background image

DESCRIPTION

Bell  &  Gossett  Booster  Pumps  feature  oil  lubricated  sleeve
bearings, a carbon/ceramic seal and a noise dampening spring
coupler.  Bell  &  Gossett  Booster  Pump  motors  are  designed
specifically  for  quiet  operation  and  are  built  with  thermal  pro-
tection  and  drip-proof  construction.  The  motor  is  non-
over-loading at any point on the pump curve.

This pump is nonsubmersible, for indoor use only. 

PUMP APPLICATION

Bell & Gossett Pumps may be used for water circulating appli-
cations  in  hydronic,  solar  and  chilled  water  systems.  Bell  &
Gossett recommends that bronze constructed pumps be used
for pumping potable water. For other applications contact your
local  Bell  &  Gossett  Representative.  Note  that  some  local
codes require using a check valve in the supply line when recir-
culating potable water.

It has not been investigated, nor is it intended for use in swim-
ming pool and marine areas.

OPERATIONAL LIMITS

These  pumps  are  designed  to  pump  liquids  compatible  with
their  iron  or  bronze  body  construction.  Unless  special  provi-
sions  have  been  made  by  ITT  Bell  &  Gossett,  the  operational
limits for Series 100, HV, PR and 2" Pumps are listed below.

Do not exceed these values.

Maximum Working Pressure:

125 psi

Maximum Operating Temperature: 225ºF
Electrical Rating:

115V, 60 Hz, 1PH

Motors  with  special  electrical  characteristics  are  available  on
request.  Contact  your  local  Bell  &  Gossett  Representative  for
details.

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual and on the
pump  instructions  decal  to  draw  attention  to  safety  related
instructions.  When  used,  the  safety  alert  symbol  means
ATTENTION!  BECOME  ALERT!  YOUR  SAFETY  IS  INVOLVED!
FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN
A SAFETY HAZARD.

Your  Booster  Pump  should  have  these  warning  labels  affixed
near  the  conduit  box  cover.  If  these  warnings  are  missing  or
illegible,  contact  your  local  Bell  &  Gossett  Representative  for
replacement labels.

Iron & Bronze Booster Pumps

INSTALLER:

PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Series 100
Series HV
Series PR

Series 2"

WARNING

BEFORE INSTALLING, USING OR

SERVICING THIS PRODUCT,

READ THE WARNING NOTES

AND INSTRUCTIONS IN

INSTRUCTION MANUAL.

FAILURE TO DO SO MAY

RESULT IN SERIOUS INJURY

OR PROPERTY DAMAGE

V56845

WARNING

RISK OF ELECTRIC SHOCK;

THIS PUMP HAS NOT

BEEN INVESTIGATED FOR

USE IN SWIMMING POOL

AND MARINE AREAS.

-NONSUBMERSIBLE PUMP-

P86313

INSTRUCTION MANUAL 

P81748F

Summary of Contents for Series 100

Page 1: ...ies 100 HV PR and 2 Pumps are listed below Do not exceed these values Maximum Working Pressure 125 psi Maximum Operating Temperature 225ºF Electrical Rating 115V 60 Hz 1PH Motors with special electrical characteristics are available on request Contact your local Bell Gossett Representative for details SAFETY INSTRUCTIONS This safety alert symbol will be used in this manual and on the pump instruct...

Page 2: ...0 F max open the drain valve take precautions against water damage and leave the drain valve open until servicing is complete Failure to follow these instructions could result in serious personal injury death and or property damage 2 Loosen the conduit box cover screw and remove the cover 3 Disconnect the electrical supply lines to the pump WARNING HIGH PRESSURE HAZARD Pressure may be present in t...

Page 3: ...ion and discharge piping with pipe hangers near the pump Line up the vertical and horizontal piping so that the bolt holes in both the pump and pipe flanges are aligned DO NOT ATTEMPT TO SPRING THE SUCTION OR DISCHARGE LINES INTO POSI TION THIS MAY RESULT IN UNWANTED STRESS IN THE PUMP BODY FLANGE CONNECTIONS AND OR PIPING The code for pressure piping ANSI B31 1 lists types of supports for various...

Page 4: ...may cause spillage onto surrounding surfaces Deteriorated motor mounts will lead to misalignment and excessive coupler wear PRIMING AND STARTING Do not run B G circulator pumps dry Before starting the pump must be filled with water Air should be vented from the system by means of a system air vent or by an alternate method 1 Remove the screws securing the conduit box cover wiring compartment and l...