![Bender AGH675S-7 Manual Download Page 14](http://html1.mh-extra.com/html/bender/agh675s-7/agh675s-7_manual_2731575014.webp)
14
IRDH275BM-7_D00123_07_M_XXEN / 08/2020
Dimensions, installation and connection
Wiring AGH675S-7MV15
Legend wiring diagrams
1
Supply voltage
U
s
(see nameplate) via 6 A fuse
2, 3
Terminals L1, L2 are not connected!
4
Connection to the coupling device AGH675S-7 or the two coupling devices AGH675S-7MV15:
connect terminal AK to terminal(s) 5 of the coupling device AGH675S-7 (or the two coupling devices AGH675S-7MV15), connection
with standard low-voltage cable, maximum voltage at terminal 5: 200 V
5
Separate connection of
and KE to PE
6
Separate connection of the terminals 3 and 4 of the AGH675S-7 or AGH675S-7MV15 to PE
7
External TEST button (NO contact)
8
External RESET button (NC contact or wire jumper), when the terminals are open, the fault message will not be stored
9
STANDBY by means of the function input F1, F2:
When the contact is closed, insulation measurement does not take place.
10
Current output, galvanically separated: 0…20 mA or 4…20 mA
U
S
AGH675S-7MV15
AGH675S-7MV15
15,5 kV
DC 15,5 kV
AC/DC
15,5 kV AC/DC
2
2
14
1
6
5
4
3
2
13
12
11
10
9
8
7