MODE OF DISCHARGE

Bell & Gossett Pumps can be installed to discharge up, down,
left or right. The oiling ports must always be in the twelve
o’clock position (on top) with motor and bearing assembly in a
horizontal position.  THE ARROW ON THE PUMP BODY MUST
POINT IN THE DIRECTION OF THE FLOW. If it becomes nec-
essary to change the mode of discharge, refer to B&G
Instruction Manual HS-105-SM for specific instructions in
removing the motor and bearing assembly from the pump
body.

NOTE:

The position of the conduit box is determined by the

model of the motor used. The oiling ports must always be in
the up position.

3

WARNING: WATER LEAKAGE HAZARD

To prevent leakage, make certain that the flange

bolts have been adequately torqued. Failure to follow these
instructions could result in serious personal injury and/or
property damage.

PUMP LOCATION

Bell & Gossett Booster Pumps should be installed where there
will be sufficient room for future inspection, maintenance and
service. It is highly recommended that service valves (shut-off)
also be installed on each side of circulator pumps to facilitate
servicing or replacing the pump without draining the system.

IMPORTANT:

In closed systems, do not install and operate

Bell & Gossett pumps, 3D valves, suction diffusers, etc., with-
out properly sized safety and control devices. Such devices
include the properly sized and located pressure relief valves,
expansion tanks and pressure, temperature, and flow con-
trols. If the system is not equipped with these devices, consult
the responsible engineer or architect before operating.

PUMP SUPPORTING AND PIPING

Install the suction and discharge flanges on the pipe ends
using Teflon

®

* tape sealer or high quality thread sealant.

Minimize strain on the pump by supporting the suction and
discharge piping with pipe hangers near the pump. Line up the
vertical and horizontal piping so that the bolt-holes in both the
pump and pipe flanges are aligned. DO NOT ATTEMPT TO
SPRING THE SUCTION OR DISCHARGE LINES INTO POSI-
TION. THIS MAY RESULT IN UNWANTED STRESS IN THE
PUMP BODY, FLANGE CONNECTIONS AND/OR PIPING. The
code for pressure piping, ANSI B31.1, lists types of supports
for various applications.

Ordinary wire or band hangers are not adequate to maintain
alignment. It is very important to provide strong, rigid support
for the suction and discharge lines.

IMPORTANT:

Do not support the pump by its power pack. To

function properly, the motor power pack must not be strained.

PUMP FLANGES

New Bell & Gossett flanges gaskets must be installed between
the flanges of the pump body and suction and discharge
pipes. The gaskets should be clean and grease-free; old gas-
kets should never be reused.

Apply torque in even increments to both flange bolts until the
value listed in the table below is reached. Both the suction and
discharge flanges must be torqued in this manner.

PUMP INSTALLATION

WARNING: HOT WATER HAZARD

When disassembling a gasketed joint, always use

a new gasket upon reassembly. NEVER RE-USE OLD
GASKETS. Failure to follow these instructions could result
in serious personal injury, death and/or property damage.

OIL PORTS

*Teflon

®

is a registered trademark of E.I. DuPont de Nemours and Company.

100 With
Full Face

100 With Ring

Pump Series

Flange Gasket*

Flange Gasket

PR

HV

2"

Bolt Torque

150-180 in. lbs.

96-132 in. lbs.

96-132 in. lbs.

96-132 in. lbs.

96-132 in. lbs.

12.5-15 ft. lbs.

8-11 ft. lbs.

8-11 ft. lbs.

8-11 ft. lbs.

8-11 ft. lbs.

Full turns of

the nut from

1-1/4

1

1

3/4

3/4

finger tight

* No longer used.

WARNING: HOT WATER HAZARD

Make sure that each flange gasket remains seated in

the flange groove during and after installation. Failure to fol-
low these instructions could result in serious personal
injury, death and/or property damage.

Summary of Contents for Series 100

Page 1: ...ies 100 HV PR and 2 Pumps are listed below Do not exceed these values Maximum Working Pressure 125 psi Maximum Operating Temperature 225ºF Electrical Rating 115V 60 Hz 1PH Motors with special electrical characteristics are available on request Contact your local Bell Gossett Representative for details SAFETY INSTRUCTIONS This safety alert symbol will be used in this manual and on the pump instruct...

Page 2: ...0 F max open the drain valve take precautions against water damage and leave the drain valve open until servicing is complete Failure to follow these instructions could result in serious personal injury death and or property damage 2 Loosen the conduit box cover screw and remove the cover 3 Disconnect the electrical supply lines to the pump WARNING HIGH PRESSURE HAZARD Pressure may be present in t...

Page 3: ...ion and discharge piping with pipe hangers near the pump Line up the vertical and horizontal piping so that the bolt holes in both the pump and pipe flanges are aligned DO NOT ATTEMPT TO SPRING THE SUCTION OR DISCHARGE LINES INTO POSI TION THIS MAY RESULT IN UNWANTED STRESS IN THE PUMP BODY FLANGE CONNECTIONS AND OR PIPING The code for pressure piping ANSI B31 1 lists types of supports for various...

Page 4: ...may cause spillage onto surrounding surfaces Deteriorated motor mounts will lead to misalignment and excessive coupler wear PRIMING AND STARTING Do not run B G circulator pumps dry Before starting the pump must be filled with water Air should be vented from the system by means of a system air vent or by an alternate method 1 Remove the screws securing the conduit box cover wiring compartment and l...

Reviews: