VRP-M VAV
Overview of the system
2 / 28
Product information S4-VRP-M VAV • en • v2.0 • 11.2006 • Subject to changes
www.belimo.eu
Pressure sensors for
static differential pressure measurement
VFP-100
VFP-300
VFP-600
Pressure range
0 ... 100 Pa
0 ... 300 Pa
0 ... 600 Pa
Medium
– Slightly dusty air
– Very dusty air
– Corrosive gases
●
●
*
●
●
*
●
●
*
Power supply
From VRP-M
From VRP-M
From VRP-M
VRP-M connection
Ready to connect
Ready to connect
Ready to connect
* For a list of sensor materials that come into contact with the medium,
see «Technical data» for the VFP-.., page 19
Damper actuators
NMQB24-SRV-ST
NM24A-V-ST
Torque
4 Nm
10 Nm
Speed
< 5 s
110 ... 150 s
Power supply
From VRP-M
From VRP-M
VRP-M connection
Ready to connect
Ready to connect
VAV functions
Application
Volumenstrom
VAV / CAV
Pressure
STP
VAV:
min
...
max
●
CAV:
min
/
mid
/
max
●
Override functions:
Open – closed
●
Extraction systems
●
Laboratory exhaust systems
●
Bus integration
●
●
Fan optimisation
●
Modulating pressure:
P
min
… P
max
●
Stepped pressure: P
min
/ P
max
●
Override functions OPEN / CLOSE
●
Motor stop function
●
System components
VRP-M control solution
VRP-M
VAV / CAV
STP
Power supply
AC/DC 24 V
AC/DC 24 V
Modulating control
0 ... 10 / 2 ... 10 V
0 ... 10 / 2 ... 10 V
0 ... 20 / 4 ... 20 mA
0 ... 20 / 4 ... 20 mA
Stepped control
Contacts, switches
Contacts, switches
Bus function
MP
BUS
®
TECHNOLOGY BY BELIMO
MP
BUS
®
TECHNOLOGY BY BELIMO
– Optimiser COU24-A-MP
●
– L
ON
W
ORKS
®
integration
●
●
– EIB/Konnex integration
●
●
Settings, diagnostics
VRP-M-Tool
VRP-M-Tool