Description

Type

Service Tools

  Service tool for parametrisable and communicative Belimo actuators / 

VAV controller and HVAC performance devices

ZTH EU

 

 

Belimo PC-Tool, software for adjustments and diagnostics

MFT-P

 

 

Adapter to Service Tool ZTH

MFT-C

Electrical installation

!

Notes

•  Connection via safety isolating transformer.

•  The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in 

accordance with applicable RS485 regulations.

•  Modbus / BACnet: Supply and communication are not galvanically isolated. 

Connect earth signal of the devices with one another.

Wiring diagrams

BACnet MS/TP / Modbus RTU

1

2

3

5

6

7

D+

D

 

~

T

AC/DC

 

24

 

V

D+

D

 

1

2

3

5

6

7

D+

D

 

~

T

AC/DC

 

24

 

V

GND

Cable colours:

 

1= black 

2 = red 

3 = white 

5 = orange 

6 = pink 

7 = grey

Signal assignement Modbus: 

C1 = D– = A 

C2 = D+ = B

Connection with passive sensor, e.g. Pt1000, Ni1000, NTC  

1

2

~

T

3

5

6

7

Ni1000

PT1000

NTC

–28...+98°C

–35...+155°C

–10...+160°C

 1)

850...1600 Ω

 2)

850...1600 Ω

 2)

200 Ω...60 kΩ

 2)

MFT

D+

D

 

D–
D+

1) depending on type 

2) Resolution 1 Ohm

Connection with active sensor, e.g. 0...10 V @ 0...50°C

1

2

~

T

3

5

6

7

MFT

D+

D

 

-

D-
D+

Possible voltage range:

0...32 V (resolution 30 mV)

NM24A-MOD

Damper actuator, modulating

communicative

hybrid mode, AC/DC 24 V, 10 Nm,

Accessories

www.belimo.com

NM24A-MOD • en-gb • 2018-04-26 • subject to changes

4

Summary of Contents for NM24A-MOD

Page 1: ...ectable with switch 0 1 Direction of motion note Y 0 At switch position 0 for ccw rotation or 1 for cw rotation respectively Direction of motion variable electronically reversible Manual override with...

Page 2: ...tioning signal from the control system and returns the current status Converter for sensors Connection option for a sensor passive active or with switching contact In this way the analogue sensor sign...

Page 3: ...8 kOhm add on P2800A Feedback potentiometer 2 8 kOhm add on grey P2800A GR Feedback potentiometer 5 kOhm add on P5000A Feedback potentiometer 5 kOhm add on grey P5000A GR Feedback potentiometer 10 kOh...

Page 4: ...arth signal of the devices with one another Wiring diagrams BACnet MS TP Modbus RTU 1 2 3 5 6 7 D D T AC DC24V D D 1 2 3 5 6 7 D D T AC DC24V GND Cable colours 1 black 2 red 3 white 5 orange 6 pink 7...

Page 5: ...current of 16 mA 24 V Modbus RTU BACnet MS TP with analog setpoint hybrid mode D D 1 2 3 5 6 7 D D T AC DC24V GND Y U DC 0 2 10 V DC 2 10 V Operation on the MP Bus 1 2 3 5 6 D 7 D T Y U Sensor MP MFT...

Page 6: ...e tools Check power supply connection 2 Off and 3 On Possiple wiring error in power supply Service Quick adressing 1 Press the Address button until the green Power LED is no longer illuminated LED fla...

Page 7: ...her documentation Tool connections Description Protocol Implementation Conformance Statement PICS Description Modbus register Overview MP Cooperation Partners MP Glossary Introduction to MP Bus Techno...

Reviews: