Technical Data

LMB(X)24-MFT

Power supply

24 VAC ± 20% 50/60 Hz
24 VDC ± 10%

Power consumption

2.5 W (1.2 W)

Transformer sizing

5 VA (Class 2 power source)

Electrical connection

18 GA plenum rated cable
1/2” conduit connector
Protected NEMA 2 (IP54)
3 ft [1m]  10 ft [3m]  16 ft [5m]

Overload protection

electronic throughout 0 to 95° rotation

Operating range Y

2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, fl oating point, on/off)

Input impedance

100 k

Ω

 (0.1 mA), 500 

Ω

1500

Ω

 (PWM, fl oating point, on/off)

Feedback output U

2 to 10 VDC, 0.5mA max
VDC variable

Angle of rotation

max. 95°, adjustable with mechanical stop
electronically variable

Torque

45 in-lb [5 Nm]

Direction of rotation

reversible with

switch

Position indication

reflective visual indicator (snap-on)

Manual override

external push button

Running time

150 seconds (default)
variable (35 to 150 seconds)

Humidity

5 to 95% RH non condensing (EN 60730-1)

Ambient temperature

-22°F to 122°F [-30°C to 50°C]

Storage temperature

-40°F to 176°F [-40°C to 80°C]

Housing

NEMA 2, IP54, UL enclosure type 2

Housing material

UL94-5VA

Agency listings

cULus acc. to UL 60730-1A/-2-14, 
CAN/CSA E60730-1:02,
CE acc. to 2004/108/EEC and 2006/95/EC

Noise level

<35dB(A)

Servicing

maintenance free

Quality standard

ISO 9001

Weight

1.5 lbs  [0.7 kg]

LMB(X)24-MFT

Proportional, Non-Spring Return, 24 V, Multi-Function Technology

®

Torque min. 45 in-lb for control of damper surfaces up to 11 sq ft.

Application

For proportional modulation of dampers in HVAC systems. Actuator sizing should be
done in accordance with the damper manufacturer’s specifications.

The actuator is mounted directly to a damper shaft from 1/4” up to 5/8” in diameter
by means of its universal clamp.  Shafts up to 3/4” diameter can be accommodated by
an accessory clamp.

The default parameters for 2 to 10 VDC applications of the …MFT actuator are
assigned during manufacturing. If necessary, custom versions of the actuators can be
ordered. The parameters can be changed by two means: pre-set and custom
configurations from Belimo or on-site configurations using the Belimo PC-Tool
software.

Operation

The actuator is not provided with and does not require any limit switches, but is
electronically protected against overload.  The anti-rotation strap supplied with the
actuator will prevent lateral movement.

The LMB(X) series provides 95° of rotation and a visual indicator indicates position of
the actuator.  When reaching the damper or actuator end position, the actuator
automatically stops.  The gears can be manually disengaged with a button on the
actuator cover.

The LMB(X)24-MFT… actuators use a brushless DC motor, which is controlled by an
Application Specific Integrated Circuit (ASIC).  The ASIC monitors and controls the
actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent
damage to the actuator in a stall condition.  Power consumption is reduced in holding
mode.

Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto
the actuator body for signaling and switching functions.

Dimensions

 (Inches [mm])

4.57" [116]

3.47" [88]

2" [50.8]

0.86" [22]

2

.3

4" [5

9

.4

]

2

.6

" [

66]

1/4” to 3/4” [6 to 20] 

5/16” to 3/4” [8 to 26]

D141

M

40024 - 05/10 - Subject to change.