Wiring for Multiple SY

On/Off, 24V, 120/230V

Actuators:    SY4...5-24     SY4...12-110     SY4...12-220

800-543-9038 

USA

866-805-7089 

CANADA

203-791-8396 

LATIN AMERICA

12

Wiring for Multiple SY
On/Off, 24V, 120/230V

Observe class 1 and class 2 wiring restrictions.
Transformer sizing = SY actuator draw X 1.25 (safety margin)
(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 
3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause irreversible damage to the 

actuator(s) or associated equipment.

Equipment damage!

Power consumption and input impedance must be observed. 

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in 

minor or moderate injury. It may also be used to alert against unsafe practices.

Warnings and Cautions appear at appropriate sections throughout this 

manual. Read these carefully.

Hazard Identification

INSTALLATION NOTES

24 VAC Transformer

Line 

Volts

 G     Ground

 1     Common

 3     Open
 4     Closed
 5     
 6     
 7     

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY4…5-24

 G     Ground

 1     Common
 3     Open
 4     Closed

 5     
 6     
 7     

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY4…5-24

K1

Open

Close

K1-B

K1-A

Actuator A

Actuator B

 G     Ground

 1     Common

 3     Open
 4     Closed
 5     
 6     
 7     

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

 G     Ground

 1     Common

 3     Open
 4     Closed

 5     
 6     
 7     

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY4…12-110 (220)

SY4…12-110 (220)

Open

Close

K1-B

K1-A

Actuator A

Actuator B

120 and 230 VAC

N L1

H L2

NOTES

•  

Caution:

 Power Supply Voltage.

•  Isolation relays must be used in parallel connection of multiple actuators 

    using a common control signal input.
•  "H" (L2) cannot be connected to terminal #3 and #4 simultaneously.
•  

Required: 

Terminal #7 needs to be field wired to enable heater circuit.

G

G

G

K1

G

Actuators:   SY4...5-24       SY4...12-110       SY4...12-220 

71150-00001.D

  01/17

 - 

Subject

 to

 change.

 ©

 Belimo

 Ai

rcontrols 

(USA

), 

Inc

.

71

90

6-

00

00

1  S

ub

je

ct t

o c

ha

ng

e. © B

el

im

o A

irc

on

tro

ls (

US

A)

, I

nc

.

Reviews: