Testing / Commissioning (self test)

Functionality of the test switch.

1) A short press (>1s) on the button start a function test lasting 5 seconds (The    
  battery’s capacity should be more than 5% = charging 30 mins

2) Holding down the button(>10s) resets the timer(System-resets)

Functional test 

The 5 second long, each 7 days’ function test serves to check the functionality of 
the emergency unit, the batteries and LED Module.

Notice.

If a mains supply failure occurs whilst a functional test is in progress, the test 
shall be postponed and the system shall enter emergency operation. Following 
restoration of the mains supply, a postponed functional test shall re-commence 
automatically as soon as conditions permit.

Duration test (EN)

Initial duration test: The test will be carried out exactly 24 hours after the initial 
installation.

Half year duration test: The test will be carried out on each 180-182 days.

Notice.

A duration test shall only be started when the battery supply is fully charged if a 
mains supply failure occurs whilst a duration test is in progress, the test shall be 
postponed and the system shall enter emergency operation. Following restoration 
of the mains supply, a postponed duration test shall re-commence automatically 
when the battery supply is fully re-charged.

The indicator will be slow flashing Green within 5 days if the duration test be 
carried out successfully.

Indicator LED

System status is locally by a bi-color indicator LED.

Notice Fault Status

 

If an error is detected, the indicator LED
switches to RED. If the error has been corrected please 
re-connecting the battery after the mains power is switched 
off, the indicator LED immediately switches back to GREEN 
when mains power is switched on.

Notice

 

Battery failed during test: After an exchange of the battery 
and holding down the button (>10S) reset the timer, the
indicator LED switches to GREEN.

- 02 -

EFFORT SEMICONDUCTOR LIGHTING LTD

 

 

 

.

Functionality of the test switch

Functional test

1) A short press (>1s) on the button start a function test lasting 5 seconds (The battery’s capacity should be more than 

   

2)Holding down the button(>10s) resets the timer(System-resets)

The 5 second long, each 7 days’ function test serves to check the functionality of the emergency unit, the batteries and  

Duration test (EN)

-Initial duration test: The test will be carried out exactly 24 hours later after the initial installation.  

-Half year duration test: The test will be carried out on each 180-182days. 

Testing/Commissioning(self test)

LED module.

5%=charging 30mins

Indicator LED

System status is locally by a bi-color indicator LED.

LED Indication

Commentary

Status

Standby,System OK

Permanent green

Mains Operation, battery is charged

Fast flashing green

(0.25s on–0.25s off)

Function test

underway

Function test underway

Slow flashing green

(1 s on – 1 s off)

Duration test

underway

Duration test underway

Permanent Red

Lamp failure

Open Circuit or Short Circuit or LED failure 

   Fast flashing red

(0.25 s on – 0.25 s off)

Battery capacity

failure

Battery failed duration test

 

Slow flashing red

(1 s on – 1 s off)

Battery fault

Green and red off

Battery Operation

Emergency mode: Mains disconnected 

Incorrect battery voltage or Short Circuit  
or Open Circuit  

or Mains failure 

Notice.

-A duration test shall only be started when the battery supply is fully charge if a mains supply failure occurs whilst a  

duration test is in progress, the test shall be postponed and the system shall enter emergency operation. Following

restoration of the mains supply, a postponed duration test shall re-commence automatically when the battery supply 

is fully re-charge 
-The indicator will be slow flashing Green within 5 days if the duration test be carried out successfully.

Notice.

-If a mains supply failure occurs whilst a functional test is in progress, the test shall be postponed and the system shall

enter emergency operation. Following restoration of the mains supply, a postponed functional test shall re-commence  

automatically as soon as conditions permit.  

If an error is detected, the indicator LED   

 switches to RED. If the error has been   

 corrected please re-connecting the battery   

 after the mains power off, the indicator LED   

 immediately switches back to GREEN when 

 

After an exchange of the battery and holding 

 down the button (>10S) reset the timer, the  

 indicator LED switches to GREEN.  

 

Fault status:  

 

Battery failed duration test:  

 

 mains power on.  

 

NOTICE

NOTICE

Installation Instructions: Deco Grande (06810/11/12/13)

Date

Revision

1.6.2022

2

06810-11_12_13 Deco Grande Installation Ins.indd   3

06810-11_12_13 Deco Grande Installation Ins.indd   3

23/06/2022   09:22

23/06/2022   09:22

Summary of Contents for Deco Grande 06810

Page 1: ...driver lead must be connected to the socket marked DC The emergency module lead must be connected to the socket marked YJD Maintained operation In this mode the luminaire is continuously on In the event of power failure the luminaire will revert to emergency mode Connections NEUTRAL to N Permanent 230V mains to PERMANENT LIVE L SWITCHED LIVE K link to PERMANENT LIVE Non maintained operation In thi...

Page 2: ...nton West Yorkshire WF6 1TN T 44 0 1924 893380 F 44 0 1924 894320 E sales belllighting co uk www belllighting co uk Installation Instructions Deco Grande 06810 11 12 13 0 C to 35 C Date Revision 1 6 2022 2 06810 11_12_13 Deco Grande Installation Ins indd 2 06810 11_12_13 Deco Grande Installation Ins indd 2 23 06 2022 09 22 23 06 2022 09 22 ...

Page 3: ...ns power is switched off the indicator LED immediately switches back to GREEN when mains power is switched on Notice Battery failed during test After an exchange of the battery and holding down the button 10S reset the timer the indicator LED switches to GREEN 02 Indicator LED System status is locally by a bi color indicator LED LED Indication Commentary Status Standby System OK Permanent green Ma...

Page 4: ...r 5 Monthly Test Signed Date Signed Date Signed Date Signed Date Signed Date Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Tel 44 0 1924 893380 www belllighting co uk Email sales belllighting co uk Page 1 Check the Charge LED illuminates Switch on the Maintained Supply Check the LED illuminates as normal Switch off the Maintained Supp...

Reviews: