ATICS-DIO_D00080_03_M_XXEN / 04.2021 79
ATICS-…-DIO
Menu
Description
4. Failure monitoring
on
Reports when no (more) communication with the BMS master is
detected.
off
It is not monitored whether a BMS master is present. This
setting is required when ATICS® is used as a "Stand-alone"
device without BMS master.
I
D
anger
!
When this setting is selected, the conditions for functional sa-
fety (SIL2) are no longer met.
I
C
aution
!
In the event of a power failure of more than eight hours, the
time and date will be reset to the factory settings.
If the "Clock" setting is
not corrected, all functions depending on this setting (history memory,
logger, test interval, service interval…) will lead to unusable results.
5. Profile
Stand.
Standard setting for channel assignment for alarms/meas. values and BMS
channels
TEST
Alternative setting (see p. P. 46 and P. 64)
7.3.4.9 Settings menu 9: Clock
Time and date are required for displays in the "History/Loggers" menu. The time setting is synchronised
via the BMS bus. The device with address 1 (MK800, MK2430, CP9xx or TM…) synchronises all other de-
vices every hour.
The time setting for the ATICS® is required for the rare case of use without a BMS bus. In this case,
ATICS® displays the fault message "No master". The date format, date and time can be set. These set-
tings remain stored for approx. eight hours following a supply interruption. The date and time will then
be reset to the factory settings (01.01.2010, 00:00:00).
Menu
Description
Exit
Exit settings menu "Clock"; go up one menu level
1. Format
d.m.y
German format (day.month.year)
m-d-y
American format
2. Date
Setting the date (e.g. dd.mm.yyyy)
3. Time
Setting the time (hours and minutes)
Summary of Contents for ATICS Series
Page 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Page 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Page 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Page 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Page 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Page 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Page 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Page 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Page 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...