background image

GM

105

G20492-Subject to change. © Belimo Aircontrols (USA), Inc.

®

Accessories
IRM-100

Input scaling module

KH8

Universal crankarm

KG10 Ball 

Joint

NSV24

Battery back-up module

P…

Feedback potentiometer

PTA-250

Pulse width modulation interface

SGA24

Min. and/or manual positioner in NEMA 4 housing

SGF24

Min. and/or man. positioner for flush panel mount

S1,S2

Auxiliary switch

Tool-06

8mm and 10 mm wrench

ZAD24

Digital position indication

ZDB-GM

Angle of rotation limiter (Series 2)

ZG-H2

Actuator operator handle

ZG-GM2

Crankarm adaptor kit

ZG-R01

500

resistor for 4 to 20 mA

ZG-100

Universal mounting bracket

ZG-101

Universal mounting bracket

ZG-102

Multiple actuator mounting bracket

ZG-103 

Universal mounting bracket

ZG-104

Universal mounting bracket

ZS-100 

Weather shield (metal)

ZS-150

Weather shield (polycarbonate)

ZS-260

Explosion-proof housing

ZS-300

NEMA 4X housing

NOTE: When using GM24-SR US actuators, use only 

the accessories listed on this page.  

Wiring diagrams

GM24-SR US - Typical Specification:
Control damper actuators shall be electronic direct coupled
type which require no crankarm and linkage.  Actuators shall
be UL listed and CSA certified, have a 2 year warranty, and
be manufactured under ISO 9001 International Quality Control
Standards.  Actuators shall have reversing switch and gear
disengagement button on the cover.  Actuators shall use a
brushless DC motor and be protected from overload at all
angles of rotation.  Run time shall be constant and independ-
ent of torque.  The actuator must provide proportional damper
control in response to a 2 to 10 VDC or, with the addition of a
500

resistor, a 4 to 20 mA control input from an electronic

controller or positioner.   A 2 to 10 VDC feedback signal shall
be provided for position indication or master-slave applica-
tions.  Actuators shall be as manufactured by Belimo.

2

1

Provide overload protection and disconnect as required.

Actuators may be connected in parallel.  Power con-
sumption and input impedance must be observed.

4 to 20 mA control of GM24-SR US with 2 to 10 VDC feed-
back output.  

0 to 10 VDC control of GM24-SR US 

2

1

3

Provide overload protection and disconnect as required.

Connect actuator common (wire 1) to negative (–) leg
of control circuits only.

Up to 4 actuators may be connected in parallel.  With 4
actuators wired to one 500

resistor, a +2% shift of

control signal may be required.  Power consumption
must be observed.

The 500

resistor converts the 4 to 20 mA control sig-

nal to 2 to 10 VDC.  

Actuator may also be powered by 24 VDC.

4

5

GM24-SR US

Proportional damper actuator, non-spring return, direct coupled, 

24 V for 2 to 10 VDC and 4 to 20 mA control signal.

Multiple actuators mounted to shaft

Model

Maximum quantity per shaft

GM24 US

2

GM24-SR US

2

Control Signal  (+)

2 to 10 VDC       

(–)

1  Common

2  + Hot

3  Y  Input, 

2 to 10V

 

5  U  Output 

2 to 10V

1

2

24 VAC Transformer

A

GM24-SR US

Line  
Volts

1

1  Common

2  + Hot

3  Y  Input, 

2 to 10V

5  U  Output 

2 to 10V

1

24 VAC Transformer

2

5

4

3

A

GM24-SR US

Control Signal  (+)

0 to 20 mA       

(–)

Feedback Signal  (+)

2 to 10 VDC       

(–)

500

To other 

actuators

Line  
Volts

1

W072

W073