5. Parameter overview
5.1 Response value setting
The two parameters that monitor the insulation resistance are "R1" and "R2". The value
R1 can only be set higher than the value R2. If the insulation resistance
R
F
reaches or falls
below the activated values R1 or R2, this leads to an alarm message. If
R
F
exceeds the
values R1 or R2 plus the hysteresis value (see table below), the alarm will be cleared.
The two parameters ("U <" and "U >") for monitoring the system voltage can be activat-
ed or deactivated. The maximum undervoltage value is limited by the overvoltage val-
ue.
FAC
= Factory settings;
Cs
= Customer settings
5.2 Configuration of the relay operating mode
FAC
= Factory settings;
Cs
= Customer settings
Para
meter
Activation
Setting value
Description
Available via
FAC
Value
range
FAC
Cs
BMS Modbus
R1
on
R2 … 200
46
kΩ
Pre-alarm value
R
an1
Hys. = 25 %/min. 1kΩ
X
X
R2
on
5… R1
23
kΩ
Alarm value
R
an2
Hys. = 25 %/min. 1kΩ
X
X
U <
off
10 … "U>"
10
V
Alarm value
undervoltage RMS
Hys. = 5 %/min. 5 V
X
X
U >
off
"U<" … 500
500
V
Alarm value
overvoltage RMS
Hys. = 5 %/min. 5 V
X
X
Relay K1
Relay K2
Description
Available via
FAC
Cs
FAC
Cs
BMS
Modbus
n.c.
n.c.
Operating mode of the relay
n.c/n.o.
X
X