Wiring Diagrams

Meets cULus requirements without the need of an electrical ground 

connection.

UP

Universal Power Supply (UP) models can be supplied with 24 VAC up to 

240 VAC, or 24 VDC up to 240 VDC.

Disconnect power.

Provide overload protection and disconnect as required.

Two built-in auxiliary switches (2x SPDT), for end position indication, 

interlock control, fan startup, etc.

Only connect common to negative (-) leg of control circuits.

46

Actuators may be controlled in parallel. Current draw and input 

impedance must be observed.

!

WARNING! LIVE ELECTRICAL COMPONENTS!

During installation, testing, servicing and troubleshooting of this 

product, it may be necessary to work with live electrical components. 

Have a qualified licensed electrician or other individual who has been 

properly trained in handling live electrical components perform these 

tasks. Failure to follow all electrical safety precautions when exposed to 

live electrical components could result in death or serious injury.

 

N               

L                 

Y

1

Y

2

    

Common               

+ Hot               

Input CCW (open)

Input CW (close)

24 to 240 VAC 

or 

24 to 125 VDC

1

UP

46

1

!

On/Off

 

N               

L                 

Y

1

Y

2

    

1

UP

46

!

Common               

+ Hot                

Input CCW (open)

Input CW (close)

24 to 240 VAC 

or 

24 to 125 VDC

Floating Point

 

N               
L                 
Y

1

Y

2

 

N

5

UP

46

24 to 240 VAC

or 

24 to 125 VDC

-
+                 
Y

3

U5

Com -
24 VDC Out (max 5mA)                
Y

3  

0 - 10 VDC, 4-20 mA

U5/MP 0 - 10 VDC

1

Modulating

 

N               
L                 
Y

1

Y

2

 

N

24 to 240 VAC

or

24 to 125 VDC

Com
D +
D -

Com
Bacnet D +               
D -

BACnet

PRBUP-MFT-T

Modulating, Non-Spring Return, 24-240 V, NEMA 4X with BACnet

800-543-9038

 USA

866-805-7089

 CANADA

203-791-8396

 LATIN AMERICA / CARIBBEAN

Date created, 11/29/2017 - Subject to change. © Belimo Air

controls (USA), Inc.

Summary of Contents for F6 Series

Page 1: ...to 24 Type of end fitting ANSI 300 flanges Materials Body Disc Seat Shaft Gland seal Bushings carbon steel full lug 316 stainless steel RPTFE 17 4 PH stainless PTFE glass backed PTFE Media temperature range 20 F to 400 F 30 C to 204 C Body pressure rating ANSI Class 300 Close off pressure 740 psi Rangeability 100 1 for 30 deg to 70 deg range Maximum velocity 32 FPS Leakage bubble tight 2 way Valve...

Page 2: ...9 00 20 00 5 88 8 3 4 10 UNC 150 F680 300SHP 3 1 92 9 00 9 00 20 50 6 63 8 3 4 10 UNC 150 F6100 300SHP 4 2 13 9 00 9 00 21 00 7 88 8 3 4 10 UNC 150 F650 300SHP 2 1 75 9 00 9 00 19 50 5 00 8 5 8 11 UNC 2 GK 400 F665 300SHP 2 1 88 9 00 9 00 20 00 5 88 8 3 4 10 UNC 400 F680 300SHP 3 1 92 9 00 9 00 20 50 6 63 8 3 4 10 UNC 400 F650 300SHP 2 1 75 9 00 9 00 19 50 5 00 8 5 8 11 UNC GM 285 Non Spring Retur...

Page 3: ...dified equal percentage unidirectional Controllable flow range 82 Sizes 2 to 24 Type of end fitting ANSI 300 flanges Materials Body Disc Seat Shaft Gland seal Bushings carbon steel full lug 316 stainless steel RPTFE 17 4 PH stainless PTFE glass backed PTFE Media temperature range 20 F to 400 F 30 C to 204 C Body pressure rating ANSI Class 300 Close off pressure 740 psi Rangeability 100 1 for 30 de...

Page 4: ... 14 15 00 19 62 19 62 36 00 18 75 20 1 1 8 8 UNC SY8 400 SY10 600 F7400 300SHP 16 16 50 21 75 21 75 37 50 21 25 20 1 1 4 8 UNC SY9 285 SY10 400 SY12 600 SY7 150 F7450 300SHP 18 18 00 23 88 23 88 42 25 22 75 24 1 1 4 8 UNC SY10 150 F7 Series 3 Way ANSI Class 300 Butterfly Valve Reinforced Teflon Seat 316 Stainless Disc B C D A Dimensions 4 D104 Dimensions A B and C do not include flange gaskets 3 r...

