Belimo NM24A-MOD Technical Data Sheet Download Page 3

Home position

The first time the supply voltage is switched on, i.e. at the time of commissioning, the 

actuator carries out a synchronisation. The synchronisation is in the home position 

(0%).

The actuator then moves into the position defined by the positioning signal.

Y = 0%

cw

Y  =  0%

ccw

1

0

Adaption and synchronisation

An adaption can be triggered manually by pressing the “Adaption” button or with the 

PC-Tool. Both mechanical end stops are detected during the adaption (entire setting 

range).

Automatic synchronisation after pressing the gearbox disengagement button is 

configured. The synchronisation is in the home position (0%).

The actuator then moves into the position defined by the positioning signal.

A range of settings can be adapted using the PC-Tool (see MFT-P documentation)

Accessories

Description

Type

Electrical accessories

  Auxiliary switch, add-on, 1 x SPDT

S1A

 

 

Auxiliary switch, add-on, 2 x SPDT

S2A

 

 

Feedback potentiometer 140 Ohm, add-on

P140A

 

 

Feedback potentiometer 140 Ohm, add-on, grey

P140A GR

 

 

Feedback potentiometer 200 Ohm, add-on

P200A

 

 

Feedback potentiometer 500 Ohm, add-on

P500A

 

 

Feedback potentiometer 500 Ohm, add-on, grey

P500A GR

 

 

Feedback potentiometer 1 kOhm, add-on

P1000A

 

 

Feedback potentiometer 1 kOhm, add-on, grey

P1000A GR

 

 

Feedback potentiometer 2.8 kOhm, add-on

P2800A

 

 

Feedback potentiometer 2.8 kOhm, add-on, grey

P2800A GR

 

 

Feedback potentiometer 5 kOhm, add-on

P5000A

 

 

Feedback potentiometer 5 kOhm, add-on, grey

P5000A GR

 

 

Feedback potentiometer 10 kOhm, add-on

P10000A

 

 

Feedback potentiometer 10 kOhm, add-on, grey

P10000A GR

 

 

Connecting cable 5 m, A+B: RJ12 6/6, To ZTH EU

ZK1-GEN

 

 

Connection cable 5 m, A: RJ11 6/4, B: Free wire end, To ZTH EU

ZK2-GEN

Description

Type

Mechanical accessories

  Actuator arm, for one-sided spindle clamp K-ENSA

AH-25

 

 

Shaft extension 240 mm, for damper spindles  Ø 8...25 mm or  Ø 

10...25 mm

AV8-25

 

 

Angled ball joint with M8, suitable for damper crank arm KH8

KG8

 

 

Straight ball joint with M8, suitable for damper crank arm KH8

KG10A

 

 

Damper crank arm, for damper spindles

KH8

 

 

Spindle clamp, one side for NM..A

K-ENMA

 

 

Spindle clamp, one side for NM..A, SM..A

K-ENSA

 

 

Spindle clamp, reversible for NM..A and LMQ..

K-NA

 

 

Form fit insert 8x8 mm, for NM..A

ZF8-NMA

 

 

Form fit insert 10x10 mm, for NM..A / SM..A

ZF10-NSA

 

 

Form fit insert 12x12 mm, for NM..A / SM..A

ZF12-NSA

 

 

Form fit insert 15x15 mm, for NM..A / SM..A

ZF15-NSA

 

 

Form fit insert 16x16 mm, for NM..A / SM..A

ZF16-NSA

 

 

Mounting kit for linkage operation, NM..A for flat installation

ZG-NMA

 

 

Anti-rotation mechanism 180 mm

Z-ARS180

 

 

Base plate extension from NM..A to NM..

Z-NMA

 

 

Position indication for LM..A, NM..A, SM..A, GM..A

Z-PI

NM24A-MOD

Damper actuator, modulating

communicative

hybrid mode, AC/DC 24 V, 10 Nm,

Product features

www.belimo.com

NM24A-MOD • en-gb • 2018-04-26 • subject to changes

3

Summary of Contents for NM24A-MOD

Page 1: ...ectable with switch 0 1 Direction of motion note Y 0 At switch position 0 for ccw rotation or 1 for cw rotation respectively Direction of motion variable electronically reversible Manual override with...

Page 2: ...tioning signal from the control system and returns the current status Converter for sensors Connection option for a sensor passive active or with switching contact In this way the analogue sensor sign...

Page 3: ...8 kOhm add on P2800A Feedback potentiometer 2 8 kOhm add on grey P2800A GR Feedback potentiometer 5 kOhm add on P5000A Feedback potentiometer 5 kOhm add on grey P5000A GR Feedback potentiometer 10 kOh...

Page 4: ...arth signal of the devices with one another Wiring diagrams BACnet MS TP Modbus RTU 1 2 3 5 6 7 D D T AC DC24V D D 1 2 3 5 6 7 D D T AC DC24V GND Cable colours 1 black 2 red 3 white 5 orange 6 pink 7...

Page 5: ...current of 16 mA 24 V Modbus RTU BACnet MS TP with analog setpoint hybrid mode D D 1 2 3 5 6 7 D D T AC DC24V GND Y U DC 0 2 10 V DC 2 10 V Operation on the MP Bus 1 2 3 5 6 D 7 D T Y U Sensor MP MFT...

Page 6: ...e tools Check power supply connection 2 Off and 3 On Possiple wiring error in power supply Service Quick adressing 1 Press the Address button until the green Power LED is no longer illuminated LED fla...

Page 7: ...her documentation Tool connections Description Protocol Implementation Conformance Statement PICS Description Modbus register Overview MP Cooperation Partners MP Glossary Introduction to MP Bus Techno...

Reviews: