ISOMETER® IRDH275BM-7
Status number
Value of the respective number
Position
of num-
bers from
the left
0 =
1 =
2 =
3 =
4 =
1
K1: N/O operation Test
K1: N/C operation Test K1: flashing function
K1: N/O operation
K1: N/C operation
2
K2: N/O operation Test
K2: N/C operation Test K2: flashing function
K2: N/O operation
K2: N/C operation
3
AK AGH675S-7
4
Cemax 0,1 μF**
Cemax 1 μF**
Cemax 2 μF
Cemax 5 μF
5
6
Self test every 24 h
Self test every hour
no periodic self test
7
Language German
Language English
8
Password protection
not activated
Password protection
activated
9
AMP measuring
principle
10
max. filter frequency
0,1Hz **
max. filter frequency
1Hz **
max. filter frequency
10Hz **
max. filter frequency
50Hz **
11
min. filter frequency
0,1Hz **
min. filter frequency
1Hz **
min. filter frequency
10Hz **
min. filter frequency
50Hz **
12
BMS mode **
test data **
13
Bus address in the
tens place IRDH275
Value: 5 ... 9
14
Bus address in the
units place IRDH275
Value: 5 ... 9
15
Number of pulses
2-9 **
Value: 5 ... 9
** The parameters marked with two asterisks are settable via the Service menu item! A password is required for that
purpose !