Page 5: ...hysteresis SY 24MFT 1 0 mA 500mV Feedback SY 24MFT 2 10 VDC Angle of rotation 90 Direction of rotation reversible Position indication top mounted domed indicator Internal humidity control resistive heating element Auxiliary switches factory set for 5 and 85 change of state SY1 2 SPDT min 1 mA 24 VAC max 3A 250 VAC SY4 12 2 SPDT min 1 mA 24 VAC max 5A 250 VAC Ambient temperature 22 F to 150 F 30 C ...

Page 6: ...4 12 2 SPDT min 1 mA 24 VAC max 5A 250 VAC Ambient temperature 22 F to 150 F 30 C to 65 C Humidity range up to 95 Housing type IP67 NEMA 4X Housing material die cast aluminum alloy Agency listings ISO CE cCSAus Note Leakage current is possible 3 5 mA Connect ground before applying voltage Power Supply 120 VAC 50 60Hz single phase Model Torque Speed 60Hz Speed 50Hz Power Consumption Duty Cycle Over...

Page 7: ...bs 58s 70s 2 0A 30 50 Hand Wheel 56kg 123 5 lb SY11 230 MFT 3000Nm 26700 in lbs 58s 70s 1 6A 30 50 Hand Wheel 56kg 123 5 lb SY12 230 MFT 3500Nm 31150 in lbs 58s 70s 2 2A 30 50 Hand Wheel 56kg 123 5 lb Technical Data Electrical connection conduit connector screw terminals Overload protection thermally protected 135 C cut out Motor protection H Class insulation SY 1 F Class SY 2 12 Gear train high a...

Page 8: ... cover removal DIM B DIM C MAX DIM D Inches mm Inches mm Inches mm Inches mm Inches mm SY4 6 12 40 315 8 86 225 9 21 234 14 96 380 11 81 300 SY7 8 16 54 420 8 86 225 9 21 234 17 72 450 13 39 340 SY9 12 23 23 590 8 86 225 10 24 260 18 50 470 13 78 350 SY Series Non Spring Return Actuator Dimensions O50904 02 12 Subject to change Belimo Aircontrols USA Inc ...

Page 9: ... seconds 2 7 A 2 8 A 304 311 324 336 Hand wheel 72 kg 176 4 lbs SY10 110 22130 in lbs 2500 Nm 75 seconds 62 seconds 2 8 A 2 9 A 318 335 336 348 Hand wheel 72 kg 176 4 lbs SY11 110 26550 in lbs 3000 Nm 78 seconds 69 seconds 3 3 A 3 6 A 365 387 396 432 Hand wheel 72 kg 176 4 lbs SY12 110 30980 in lbs 3500 Nm 72 seconds 60 seconds 3 7 A 3 8 A 415 422 444 456 Hand wheel 72 kg 176 4 lbs Power Supply 23...

Page 10: ...A 3 4 A 397 382 432 408 Hand wheel 72 kg 176 4 lbs SY10 120MFT 22130 in lbs 2500 Nm 52 seconds 51 seconds 4 0 A 4 0 A 450 445 480 480 Hand wheel 72 kg 176 4 lbs SY11 120MFT 26550 in lbs 3000 Nm 55 seconds 56 seconds 3 1 A 3 0 A 332 318 372 360 Hand wheel 72 kg 176 4 lbs SY12 120MFT 30980 in lbs 3500 Nm 61 seconds 62 seconds 3 6 A 3 4 A 386 368 432 408 Hand wheel 72 kg 176 4 lbs Power Supply 230 VA...

Page 11: ...d in parallel connection of multiple actuators using a common control signal input H cannot be connected to terminal 3 and 4 simultaneously 24V AC DC Transformer Line Volts Open Close G Ground 1 Common 3 Open 4 Closed 5 6 7 G Ground 1 Common 3 Open 4 Closed 5 6 7 HTR A B C D E F LS3 A C Open Indication LS4 D F Closed Indication Contact Rating 5A 250 VAC Max SY2 5 24 120V or 230V AC DC G Open Close...

Page 12: ...rol panel chassis Tape back ground at actuator NOTES SY2 5 24MFT NOTES SY2 12 120MFT 230MFT s Caution 0OWER SUPPLY VOLTAGE SY2 5 24MFT SY2 12 120MFT 230MFT A B C E F ONTACT 2ATING 6 AX 6 AX PEN NDICATION LS4 LS3 LOSED NDICATION ŏ1 Y U5 C1 ŏ2 C2 B A 1 9 8 10 3 2 ŏ Internal Use Only Internal Use Only Internal Use Only Not Used Control Signal Not Used Internal Use Only Internal Use Only Internal Use ...

Page 13: ...entially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully Hazard Identification INSTALLATION NOTES G Ground 1 Common 3 Open 4 Closed 5 6 7 HTR A B C D E F LS3 A C Open Indication LS4 D F Closed Indication Contact Ratin...

Page 14: ... U5 C1 ŏ2 C2 B A 1 9 8 10 3 2 ŏ Internal Use Only Internal Use Only Internal Use Only Not Used Control Signal Not Used Internal Use Only Internal Use Only Internal Use Only Internal Use Only Power Supply Com Power Supply Hot 24V AC DC Internal Use Only Feedback Control Signal Feedback Signal Feedback Signal Control Signal SYx 24MFT PC Tool Service Jack G PE G PE Actuator B Actuator A Address Adapt...

Page 15: ...ice Jack SYx 120MFT L N Power Supply Com 120 VAC N 230 VAC L1 Power Supply Hot 120 VAC H 230 VAC L2 ŏ1 Y U5 C1 ŏ2 C2 B A 1 9 8 10 3 2 Internal Use Only Internal Use Only Internal Use Only Not Used Control Signal Not Used Internal Use Only Internal Use Only Internal Use Only Internal Use Only Internal Use Only Feedback Control Signal Feedback Signal Feedback Signal Control Signal SYx 230MFT Address...

Page 16: ...h CW CCW mounting Mechanical angle of rotation 95 adjustable with mechanical end stop 35 to 95 Running time motor 75 sec spring 20 sec 4 F to 122 F 20 C to 50 C 60 sec 22 F 30 C Position indication visual indicator 0 to 95 0 is full spring return position Manual override 5 mm hex crank Allen supplied Humidity max 95 RH non condensing Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperatu...

Page 17: ...out the need of an electrical ground con nection WARNING Live Electrical Components G During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical ...

Page 18: ... stop 35 to 95 Running time spring 20 sec 4 F to 122 F 20 C to 50 C 60 sec 22 F 30 C motor 150 seconds default variable 70 to 220 seconds Angle of rotation adaptation off default Override control min position 0 mid position 50 max position 100 Position indication visual indicator 0 to 95 0 is spring return position Manual override 5 mm hex crank Allen supplied Humidity max 95 RH non condensing Amb...

Page 19: ...icing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury AF Actuators Mul...

Page 20: ...on indication visual pointer N4 Manual override internal push button UL Type 4 external push buttom UL Type 2 Running time 150 seconds default Fail Safe 35 seconds Humidity 5 to 100 RH UL Type 4 5 to 95 RH non condensation UL Type 2 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing type UL Type 4 NEMA 4 IP66 UL Type 2 NEMA 2 IP54 Housing material...

Page 21: ...components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury Electrical Installation Wiring diagram Y U 1 3 2 5 T Cable colors 1 black 2 red 3 white 5 orange Cable leng...

Page 22: ...tronically variable Position indication visual pointer N4 Manual override internal push button UL Type 4 external push buttom UL Type 2 Running time 150 seconds default variable 75 to 290 seconds Fail Safe 35 seconds Humidity 5 to 100 RH UL Type 4 5 to 95 RH non condensation UL Type 2 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing type UL Type...

Page 23: ... A B should both be closed for triac source and open for triac sink 10 For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller Position feedback cannot be used with a Triac sink controller The actuator internal common reference is not compatible 12 IN4004 or IN4007 diode IN4007 supplied Belimo part number 40155 The ZG R01 500 Ω resistor conv...

Page 24: ...f rotation 90 Position indication visual pointer Manual override internal push button UL Type 4 external push buttom UL Type 2 Running time 35 seconds default Humidity 5 to 100 RH UL Type 4 5 to 95 RH non condensation UL Type 2 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing type UL Type 4 NEMA 4 IP66 UL Type 2 NEMA 2 IP54 Housing material Poly...

Page 25: ...common reference is not compatible Meets cULus or UL and CSA requirements without the need of an electrical ground connection WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live...

Page 26: ...20 mA 1000 Ω for floating point and on off control Angle of rotation 90 electronically variable Position indication visual pointer Manual override internal push button UL Type 4 external push buttom UL Type 2 Running time DRX 150 seconds DRCX 35 seconds Humidity 5 to 100 RH UL Type 4 5 to 95 RH non condensation UL Type 2 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 17...

Page 27: ...he 4 to 20 mA control signal to 2 to 10 VDC up to 2 actuators may be connected in parallel WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live electrical components perform thes...

Page 28: ... electronically variable Direction of rotation reversible with switch Fail safe position adjustable with dial or tool 0 to 100 in 10 increments Position indication reflective visual indicator snap on Manual override external push button Running time normal operation fail safe 150 seconds default variable 90 to 150 seconds 35 seconds Humidity 5 to 95 RH non condensing EN 60730 1 Ambient temperature...

Page 29: ...o has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury NOTE Wiring diagrams shown are for single actuator mounted solutions Electrical Installation Wiring diagram Y U 1 3 2 5 T Cable colors 1 black 2 red 3 white 5 orange Cable length...

Page 30: ...cal stop electronically variable Direction of rotation reversible with switch Fail safe position adjustable with dial or tool 0 to 100 in 10 increments Position indication reflective visual indicator snap on Manual override external push button Running time normal operation fail safe 95 seconds default variable 90 to 150 seconds 35 seconds Humidity 5 to 95 RH non condensing EN 60730 1 Ambient temp...

Page 31: ...f control Off l W399_Butterfly Floating Point control Wiring Diagrams 1 Provide overload protection and disconnect as required 3 Actuators may also be powered by 24 VDC 4 Position feedback cannot be used with Triac sink controller The actuator internal common reference is not compatible 5 Control signal may be pulsed from either the Hot source or the Common sink 24 VAC line 8 Contact closures A B ...

Page 32: ...tion 95 adjustable with mechanical stop Direction of rotation reversible with protected switch Position indication handle Manual override external push button Running time 95 seconds Humidity 5 to 95 RH non condensing EN 60730 1 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing NEMA 2 IP54 Housing material UL94 5VA Agency listings cULus according...

Page 33: ...ified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury AM AR Series Actuators On Off Floating Point j y 2 3 5 24 VAC Transformer a open a closed Blk 1 Common Red 2 Wht 3 a Line Volts T...

Page 34: ...output U 2 to 10 VDC 0 5 mA max VDC variable Angle of rotation 95 electronically variable Direction of rotation reversible with protected switch Position indication handle Manual override external push button Running time 150 seconds default variable 90 to 350 secs Humidity 5 to 95 RH non condensing EN 60730 1 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to...

Page 35: ...d electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury AM AR Series Actuators Multi Function Technology Blk 1 Common Red 2 Hot Wht 3 Y Input Org 5 U Output Line Volts 24 VAC DC Transformer a Positi...

Page 36: ...nce 600 Ω Angle of rotation mechanically limited to 95 Direction of rotation reversible with switch A B Position indication 0 to 1 and reversible indicator Running time 150 sec Humidity 5 to 95 RH non condensing Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing NEMA 2 IP54 Housing material UL94 5VA flammability rating Agency listings cULus accord...

Page 37: ...f this product it may be necessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury GM GR Actuators On Off Floating Point 2 3 5...

Page 38: ... 500 Ω for 4 to 20 mA 750 Ω for PWM 1500 Ω for on off and floating point Angle of rotation mechanically limited to 95 Direction of rotation reversible with switch A B Position indication 0 to 1 and reversible indicator Running time 150 seconds Humidity 5 to 95 RH non condensing Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing NEMA 2 IP54 Housing...

Page 39: ...roperly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury GM GR Actuators Multi Function Technology 7 Blk 1 Common Red 2 Hot Wht 3 Y1 Input 2 to 10V Org 5 U Output 2 to 10V 4 to 20 mA or 2 to 10 VDC Control Signal Line Volts 24 VAC Transformer Ω 50...

Page 40: ...at control input Angle of rotation 90 adjustable with mechanical stop Position indication visual pointer Manual override internal push button UL Type 4 Running time 35 seconds default Humidity 5 to 100 RH UL Type 4 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing type UL Type 4 NEMA 4 IP66 Housing material Polycarbonate Agency listings cULus acc...

Page 41: ...the conduit fitting WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when expose...

Page 42: ... mA 1000 Ω for floating point and on off control Angle of rotation 90 adjustable with mechanical stop electronically variable Position indication visual pointer Manual override internal push button UL Type 4 Running time 150 seconds default variable 75 to 290 seconds Humidity 5 to 100 RH UL Type 4 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing...

Page 43: ... 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC up to 2 actuators may be connected in parallel WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live electric...

