150 V
Elektrische Lebensdauer (AC 220V /60 Hz).......................................................12 000 Schaltspiele
Kontaktklasse.....................................................................................................IIB (IEC60255-0-20)
EinschaltvermögenAC/DC ............................................................................................................5 A
Ausschaltvermögen bei AC 230 V, cos phi 0,4 .............................................................................2 A
Ausschaltvermögen bei DC 24 V, L/R=0 s ............................................................................... 0,2 A
Arbeitsweise .....................................................................................................................Ruhestrom

Allgemeine Daten

EMV Störfestigkeit ............................................................................................. nach EN 61000-6-2
EMV Störaussendung  ....................................................................................... nach EN 61000-6-4
Schockfestigkeit IEC60068-2-27 (Gerät in Betrieb) .......................................................15 g/11 ms
Dauerschocken IEC60068-2-29 (Transport)..................................................................... 40 g/6 ms
Schwingungsbeanspruchung IEC 60068-2-6 (Gerät in Betrieb)......................1 g / 10 … 150 Hz
Schwingungsbeanspruchung IEC 60068-2-6 (Transport)................................2 g / 10 … 150 Hz
Umgebungstemperatur (bei Betrieb) ................................................................... -5 °C … +55 °C
Umgebungstemperatur (bei Lagerung) ............................................................. -25 °C … +60 °C
Klimaklasse nach DIN IEC60721-3-3 ...........................................................................................3K5
Betriebsart......................................................................................................................Dauerbetrieb
Einbaulage .............................................................................................................................beliebig
Anschlussart...............................................................................................Schraub-/Steckklemmen

Summary of Contents for MK2418

Page 1: ...glicht eine gleichzeitige Anzeige von Meldungen an mehreren Orten Remote alarm indicator and test combination for medical locations Intended use The MK2418 alarm indicator and test combination is intended to be used in medical locations In particular it is used to indicate op erating and alarm messages determined by insulation monitor ing devices in accordance with DIN VDE 0100 710 In addition it ...

Page 2: ...tion may personnel expose to electric shock Further more substantial damage to the electrical instal lation and destruction of the device can occur Bedienelemente 1 LED ALARM gelb leuchtet wenn ein Fehler erkannt wurde Sie verlöscht erst wenn Fehler beseitigt ist 2 LED ON grün leuchtet wenn Gerät im Betrieb ist 3 Beleuchtete Text Anzeige 2 x 16 Zeichen 4 Im Anzeige Modus Zusatzinformation bzw Spra...

Page 3: ...ckelbefestigung MK2418 und MK2418K Schalttafelausbruch 160 x 75 mm Anschluss Anschluss über BMS Bus MK2418 12 zeigt Meldungen von Medics Systemen an Legende zum Anschlussschaltbild Geräte mit BMS Bus Hier können über den BMS Bus verschiedene Bender Geräte mit BMS Bus angeschlossen werden Dies können zum Beispiel sein ISO METER 107TD47 Steuergeräte PRC487 Diffe renzstrom Auswertegeräte RCMS470 und ...

Page 4: ...Bus verschiedene Bender Geräte mit BMS Bus angeschlossen werden Dies können zum Beispiel sein ISO METER 107TD47 Steuergeräte PRC487 Diffe renzstrom Auswertegeräte RCMS470 und viele mehr 107 TL47 Isolationsüberwachungsgerät Versorgt aus dem internen Signalspannungstransformator eine MK2418 AN450 Zusatztransformator für die Versorgung von max 3 MK2418 LSE470 Lastüberwachungsgerät zur Meldung von Übe...

Page 5: ...ection test button 107TL47 Wire cross section 1 MK2418 2 MK2418 3 MK2418 0 8 mm2 750 m 400 m 150 m 1 5 mm2 1500 m 700 m 250 m 2 5 mm2 2300 m 1200 m 400 m Klemmleisten Die Melde und Prüfkombination MK2418 11 enthält auf der Ge räterückseite eine obere und eine untere Klemmleiste sowie die Anschlüsse PT1 PT2 Die Ausführung MK2418 12 enthält nur die untere Klemmleiste da sie alle Meldungen über BMS B...

Page 6: ...PERSON 6 S QUIT Einstellen im Menü Modus Während des Betriebes befindet sich die MK2418 im Anzeige Mo dus Im Menü Modus erfolgt die Einstellung aller Parameter der MK2418 Erklärung der Bedienschritte 1 So aktivieren Sie den Menü Modus und dann drücken und beide Tasten mindestens 3 Sekunden fest halten bis das Hauptmenü erscheint Hinweis Erfolgt innerhalb des Menümodus 20 Sekunden kein Tastendruck ...

Page 7: ...rtuguese P Danish DK Kroatic CRO Slowene SLO Serbo Croatian YU Finnish SF 1 EXIT Zurück ins Hauptmenü 2 ADDRESS Einstellung der eigenen Adresse der MK2418 zwecks eindeutiger Identifizierung innerhalb des BMS Bussystems Mit ENTER wird der aktuell eingestellte Parameter z B 01 angewählt Mit den Pfeiltasten kann die Adresse innerhalb ihres zulässigen Bereiches zwischen 1 und 30 geändert werden Mit EN...

Page 8: ...1 24 V IN 8 24 V 1 EXIT MK2418 11 VERSION 1 62 ADRESS 01 UPDATE 08 02 02 Untermenü ALARM ADDRESS Einstellung der Adressen derjenigen Geräte deren Meldungen auf dieser MK2418 angezeigt werden sollen Einstellbar sind Ad ressen von 1 30 Setzen Sie die Adressen von Geräten deren Meldungen angezeigt werden sollen auf on Die eigene Adres se ist automatisch auf on gesetzt Alle anderen Adressen blei ben o...

Page 9: ...er 4 0 no function 107TD47 1 Master 3 3 RCMS System 2 30 All addresses of evaluating devices 0 no function Werkseinstellung MK2418 12 Beispiele für einfache Systeme mit einer MK 2418 PrüfenSieimmerdieseAdresseinstellung BeiSystemenmitmehre ren MK2418 oder anderen Bender Geräten als BMS Master sind andere Einstellungen erforderlich Bedienen Taste Zusatztext Die Taste Zusatztext gibt zusätzliche Inf...

Page 10: ...s been recognized Fault xx A fault from the bus device xx has been recognized and signalled IT SYSTEM Load 032 Taste Summer aus Die Taste schaltet den Summer stumm Der Summer ertönt erneut bei Auftreten einer neuen Alarmmeldung Meldungen im Anzeigemodus Im normalen und fehlerfreien Betrieb zeigt die Anzeige z B Dies bedeutet Es liegt kein Alarm vor Die Auslastung des IT Sys tem Transformators betr...

Page 11: ...Climatic class acc to DIN IEC60721 3 3 3K5 Operating mode continuous operation Mounting any position Connection screw terminals plug in terminals Normen DIN VDE 0100 710 VDE 0100 Teil 710 2002 11 ÖVE EN7 1991 ÖVE EN7a 1994 ÖVE ÖNORM E8007 A1 2001 02 01 ÖVE ÖNORM E8007 A2 2002 11 01 IEC 60364 7 710 2002 11 DIN EN 60439 1 VDE 0660 Teil 500 2000 08 Technische Daten Isolationskoordination nach IEC 606...

Page 12: ...entical with MK2418 11 but enclo sure for surface mounting B923795 MK2418A 12 Identical with MK2418 12 but enclo sure for surface mounting B923 796 MK2418K 11 Identical with MK2418 11 but for cable duct mounting in horizontal direction B923797 MK2418K 12 Identical with MK2418 12 but for cable duct mounting in horizontal direction B923798 Wall mounting kit B 923 711 Panel mounting kit B 923 780 Ans...