background image

2.9.1

Pump

The available head shown in fig. 5 is that in
excess of the appliance hydraulic
resistance, i.e. that available for the system
at any given heating load up to the
maximum output in C.H. mode. Never
reduce the pump speed below maximum as
this will reduce D.H.W. output. The pump
speed is indicated on the side of the pump
speed selector switch (if fitted).

2.9.2

System volume 
(total water content)

The 

Table 4

gives the maximum system

volume that the integral expansion vessel
can sustain under different charge
pressure conditions. 
If the system volume exceeds that shown,
an additional expansion vessel must be
fitted and connected to the heating system
primary return pipe as close as possible to
the appliance. 
If an extra vessel is required, ensure that
the total capacity of both vessels is
adequate. Further details are available in
the current issues of BS5449 and BS6798.

NOTE: If the pressure gauge indicates
2.65 bar or greater when the appliance is
at maximum temperature with all
radiators in circulation an extra
expansion vessel is required.

2.9.3

Pressure gauge

A pressure gauge is mounted in the base of
the appliance.

2.9.4

Safety valve

A safety valve set at 3 bar is fitted to the
appliance and a discharge pipe is routed to
outside of the appliance.
This discharge pipe should be extended to
terminate safely away from the appliance
and where a discharge would not cause
damage to persons or property but would
be detected. 
The pipe should be able to withstand boiling
water, be a minimum of 15 mm in diameter,
and installed with a continuous fall.

2.10

D.H.W. SYSTEMS

– Check that the mains supply pressure is

within the prescribed limits (1.3 point).
If necessary, a pressure reducing valve
should be fitted to the mains supply
before the D.H.W. inlet connection.

– A maximum D.H.W. flow rate of 11.4 l/m

(3.0 gpm). 
Higher flow rates will not damage the
appliance but may lower the water
temperature below an acceptable level.

– If the appliance is installed in an area

where the temporary hardness of the
water supply is high, say over 150 ppm,
the fitting of an in line scale inhibitor may
be an advantage. Consult the Local
Water authority if in doubt.

2.10.1

Domestic hot/cold water supply 
taps and mixing taps

All equipment designed for use at mains
water pressure is suitable.

2.10.2 Showers

Any 

WRAS

approved shower suitable for

the mains water pressure available may be
used. A loose or flexible shower head type
may require the fitting of an anti-syphon
device to comply wth water by-laws.

2.10.3 Bidets

Providing that the appliance is of the over-
rim flushing type, the outlets are shrouded
and it is impossible to attach a temporary
hand held spray, no anti syphonage device is
necessary.

2.11

FILLING THE WATER SYSTEM

– Open the C.H. flow and C.H. return valves

(3 - fig. 3). 

– Loosen the automatic air vent cap (8 fig.

2).

– Open all radiator valves and system air

vents. Fill the system with water using
one of the approved methods described
in section 2.9 to about 0.5 bar greater
than the system design pressure. Close
all air vents. Do not close the A.A.V. the
one near the pump!

– Check the system for water soundness.
– Completely drain the appliance and

heating system, thoroughly flush the
system, and refill the system design
pressure to BS 7593.

– Open the D.H.W. inlet valve, open any hot

tap, clear of air bubbles.

– Close hot tap.

2.11.1 Emptying the system

Use the cock boiler discharge to empty the system
(15 fig. 2). Turn off the boiler before draining.

2.12

ANTI-FREEZE FUNCTION

The boilers are equipped with anti-freeze
function which activates the pumps and the
burner when the temperature of the water
contained inside the appliance drops to
below value set at PAR 10. The anti-freeze
function is ensured, however, only if:
– the boiler  is correctly connected to the

gas and electricity supply circuits;

– the boiler is constantly fed;
– the boiler ignition is not blocked;
– the essential components of the boiler

are all in working  order

In these conditions the boiler is protected
against frost down to an environmental
temperature of -5°C.

ATTENTION: 
In the case of installation in a place where
the temperature drops below 0°C, the
connection pipes must be protected.

2.13

APPLIANCE PACKAGE:

– Combination boiler (assembled);
– Installation and servicing instructions;
– Users instructions;
– Wall mounting templates (paper);
– Fixing screws with wall plugs;
– Plastic bags containing:
– gas service cock;
– C.H. F/R isolation valves;
– D.H.W. isolation valve;
– D.H.W. outlet fittings;
– associated gaskets and PRV discharge

pipe.

2.14

WATER CONNECTIONS

2.14.1

Central heating 
connections

– Fit the two C.H. isolation valves using the

gaskets supplied to the flow and return
connections as shown in fig. 2. The pipe
connections are labelled on the lower
part of the boiler.

– Connect the C.H. pipework as required.

2.14.2 D.H.W. 

connections

– Fit the D.H.W. isolation valve to the cold

water inlet connection as shown in fig. 2.

– Fit the union connection to the D.H.W.

13

ENG

IT

ES

Vessel charge and initial system pressure

bar

psi

0.5

7.3

1.0

14.5

1.5

21.8

Total water content of system using 8 l (1.76 gal) capacity
expansion vessel supplied with appliance 

l

gal

96

21.1

74

16.2

51

11.2

For systems having a larger capacity multiply the total system
capacity in litres (gal) by the factor to obtain the total minimum
expansion vessel capacity required litres (gal)

.0833

.109

.156

TABLE 4

Summary of Contents for Metropolis DGT 25 BF

Page 1: ...lation and servicing instructions ENG IT ES ENSURE THAT THESE INSTRUCTIONS ARE LEFT FOR THE USER AFTER COMPLETION OF THE BENCHMARK SECTION Please read the Important Notice within this guide regarding...

Page 2: ...e recommended Avoid direct contact with sharp edges Avoid contact with any hot surfaces NOTICE Please be aware that due to the wet testing of the appliance there may some residual water in the hydraul...

Page 3: ......

Page 4: ...dards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimi se safety efficiency and performance Benchmark is managed and p...

Page 5: ...the Benchmark Checklist in the use and maintenance section of this manual been completed IPX5D Important Information IT IS A STATUTORY REQUIREMENT THAT ALL GAS APPLIANCES ARE INSTALLED BY COMPETENT P...

Page 6: ...y water systems and is supplied fully assembled and equipped with complete valve packs The boiler can be used with a 24V room thermostat class II according to EN 60730 1 This booklet provides instruct...

Page 7: ...perature C 100 125 Smokes flow gr s 16 16 Losses after shutdown to 50 C W 73 Category II2H3 Type B22P 52P C12 32 42 52 82 Electrical supply 230V 50 hz fused at 3 A Internal fuse Line F1 6AT Weight kg...

Page 8: ...Combustion chamber 6 Gas valve 7 Water pressure valve 8 Circulator with air release vent 10 Hydrometer 11 Expansion vessel 12 D H W flow meter 13 By pass 14 D H W filter 15 Boiler discharge 16 3 BAR...

Page 9: ...s that set the burner output is reduced When this set temperature is reached the burner extinguishes and the fan stops The pump continues to run for 30 seconds to prevent residual heat build up in the...

Page 10: ...ided it is modified accordingly Where installation will be in an unusual location special procedures may be necessary BS6798 gives detailed guidance on this aspect 2 3 FLUE TERMINAL POSITION Detailed...

Page 11: ...W flow rate but does not exceed the maximum D H W pressure 1 3 point Where mains pressure exceed 6 bar a pressure reducing valve must be fitted in the D H W inlet 2 8 1 Treatment of water circulating...

Page 12: ...12 ENG IT ES TYPICAL SYSTEM DESIGN NOTE A drain cock should be installed at the lowest point of the heating circuit and beneath the appliance Fig 6 Fig 7 ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM...

Page 13: ...rim flushing type the outlets are shrouded and it is impossible to attach a temporary hand held spray no anti syphonage device is necessary 2 11 FILLING THE WATER SYSTEM Open the C H flow and C H ret...

Page 14: ...duct is longer than 1 metre it is advisa ble to insulate the duct in order to avoid the formation of dew on the outside of the pipe when the weather is particularly cold With ducts with discharge posi...

Page 15: ...horizontal pipe 80 x 0 20 1 40 7 meter horizontal pipe 80 x 0 30 2 10 No 2 90 elbows 80 x 0 35 0 70 No 2 90 elbows 80 x 0 40 0 80 No 1 wall terminal 80 0 15 0 50 Total head loss 2 25 3 40 5 65 mm H2O...

Page 16: ...he boiler casing remove the two securing screws and tilt the control panel Connect the thermostat to the 6 pole ter minal board as indicated in the boiler elec trical diagram see diagram 2 19 after ha...

Page 17: ...SSO RED FLM VERDE GREEN ARANCIO ORANGE VCC GND OUT ROSSO RED ROSSO RED ROSSO RED 3 3 VDC 24 VDC 3 3 VDC 3 3 VDC 24 VDC 3 3 VDC 24 VDC 17 VDC 12 VDC 24 VDC R59 Fig 11 KEY F Fuse 1 6 AT TRA Ignition tra...

Page 18: ...T is only available if a resettable anomaly is signalled D H W SET Press the key to display the D H W temperature value set HEATING SET Press the key to display the heating temperature value set value...

Page 19: ...03 17 Pump heating activation delay 0 99 10 sec 1 01 18 Re ignition delay 0 10 Min 1 03 19 Modulation D H W flowmeter Disabled 01 1 Enabled 29 Anti legionella only D H W tank Disabled C 1 50 80 PARAME...

Page 20: ...nition failure with consequent activation of block can be due to Lack of gas The ignition electrode persists in dischar ging for max 10 seconds If the burner does not ignite the anomaly is signalled T...

Page 21: ...NTILATORE CAMERA STAGNA Fig 14 SEALED CHAMBER FAN PRESSURE SWITCH A B C RIFERIMENTO POSIZIONE BY PASS D Fig 15 KEY A By pass on B By pass off C Water pressure valve D Automatic air vent E Drain vent R...

Page 22: ...ws fig 18 Connect the column or a manometer to the intake down stream of the gas valve and disconnect the valve VENT pressure test point tube 5 fig 16 Remove the cap 1 from the modulator Connect the c...

Page 23: ...manifold unit Ideally use a vacuum clea ner and a soft brush so as to remove any dust particles that may have accumulated take care not to damage the insulation Clean the heat exchanger removing any...

Page 24: ...05 FLAME LOCKOUT ALARM 06 fig 20 a If the flame control has not detected the presence of the flame after a complete ignition sequence or for any other rea son the card cannot see the flame the boiler...

Page 25: ...general once a year should be adequate It is the law that a competent person such as a Gas Safe Register registered engineer must carry out any service work 4 7 1 Combustion Check Incorporated into t...

Page 26: ...ot affect the customer s statutory rights If yes and if required by the manufacturer has a water scale reducer been fitted CONDENSING BOILERS ONLY The condensate drain has been installed in accordance...

Page 27: ...er No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date...

Page 28: ...e the position of the sensing pipe and disconnect 6 REPLACEMENT OF PARTS If an electrical fault occurs on the appliance the preliminary electrical system checks must be carried out first When any serv...

Page 29: ...iler cover see 4 3 Close the flow and return isolation valves Drain the boiler using the fitted drain vent see fig 15 Disconnect the electrical connections to the pump Remove the four fixing screws Re...

Page 30: ...Water heat exchanger 014 6231362 NTC sensor 015 6318600 Sealed chamber front panel 016 6225636 Fan 017 6317900 Combustion chamber front panel 018 6318700 Combustion chamber side insulat 019 6264841 C...

Page 31: ...valve operation 062 6319630 Flowmeter 063 6147231 Straight fitting 1 2 15 064 6245000 Ball cock 3 4 x22 065 6245001 Ball cock 1 2 x15 066 6063601 Gas cock 1 2 068 2030227 Gasket 12x18x2 069 6226457 O...

Page 32: ...4258 Gas Water heat exchanger 014 6231362 NTC sensor 015 6318600 Sealed chamber front panel 016 6225636 Fan 017 6317900 Combustion chamber front panel 018 6318700 Combustion chamber side insulat 019 6...

Page 33: ...9630 Flowmeter 063 6147231 Straight fitting 1 2 15 064 6245000 Ball cock 3 4 x22 065 6245001 Ball cock 1 2 x15 066 6063601 Gas cock 1 2 068 2030227 Gasket 12x18x2 069 6226457 O ring 12bis diam 16x1 90...

Page 34: ...34 ENG IT ES NOTES...

Reviews: