background image

1

Installation

Each ZIP Economizer module is designed with a unique form fi t which allows it 

to fi t only in one location on the ECON-ZIP-BASE. 

Insert the ECON-ZIP-EM module in the center designated slot of the ZIP 

Economizer base unit. Illustration located below for location.

Press fi rmly to lock the module in place – you will hear a snap. 

MOUNTING INSTRUCTION

ZIP Economizer

 Energy Module

Technical Data

Type

Name

Description

Electrical Specifi cation

Input

CO2 +/-

CO2 sensor 
input

0-10 VDC
Sensor auto-detection

Output

IF

Indoor fan 
low speed 
enable

100'000 cycles @ inrush current 
of 3A, normal current 1.5A
Impedance for Auto detection 
@24 V:
<600 

Ω

 @ 60Hz

<800 

Ω

 @ 50Hz 

Output

EF

Exhaust fan 
enable

100'000 cycles @ inrush current 
of 3A, normal current 1.5A 
Impedance for Auto detection 
@ 24 V:
<600 

Ω

 @ 60Hz

<800 

Ω

 @ 50Hz

Input

AUX1 ±

Auxiliary input
Purge contact 
input

On/Off, 24 VAC, 50/60 Hz
Current load min. 10mA

Input

AUX2 ±

Auxiliary input
Remote 
Potentiometer 
Input

2-10 VDC

ECON-ZIP-EM

Removal of ECON-ZIP-EM

Insert a fl at head screw driver into the latch of the module. Apply light 

pressure on the latch away from the base unit. Lift up to remove.