2

 Accessories 

K-NA

Reversible Clamp

AV8-25

Universal Shaft Extension

ZG-NMA

Shaft Adaptor

ZG-LMSA-1

Shaft Adaptor for 

³⁄₈

” Diameter Shafts

ZS-100

Weather Shield - Steel

ZS-150

Weather Shield - Polycarbonate

Tool-06

8 mm & 10 mm Wrench

S1A, S2A

Auxiliary Switch (es)

P370

Shaft Mount Auxiliary Switch

P…A

Feedback Potentiometers

SGA24

Min positioners in NEMA 4 housing

SGF24

Min positioners for flush panel mounting

ADS-100

Analog to Digital Switch

ZG-R01

Resistor for 4 to 20 mA Conversion

NSV24 US

Battery Back-Up Module

ZG-X40

Transformer

NOTE: When using LMQB(X)24-MFT actuators, only use 
accessories listed on this page.

 LMB(X)24-MFT Typical Specification

Proportional control damper actuators shall be electronic direct-coupled 
type, which require no crankarm and linkage and be capable of direct 
mounting to a shaft from ¼” to 

⁵⁄₈

”. Actuators must provide control in 

response to a control input from an electronic controller or positioner. 
Actuators shall have Brushless DC motor technology and be protected 
from overload at all angles of rotation. Actuators shall have reversing 
switch and manual override on the cover. Run time shall be constant and 
independent of torque. Actuators shall be cULus listed, have a 5-year 
warranty, and be manufactured under ISO 9001 International Quality 
Control Standards. Actuators shall be as manufactured by Belimo.

 Wiring  Diagrams

PWM

VDC/4-20 mA

On/Off

24 VAC Transformer (AC only)

Line

Volts

Position

Feedback VDC

1

2

4

1 Blk 

Common

2 Red 

+ Hot

3 Wht 

Y Input

5 Org 

U Output

…MFT

24 VAC/DC Transformer

Line

Volts

Position

Feedback VDC

1

3

2

1 Blk 

Common

2 Red 

Hot

3 Wht 

Y Input

5 Org 

U Output

a

…MFT

24 VAC Transformer

1

Line

Volts

Control Signal

4 to 20 mA or 2 to 10 VDC

1 Blk 

Common

2 Red 

+ Hot

3 Wht 

Y

1

 Input,

 

2 to 10V

5 Org 

U Output,

 

2 to 10V

2

3

5

…MFT

500 

Ω

¼ watt

Ω

Provide overload protection and disconnect as required.

Actuators may be connected in parallel if not mechanically 
mounted    to the same shaft.  Power consumption and input 
impedance must  be observed.

Actuators may also be powered by 24 VDC.

Control signal may be pulsed from either the Hot (Source)  or 
Common (Sink) 24 VAC line.

ZG-R01 may be used.