Technical data sheet

NM24A-MP

www.belimo.com

NM24A-MP • en-gb • 2020-12-14 • Subject to change

1 / 7

Communicative damper actuator for adjusting 
dampers in technical building installations

• Air damper size up to approx. 2 m²
• Torque motor 10 Nm
• Nominal voltage AC/DC 24 V
• Control modulating, communicative 2...10 V

 

variable

• Position feedback 2...10 V variable
• Conversion of sensor signals
• Communication via Belimo MP-Bus

Technical data

Electrical data Nominal voltage

AC/DC 24 V

Nominal voltage frequency

50/60 Hz

Nominal voltage range

AC 19.2...28.8 V / DC 21.6...28.8 V

Power consumption in operation

3.5 W

Power consumption in rest position

1.4 W

Power consumption for wire sizing

6 VA

Connection supply / control

Cable 1 m, 4 x 0.75 mm²

Parallel operation

Yes (note the performance data)

Functional data Torque motor

10 Nm

Torque variable

25%, 50%, 75% reduced

Communicative control

MP-Bus

Operating range Y

2...10 V

Input Impedance

100 kΩ

Operating range Y variable

Start point 0.5...30 V
End point 2.5...32 V

Options positioning signal

Open/close
3-point (AC only)
Modulating (DC 0...32 V)

Position feedback U

2...10 V

Position feedback U note

Max. 0.5 mA

Position feedback U variable

Start point 0.5...8 V
End point 2.5...10 V

Position accuracy

±5%

Direction of motion motor

selectable with switch 0/1

Direction of motion note

Y = 0 V: At switch position 0 (ccw rotation) / 1 (cw

 

rotation)

Direction of motion variable

electronically reversible

Manual override

with push-button, can be locked

Angle of rotation

Max. 95°

Angle of rotation note

can be limited on both sides with adjustable 
mechanical end stops

Running time motor

150 s / 90°

Running time motor variable

43...173 s

Adaptation setting range

manual

Adaptation setting range variable

No action
Adaptation when switched on
Adaptation after pushing the gear disengagement 
button

Override control

MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, AC only) = 50%

Summary of Contents for NM24A-MP

Page 1: ...nicative control MP Bus Operating range Y 2 10 V Input Impedance 100 k Operating range Y variable Start point 0 5 30 V End point 2 5 32 V Options positioning signal Open close 3 point AC only Modulati...

Page 2: ...solation or aggressive gases interfere directly with the device and that it is ensured that the ambient conditions remain within the thresholds according to the data sheet at any time Only authorised...

Page 3: ...osition defined by the positioning signal A range of settings can be adapted using the PC Tool see MFT P documentation Accessories Gateways Description Type Gateway MP zu BACnet MS TP UK24BAC Gateway...

Page 4: ...ration for flat installation ZG NMA Service tools Description Type Adapter for Service Tool ZTH MFT C Belimo PC Tool Software for adjustments and diagnostics MFT P Service Tool with ZIP USB function f...

Page 5: ...Functions with basic values conventional mode Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch Control remotely 0 100 with positioner SG Minimum limi...

Page 6: ...relay contacts Override control and limiting with AC 24 V with rotary switch 1 Caution This function is only guaranteed if the start point of the operating range is defined as min 0 5 V Control open...

Page 7: ...rawings Clamping range Option Accessory K NA Option Shaft clamp mounted below accessories K NA needed Min 40 Min 20 Further documentation Overview MP Cooperation Partners Tool connections Introduction...

Reviews: