Installation VAV-Compact Retrofit-Set

de

Installation VAV-Compact Retrofit-Set

en

Funktionskontrolle

Functional check

Nach erfolgter Einstellung wird empfohlen, eine Funktionskontrolle 

der VAV-/CAV-Box durchzuführen. Dazu wird der VAV-Regler mit 

dem ZTH-GEN auf den gewünschten Betriebsmode gesetzt und der 

Soll-/Istwert verglichen.

After the adjustment has been completed, it is recommended that a 

functional check be carried out on the VAV/CAV unit. The VAV controller 

is set to the desired operating mode with the ZTH-GEN and a 

setpoint/actual value comparison is made.

ZTH-GEN Stufenwahl

Volumen

400 m3/h

Stufe

>max<

Verfügbare Stufen ZU / 

min

 / 

max

 / Motorstop / AUF

ZTH-GEN Stage selection

Volume

400 m3/h

Stage

>max<

Available stages CLOSED / 

min

 / 

max

 / Motor stop / OPEN

Mögliche Fehlerursachen

Wird der Sollwert nicht erreicht, kann dies folgende Gründe haben:

– Kein Volumenstrom bzw. negativer ∆p-Wert:

→ Druckschläuche falsch angeschlossen

→ Drehrichtung falsch eingestellt

→ Brandschutzklappe geschlossen

– Ist-Volumenstrom zu tief:

→ Vordruck zu tief (Vordruckregelung, FU-Einstellung, Ventilatorleistung 

zu klein)

→ Klappenachse ist mit einem Offset montiert 

(Klappe lässt sich nicht ganz öffnen)

Possible sources of errors

– No volumetric flow or negative ∆p value, respectively:

→ Pressure hoses incorrectly connected

→ Direction of rotation set incorrectly

→  Fire damper closed

– Actual volumetric flow is too low:

→ Supply pressure too low (supply pressure control, FU setting, 

air performance too low)

→ Damper spindle is mounted with an offset 

(damper cannot be opened all the way)

Erweiterte Energiesparmassnahme

Extended energy-savings measure

Einzelraumregelung 

Fan Optimiser-System

Erweiterte Energiesparmassnahmen und Komfortsteigerungen lassen 

sich durch den Einsatz der BELIMO-Einzelraumregler CR24.. sowie 

durch die Integration der VAV-Anlage in ein Fan Optimiser-System 

erzielen.

Single room control 

Fan Optimiser System

Extended energy savings measures and comfort enhancements 

can be achieved through the utilisation of the BELIMO single room 

controller CR24.. and through the integration of the VAV system in a 

Fan Optimiser System.

Detaillierte Informationen zu diesen Komponenten und Systemen finden 

Sie auf der BELIMO-Webseite www.belimo.eu oder wenden Sie sich an 

Ihre lokale BELIMO-Vertretung.

You will find more detailed information on these components and 

systems at the BELIMO web site www.belimo.eu or consult your local 

BELIMO representative.

Summary of Contents for NMV-D3-RE2-SET

Page 1: ...le the TypeList This simplifies the conversion sequence and reduces the amount of time required for its completion Packungsinhalt Package contents 1 VAV Regler NMV D3 RE2 1 VAV controller NMV D3 RE2 2...

Page 2: ...n die Angaben der Klappenhersteller Querschnitt Bauart Einbauort sowie die lufttechnischen Bedingungen beachtet werden When calculating the required torque the specifications supplied by the damper ma...

Page 3: ...surement recording is positioned in an area of turbulence or if no sufficiently wide ranging flow takes place then measurement inaccuracies could occur under certain circumstances D 100 250 D 280 400...

Page 4: ...werden kann Preparations 1 Shorten the pick up device to the diameter of the VAV unit The auxiliary template is located on the packaging of sets Note The specified lengths must be maintained without f...

Page 5: ...ng darf die vordere Befestigungslasche unter keinen Umst nden verwendet werden Abbildung 3 Eine Besch digung des VAV Box und oder des VAV Reglers w re die Folge Spindle clamp installation The VAV cont...

Page 6: ...angle of rotation limiter The two mechanical end stops for angle of rotation limiting must be tailored to the conditions of the VAV unit and are therefore to be adjusted very carefully The dismantled...

Page 7: ...rot U Y 3 U Y weiss F hrungssignal VAV CAV 5 U Y orange Istwertsignal MP Bus Anschluss Note Supply via safety isolation transformer Connections 1 2 AC DC 24 V and 5 MP signal must be routed to access...

Page 8: ...oder via lokale Belimo Vertretung F r Luftgeschwindigkeiten bis 12 m s For air velocities up to 12 m s F r Luftgeschwindigkeiten bis 6 m s For air velocities up to 6 m s TypeList Bezeichnung Designati...

Page 9: ...125 VAV Retrofit Vxx ZPD 12 m s 125 ZPD 12 m s 125 Write ZPD 12 m s 125 Write OK Type Position Address Serial number Type Firmware Type Designation min new 0 m3 h 125 m3 h max new 551 m3 h 400 m3 h 0...

Page 10: ...om Messstab ZPD Seite 8 Luftgeschwindigkeit bis 6 m s 38 Pa Luftgeschwindigkeit bis 12 m s 150 Pa nom gem ss Tabelle Messstab ZPD Seite 8 min siehe oben nom p nom Manual setting For ZTH GEN preparatio...

Page 11: ...llung Ventilatorleistung zu klein Klappenachse ist mit einem Offset montiert Klappe l sst sich nicht ganz ffnen Possible sources of errors No volumetric flow or negative p value respectively Pressure...

Page 12: ...www belimo eu...

Reviews: