15
MODEL F6C325
F6C425
F6C525
F6C625
Specifications
Capacity 325VA
425VA
525VA
625VA
Voltage
100V, 110V, 120V, ±25%
Frequency
50Hz or 60Hz ±5% (auto sensing)
Voltage
Simulated sine wave at Line Input ±5%
(on battery)
Frequency
50Hz or 60Hz ±0.5%
(on battery)
Voltage
AVR automatically increases output voltage
Regulation
15% above input voltage if -9% to -25% of
AVR
nominal. AVR decreases output voltage
13% below input voltage if +9% to
25% of nominal
Transfer Time
2-4 milliseconds, including detection time
Spike Protection
320 Joules, 2ms
EMI/RFI filter
10dB at 15MHz,
50dB at 30MHz
Overload
UPS automatic shutdown if overload
Protection
exceeds 110% of nominal at 60 second
and 130% at 3 seconds
Unit Input
Fuse for overload and short circuit protection
10Base-T
Network (UTP, RJ45) compatible jacks
Cable Port
(F6C425, F6C525, F6C625)
Short Circuit
UPS output cut off immediately or input
fuse protection
Type
Sealed, maintenance-free lead acid
Typical
4 hours (to 90% of full capacity)
Recharge Time
Protection
Automatic self-test and discharge protection,
replace battery indicator
Back up Time
Depending on computer load...
5-17 min.
5-24 min.
5-32 min.
5-41 min.
Net Weight
4.7(10.4)
5.8(12.8)
6.2(13.7)
6.5(14.3)
Kg(lbs)
Shipping Weight
5.0(11.0)
6.1(13.4)
6.5(14.3)
6.9(15.2)
Kg(lbs)
Dimension(mm) 97
x
260
x
135
97x320x135
WxDxH
Input Inlet
IEC 320 power inlet
Battery
Slow beeping sound (about 0.47Hz)
Back-Up
Battery Low
Rapid beeping sound (about 1.824Hz)
Overload
Continuous beeping sound
RS232
Bi-directional communication port
Interface
(F6C425, F6C525, F6C625)
Safety
cUL, TUV, CE, meet FCC
Surge
Meet IEEE 587 standard
Ambient operation
6,000 meters max. elevation, 0-95% humidity
non-condensing, 0-48˚C
Audible noise
<40dBA (1 meter from surface)
Storage condition
15000 meters max. elevation
INPUT
OUTPUT
PROTECTION AND
FILTERING
BATTERY
PHYSICAL
ALARM
INTERFACE
CONFORMANCE
ENVIRONMENT
14
Storage
11.0 Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its
battery fully charged. Before storing, charge the UPS for at least 4
hours. Disconnect any cables connected to the computer interface
port to avoid unnecessary drainage of the battery.
11.1 Extended Storage
During extended storage in environments where the ambient
temperature is -15˚C to +30˚C (+5˚F to +86˚F), charge the UPS
battery every 6 months.
During extended storage in environments where the ambient
temperature is +30˚C to +45˚C (+86˚F to +113˚F), charge the UPS
battery every 3 months.
PROBLEM
POSSIBLE CAUSE
SOLUTION
Troubleshooting
On/off/test/ button not
pushed or pushed less
than 1 second
Battery voltage less than
10V
Load less than 20W
at battery mode
Power cord loose
AC fuse is burned out
Line voltage too high, too
low or black out
Battery not fully charged
Overload
Battery failure
The UPS continuously
beeps
Press the on/off/test button
more than 1 second
Recharge the UPS at least
4 hours
Normal condition
Replug the power cord
Replace the AC fuse
Normal condition
Recharge the UPS at
least 4 hours
Remove the
noncritical loads
Replace battery
UPS not on
LED not lit
UPS always at
battery mode
Back up time too short
RED LED lit