Operation
41
Residual current
The residual current flowing through the measuring current transformer
is continually measured and displayed.
If the residual current exceeds 100 mA, it will be indicated on the dis-
play.
If the residual current exceeds 2 A, an alarm message will be signalled.
Once the residual current reaches values of this magnitude, reliable
insulation fault location becomes impossible.
ALARM 1/1
Residual current
> 2 A
Addr.: 2 Channel: 1