Page 44: ...ation 95 adjustable with mechanical stop electronically variable Direction of rotation reversible with Position indication visual pointer Manual override internal push button UL Type 4 Running time 35 seconds default Humidity 5 to 100 RH UL Type 4 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 F 40 C to 80 C Housing type UL Type 4 NEMA 4 IP66 Housing material Polyca...

Page 45: ...tallation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious ...

Page 46: ...loating point and on off control Angle of rotation 95 adjustable with mechanical stop electronically variable Direction of rotation reversible with Position indication visual pointer Manual override internal push button UL Type 4 Running time 150 seconds default variable 75 to 290 seconds Humidity 5 to 100 RH UL Type 4 Ambient temperature 22 F to 122 F 30 C to 50 C Storage temperature 40 F to 176 ...

Page 47: ...ction from the actuator must be connected to the hot connection of the controller The ZG R01 500 Ω resistor may be used WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified li censed electrician or other individual who has been properly trained in handling live elect...

Page 48: ...ion BACnet MS TP Passive Sensor Inputs 2 PT1000 NI1000 NTC Application PR Series valve actuators are designed with an integrated linkage and visual position indicators For outdoor applications the installed valve must be mounted with the actuator at or above horizontal For indoor applications the actuator can be in any location including directly under the valve Operation The PR series actuator pr...

Page 49: ...a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury N L Y1 Y2 Common Hot Input CCW open Input CW close 24 to 240 VAC or 24 to 125 VDC 1 UP 46 1 On Off N L Y1 Y2 1 UP 46 Common...

Page 50: ...0 default 85 4 1 Auxiliary Switches PRBUP MFT T Modulating Non Spring Return 24 240 V NEMA 4X with BACnet 800 543 9038 USA 866 805 7089 CANADA 203 791 8396 LATIN AMERICA CARIBBEAN Date created 11 29 2017 Subject to change Belimo Aircontrols USA Inc ...

Page 51: ...installed valve must be mounted with the actuator at or above horizontal For indoor applications the actuator can be in any location including directly under the valve Operation The PR series actuator provides 90 of rotation and a visual indicator shows the position of the valve The PR Series actuator uses a low power consumption brushless DC motor and is electronically protected against overload ...

Page 52: ...cessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury N L Y1 Y2 Common Hot Input CCW open Input CW close 24 to 240 VAC or 24...

Page 53: ...ion BACnet MS TP Passive Sensor Inputs 2 PT1000 NI1000 NTC Application PR Series valve actuators are designed with an integrated linkage and visual position indicators For outdoor applications the installed valve must be mounted with the actuator at or above horizontal For indoor applications the actuator can be in any location including directly under the valve Operation The PR series actuator pr...

Page 54: ...a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury N L Y1 Y2 Common Hot Input CCW open Input CW close 24 to 240 VAC or 24 to 125 VDC 1 UP 46 1 On Off N L Y1 Y2 1 UP 46 Common...

Page 55: ...0 default 85 4 1 Auxiliary Switches PRXUP MFT T Modulating Non Spring Return 24 240 V NEMA 4X with BACnet 800 543 9038 USA 866 805 7089 CANADA 203 791 8396 LATIN AMERICA CARIBBEAN Date created 11 29 2017 Subject to change Belimo Aircontrols USA Inc ...

Page 56: ...installed valve must be mounted with the actuator at or above horizontal For indoor applications the actuator can be in any location including directly under the valve Operation The PR series actuator provides 90 of rotation and a visual indicator shows the position of the valve The PR Series actuator uses a low power consumption brushless DC motor and is electronically protected against overload ...

Page 57: ...cessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury N L Y1 Y2 Common Hot Input CCW open Input CW close 24 to 240 VAC or 24...

Page 58: ...ush button Running Time Motor 150 sec Humidity 5 to 95 RH non condensing Ambient Temperature Range 22 F to 122 F 30 C to 50 C Storage Temperature Range 40 F to 176 F 40 C to 80 C Housing NEMA 2 IP42 UL enclosure type 2 Housing Material UL94 5VA Agency Listings cULus acc to UL60730 1A 2 14 CAN CSA E60730 1 02 CE acc to 2004 108 EC and 2006 95 EC Noise Level Motor 45 dB A Servicing maintenance free ...

Page 59: ...ectrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury Blu 1 Common Brn 2 Load Wht 3 Load N L Line Wht Volts Blk A 1 11 On Off 100 to 240 VAC Blu 1 Commo...

Reviews: