Wiring Diagrams
Meets cULus requirements without the need of an electrical ground
connection.
UP
Universal Power Supply (UP) models can be supplied with 24 VAC up to
240 VAC, or 24 VDC up to 240 VDC.
Disconnect power.
Provide overload protection and disconnect as required.
Two built-in auxiliary switches (2x SPDT), for end position indication,
interlock control, fan startup, etc.
Only connect common to negative (-) leg of control circuits.
46
Actuators may be controlled in parallel. Current draw and input
impedance must be observed.
!
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
N
L
Y
1
Y
2
Common
+ Hot
Input CCW (open)
Input CW (close)
24 to 240 VAC
or
24 to 125 VDC
1
UP
46
1
!
On/Off
N
L
Y
1
Y
2
1
UP
46
!
Common
+ Hot
Input CCW (open)
Input CW (close)
24 to 240 VAC
or
24 to 125 VDC
Floating Point
N
L
Y
1
Y
2
N
5
UP
46
24 to 240 VAC
or
24 to 125 VDC
-
+
Y
3
U5
Com -
24 VDC Out (max 5mA)
Y
3
0 - 10 VDC, 4-20 mA
U5/MP 0 - 10 VDC
1
Modulating
N
L
Y
1
Y
2
N
24 to 240 VAC
or
24 to 125 VDC
Com
D +
D -
Com
Bacnet D +
D -
BACnet
PRBUP-MFT-T
Modulating, Non-Spring Return, 24-240 V, NEMA 4X with BACnet