Modbus register assignment of the ISOMETER®
Modbus register assignment of the ISOMETER®
isoBAT425_D00308_04_M_XXEN/07.2020
26
3017
RW
Parity "Adr 2"
UINT 16
---
0 = 8N1
1 = 8O1
2 = 8E1
3 = 8N2
3018
RW
Start-up delay "t"
during device start
UINT 16
s
0 …10
3019
RW
Response delay "ton"
for alarm relays "K1"
and "K2"
UINT 16
s
0 … 99
3020
RW
Delay on release "toff"
for alarm relays "K1"
and "K2"
UINT 16
s
0 … 99
3021
RW
Repetition time "test"
for automatic
device test
UINT 16
---
0 = OFF
1 = 1
2 = 24
3022
RW
Reserved
---
---
---
3023
RW
Reserved
---
---
---
3024
RW
Test of the system con-
nection during device
test "nEt"
UINT 16
---
0 = Inactive
1 = Active
3025
RW
Device test during
device start "S. Ct"
UINT 16
---
0 = Inactive
1 = Active
3026
RW
Request stop mode
(0 = deactivate device)
UINT 16
---
0 = Stop
1 = ---
3027
RW
Alarm assignment of
alarm relay 1 "r1"
UINT 16
---
Bit 10 … Bit 1*
3028
RW
Alarm assignment of
alarm relay 2 "r2"
UINT 16
---
Bit 10 … Bit 1*
3029
RW
Measuring pulse
period duration
UINT 16
---
0 = auto 0.8 s
1 = auto 2.0 s
2 = 0.8 s
3 = 2.0 s
4 = 4.0 s
5 = 8.0 s
8003
WO
Factory settings for all
parameters
UINT 16
---
0x6661 "fa"
8004
WO
Factory setting only
for parameters resetta-
ble by FAC
UINT 16
---
0x4653 "FS"
8005
WO
Start device test
UINT 16
---
0x5445 "TE"
Register
Property
Description
Format
Unit
Value range
* Bit numbers of the alarm assignment can be found on
RW = Read/Write; RO = Read only; WO = Write only
8006
WO
Clear fault memory
UINT 16
---
0x434C "CL"
9800
to 9809
RO
Device name
UNIT 16
(ASCII) -
refer to
---
---
9820
RO
Software
ID number
UINT 16
---
Software ID
number
9821
RO
Software version num-
ber
UINT 16
---
Software version
9822
RO
Software version: Year UINT 16
9823
RO
Software version:
Month
UINT 16
9824
RO
Software version: Day UINT 16
9825
RO
Modbus driver version UINT 16
Register
Property
Description
Format
Unit
Value range