Intended use

The AC/DC sensitive measuring current transformers 

of the CTUB103 series convert system leakage and 

fault currents into an evaluable measurement signal. 

The devices are suitable for detecting fault currents 

with smooth DC components. They consist of a 

CTBC… measuring current transformer core and a 

CTUB103 electronic module, which can be combined 

to suit the application. The measuring current trans-

formers can be used in DC, AC and 3(N)AC systems as 

well as in high-resistance grounded systems for mo-

nitoring the star point. The evaluation in resistance 

grounded systems is carried out with devices of the 

NGRM… series, to which the measuring current 

transformers are connected.  

General safety instructions

Part of the device documentation in addition to this 

manual is the enclosed „Important safety instructions 

for Bender products“.
Mounting, connection and commissioning are to be 

carried out by electrically skilled persons only! It is es-

sential to follow the existing safety instructions.

 

I

 D

anger

Indicates a high risk of danger that 

will result in death or serious injury if not  

avoided.

 

I

C

aution

Indicates a low-level risk that can 

result in minor or moderate injury or dama-

ge to property if not avoided.

 

i

 

Information can help to optimise the use of 

the product.

Device features

•  Multicolour LED for operation, fault and status 

messages 

•  Electronic module can be exchanged without me-

chanical separation of the primary conductors 

•  Monitoring of the connection to the measuring 

current transformer

•  Evaluator: NGRM500, NGRM700

CTUB103_D00410_02_M_XXEN / 09.2022

LINETRAXX® CTUB103

Summary of Contents for LINETRAXX CTUB103 Series

Page 1: ...Manual EN CTUB103_D00410_02_M_XXEN 09 2022 LINETRAXX CTUB103 AC DC sensitive measuring current transformer...

Page 2: ...al safety instructions Part of the device documentation in addition to this manual is the enclosed Important safety instructions for Bender products Mounting connection and commissioning are to be car...

Page 3: ...2 24 60 2 36 56 2 20 78 3 07 C CTUB103 CTBC120 188 7 40 225 8 86 96 3 78 120 4 72 65 2 56 96 3 78 139 5 47 D CTUB103 74 2 91 44 1 73 30 1 18 32 1 26 4 6 0 18 b c d a e d e f c b a d e f c b a g a d e...

Page 4: ...A 50 mA 100 1 10 A 10 A 50 mA 200 1 25 A 25 A 50 mA 500 1 1 11 10 9 2 3 4 5 6 7 8 Offset Calibration i For measuring current transformer cores with an internal diameter 120 mm an offset calibration sh...

Page 5: ...ce make sure that the installation has been de ener gised Observe the rules for working on electrical installations Observe the information on no minal voltage and supply voltage specified in the tech...

Page 6: ...the meas uring current transformer Never route an existing protective conductor through the measuring current transformer PE L1 L2 L3 N P1 K YE P2 L GY The primary conductors may only be bent from th...

Page 7: ...ue CTBC35 0 6 Nm CTBC60 CTBC120 1 Nm Other Operating mode continuous operation Mounting any position Degree of protection built in components DIN EN 60529 IP40 Degree of protection terminals DIN EN 60...

Page 8: ...fo bender de www bender de All rights reserved Reprinting and duplicating only with permission of the publisher Bender GmbH Co KG PO Box 1161 35301 Gr nberg Germany Londorfer Str 65 35305 Gr nberg Ger...

Reviews: