Product features

Air volume control strategy

The air volume can be pre-selected and set to minimum, variable (dial: 30 … 70%) and 

maximum using the push-button and the rotary knob on the controller front. This is especially 

suitable for applications requiring a defined air exchange. The heating output is not available.

Room temperature control strategy

The desired comfort temperature can be selected using the rotary knob. The room controller 

controls the air volumes as well as the heating valve on the basis of the set parameters.

Override kitchen

Pressure differences caused by the kitchen hood fan or the chimney extraction system are 

balanced out largely by reducing the exhaust air volume.

Override bathroom

Volume currents are increased to the maximum air change, e.g. in order to draw off humid air 

from rooms as quickly as possible.

Energy hold off (EHO)

The room is controlled in the energy saving mode, i.e. the VAV units are closed and the heating 

setpoint is lowered to the value for the room protection function during long periods of absence, 

for example.

Room protection (Frost)

If the current room temperature falls below 14°C, the room protection function is activated.

External temperature sensor

An external temperature sensor can be connected to the analogue input ai1, e.g. in the exhaust 

air duct for calculating the average room temperature.

Electrical installation

Wiring diagram

1 2 9 10 11 6 7 8

3

4 12

5

AC 24 V

~

NTC

CRA24-B3(P)

ai/di1

di2 di3

ao1

ao2

ao3

U5

1

U5

2

T

Inputs

Outputs

3

ai1 External temperature sensor

6

ao1 System output VAV controller supply air

di1 Energy hold off (EHO)

9/10 ao3 2-point / 3-point output heating

4

di2 Override kitchen

11

ao2 System output VAV controller exhaust 

air

5

Not used

Other connections

12 di3 Override bathroom

7

PP1 Diagnostic socket VAV controller supply 

air

8

PP2 Diagnostic socket VAV controller 

exhaust air

Notes

•  Connection via safety isolating transformer.

•  Parallel connection of other actuators possible. 

Note the performance data.

!

Configuration

Configuration

DIP

Default settings

1

P-Band normal

P-Band wide

2

Air volume control strategy

Room temperature control strategy

3

Control sequence for air cooling

Control sequence for air heating

4

Reset MAX → COMF

Off

Reset MAX → COMF

1 h

5

Max. temp. monitoring

Off

Max. temp. monitoring

On

6

Definition of heating output (ao3)

2-point actuator

Definition of heating output (ao3)

3-point actuator

1

2

3

4

5

6

ON

OFF

Note

The functions are described in detail on pages 10 

to 15.

CRA24-B3(P)

Technical data sheet

Summary of Contents for CRA24 Series

Page 1: ...bject to changes 1 24 Product information CRA24 Controller for apartments CRA24 B3 P Room controller with three outputs Supply air device Exhaust air device Heating valve CRA24 B1P 3 step switch with...

Page 2: ...temperature 12 Reset MAX COMF 13 Override functions 13 External temperature sensor ai1 14 Analogue outputs 15 CRA24 B1P Technical data sheet 17 Technical data 17 Safety notes 17 Product features 17 El...

Page 3: ...Damper actuators VAV Compact OEM product i e VAV controller can be supplied only by the manufacturer of VAV units LMV D3 MP NMV D3 MP R K TRD24 R TR24 R LR24A LM24A MF NM24A MF LM24A MP NM24A MP Acces...

Page 4: ...oom temperature control range as required see the separate documentation of the CR24 range Override kitchen The kitchen hood fan or even the chimney extractor system sucks air from the rooms This lead...

Page 5: ...is to be ensured Together with the downstream VAV units the air volumes can be adapted individually to the needs of the user The push button on the controller front can be used to enable the COMF Nom...

Page 6: ...CRA24 6 24 CRA24 en gb 2013 05 15 Subject to changes www belimo com CRA24...

Page 7: ...rotection class III Safety extra low voltage Degree of protection IP30 EN 60529 Mode of operation Type 1 EN60730 1 Software class A EN 60730 1 EMC CE according to 2004 108 EC Ambient conditions Operat...

Page 8: ...ls below 14 C the room protection function is activated External temperature sensor An external temperature sensor can be connected to the analogue input ai1 e g in the exhaust air duct for calculatin...

Page 9: ...Control sequence simulation The connected actuators as well as the control sequences can be simulated independent of the room temperature using the rotary knob for the setpoint adjustment ZTH GEN PC...

Page 10: ...otary knob CRA24 B3P hidden 30 70 air 3 K temperature 4 inputs Override kitchen Override bathroom Energy hold off EHO External temperature sensor Type NTC 5 k operating range 10 45 C 3 outputs 2 10 V...

Page 11: ...DIP switch 2 OFF Operating mode COMF Operating mode MIN Operating mode MAX The air volume can be set in the range of 30 70 of the operating volume current range min max programmed on the VAV controll...

Page 12: ...ates to the selected setpoint The connected VAV controllers are set to the maximum air volume max selected on the controller The heating valve regulates to the selected setpoint Reset MAX COMF with DI...

Page 13: ...on Component Air volume Room temperature Supply air ao1 100 max 100 max Extract air ao2 100 max 100 max Heating valve ao3 OPEN OPEN Priority 2 Kitchen di2 Chimney extractor system In order to minimise...

Page 14: ...mperature monitoring 1 2 3 4 5 6 ON OFF The room temperature can be monitored to a maximum value of 28 C This function must be enabled via DIP switch 5 ON Component Air volume Room temperature Supply...

Page 15: ...7 8 3 4 12 CRA24 B3 ai di1 di2 di3 ao1 ao2 ao3 U51 U52 AC 24 V T 1 2 3 5 Y U T 1 2 9 10 11 6 7 8 3 4 12 CRA24 B3 ai di1 di2 di3 ao1 ao2 ao3 U51 U52 AC 24 V T 1 2 3 5 Y U T Heating valve connection 1...

Page 16: ...CRA24 16 24 CRA24 en gb 2013 05 15 Subject to changes www belimo com CRA24...

Page 17: ...upply air exhaust air device VAV unit or damper actuator Safety notes The controller is not allowed to be used outside the specified field of application especially not in aircraft or in any other air...

Page 18: ...lation The air volume is regulated to the maximum value that is set at the VAV controller Advantages Maximum air exchange e g during a party or fondue evening Connecting terminals measuring points Mea...

Page 19: ...ith damper actuator instead of VAV controllers Use of damper actuators is usually possible but it must still be taken into account that this application cannot detect and regulate pressure changes in...

Page 20: ...CRA24 20 24 CRA24 en gb 2013 05 15 Subject to changes www belimo com CRA24...

Page 21: ...been removed and must be remounted proceed as follows a Insert the rotary knob approximately half way and turn it clockwise as far as the end stop b Remove the rotary knob and align it so that the ca...

Page 22: ...ng and connect the cables see page 21 2 Configure the DIP switches on the printed circuit board according to the required application 3 Assemble the printed circuit board on the baseplate of the housi...

Page 23: ...ence simulation CRA24 B3 P In simulation mode the connected actuators can be operated regardless of the room temperature The air volume min and max in the air systems and the maximum heating capacity...

Page 24: ...sortment from a single source Examinded Quality Short delivery time Comprehensive support Belimo weltweit www belimo com Belimo Europa BELIMO Automation AG Brunnenbachstrasse 1 CH 8340 Hinwil Tel 41 4...

Reviews: