Operation
56
CMS460-D_D00045_01_M_XXEN/07.2016
6.4.6.4
Settings menu 4: Relays
In this menu, you make the settings for the two common alarm relays K1 (C11,
C12, C14) and K2 (C21, C22, C24) either individually or for both relays. Select
the relay:
1. Use the arrow button "
" to set the relay. Press the "
↵
" button.
2. Use the Up/Down buttons to select one relay (1, 2) or both relays
(1…2). Press the "
↵
" button to confirm your selection.
1.Relay mode
Set the relay mode
N/O
operation. Relay only switches in the event of an alarm.
N/C
operation. Relay only switches in the event of an alarm.
N/O-T
operation. Relay switches in the event of an alarm or a test.
N/C-T
operation. Relay switches in the event of an alarm or a test.
off
Relay contacts are always open*
on
Relay contacts are always closed*
* This function can also be activated via the BMS bus. Sending the command "off"
or "on" via the BMS bus may may cause the relay to switch. This relay does not
respond to alarms. It serves merely as a signal converter BMS bus/relay contact
message.
Relay: 1
Exit
1.Relay mode:N/O-T
2.Alarm: on
Set one relay:
Relay: 1..2
Exit
1.Relay mode:N/O-T
2.Alarm: on
Set both relays:
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......