V3.3 07.2016•
Subject to modifi
cation
UL marked actuators is optional, please contact your local Sales Representative for details.
7
Characterised control valve (CCV) with
sensor-operated flow control, 2-way,
with flange PN16
• Nominal voltage AC/DC 24V
• Control modulating
• For modulating water-side control of
air handling unit and heating systems
• Communication via Belimo MP-Bus
or conventional control
• Conversion of (active) sensor signals
and switching contacts
Model No.
Frequency
[Hz]
[l/min]
kvs theor.*
[m³/h]
DN
[mm]
Rp
[”]
PN
[bar]
n(gl)
[ ]
P6065W800E-MP
50
8
480
45
65 2 1/2
16
3.2
P6080W1100E-MP
50
11
660
65
80
3
16
3.2
P6100W2000E-MP
50
20
1200
115
100
4
16
3.2
P6125W3100E-MP
50
31
1860
175
125
5
16
3.2
P6150W4500E-MP
50
45
2700
270
150
6
16
3.2
P6065W806E-MP
60
8
480
45
65 2 1/2
16
3.2
P6080W1106E-MP
60
11
660
65
80
3
16
3.2
P6100W2006E-MP
60
20
1200
115
100
4
16
3.2
P6125W3106E-MP
60
31
1860
175
125
5
16
3.2
P6150W4506E-MP
60
45
2700
270
150
6
16
3.2
Electrical data
Nominal voltage
AC/DC 24V
Nominal voltage frequency
50 /60Hz (upon request)
Nominal voltage range
AC 19.2...28.8V / DC 21.6...28.8V
Power consumption in operation
9.5 W
Power consumption in rest position
6.5 W
Power consumption for wire sizing
13 VA
Connection supply / control
Cable 1m, 4 x 0.75 mm²
Parallel operation
Yes (note the performance data)
Flow measurement
Measuring principle
Magnetic inductive volumetric flow
measurement
Measuring accuracy
±2%
(of 25...100% nom at 20°C, Glycol 0% vol.)
Min. flow measurement
1.25% of
nom
Functional data
Torque motor
20Nm (DN 65...80) / 40Nm (DN 100...150)
Positioning signal Y
DC 0...10V
Operating range Y
DC 2...10V
Operating range Y variable
Start point DC 0.5...24V
End point DC 8.5...32V
Position feedback U
DC 2...10V
Position feedback U variable
Start point DC 0.5...8V
End point DC 2…10V
Sound power level motor max.
45 dB(A)
Adjustable flow rate max
30...100% of
nom
Control accuracy
±5%
(of 25...100% nom at 20°C, Glycol 0% vol. )
Media
Cold and hot water, water with glycol up to max.
60% vol.
Media temperature
-10°C...120°C
Closing pressure ∆ps
690 kPa
Differential pressure ∆pmax
340kPa
Flow characteristic
Equal percentage (VDI/VDE 2178), linear
Leakage rate
Air bubble-tight (Leakage rate A, EN12266-1)
Pipe connections
Flange (ISO 7005-2 / EN 1092-1)
Technical data sheet
P6..W..E-MP
Type overview
Technical data
: Theoretical kvs value for pressure drop calculation
*