background image

800-543-9038 

USA

866-805-7089 

CANADA

203-791-8396 

LATIN AMERICA

294

Accessories 

K-LM20

3/4” [20 mm] Shaft Clamp

AV6-20

Shaft Extension

ZG-LMSA

Shaft Adaptor for 1/2” Diameter Shafts

ZG-LMSA-1

Shaft Adaptor for 3/8” Diameter Shafts

ZS-100

Weather Shield - Steel

ZS-150

Weather Shield - Polycarbonate

Tool-06

8 mm & 10 mm Wrench

S1A, S2A

Auxiliary Switch(es)

P370

Shaft Mount Auxiliary Switch

P…A

Feedback Potentiometers

SGA24

Min positioners in NEMA 4 housing

SGF24

Min positioners for flush panel mounting

ADS-100

Analog to Digital Switch

ZG-R01

Resistor for 4 to 20 mA Conversion

NSV24 US

Battery Back-Up Module

ZG-X40

Transformer

NOTE:

   When using LMB(X)24-MFT actuators, only use accessories listed on this page.

Typical Specification

Proportional control damper actuators shall be electronic direct-coupled type, which
require no crank arm and linkage and be capable of direct mounting to a shaft from 
1/4” to 5/8”. Actuators must provide control in response to a control input from an
electronic controller or positioner. Actuators shall have brushless DC motor technology
and be protected from overload at all angles of rotation. Actuators shall have
reversing switch and manual override on the cover. Run time shall be constant and 
independent of torque. Actuators shall be cULus listed, have a 5-year warranty, and be
manufactured under ISO 9001 International Quality Control Standards. Actuators shall 
be as manufactured by Belimo.

Wiring Diagrams

1

Provide overload protection and disconnect as required.

2

CAUTION 

Equipment Damage!

Actuators may be connected in parallel if not mechanically mounted to the same
shaft. Power consumption and input impedance must be observed.

3

Actuators may also be powered by 24 VDC.

4

Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.

5

Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.

8

Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.

9

For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.

The ZG-R01 500

Ω

 resistor may be used.

WARNING

 Live Electrical Components!

G

  During installation, testing, servicing and troubleshooting of this product, it may be

necessary to work with live electrical components.  Have a qualifi ed licensed electrician or other 
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
nents could result in death or serious injury.

W

399_0

8

VDC/4-20 mA

W399_08

PWM

M

W399_08

On/Off control

Off

l

W399_08

Floating Point control

LMB(X)24-MFT

Proportional, Non-Spring Return, 24 V, Multi-Function Technology

®

 M40024 - 05/10 - Sub

ject to chan

g

e.

 © Belimo 

Aircontrols 

(USA

), Inc.