8
10...16
10...20
4.5
191
46
92
76
23
45
216
p0087002
d0035002
AC 230 V
N L1
AM230-SR
Wiring diagram
1
2
3
AM230-SR
5
T
U PP
T
Y
Z
DC 0...10 V
U5
Y
DC 2...10 V
SGA24
SGF24
Vcc
Connecting cable for signals
N L1
Connecting cable
for power supply
To isolate from the main
power supply, the system
must incorporate a device
which disconnects the
phase conductors (with at
least a 3 mm contact gap).
Parallel connection
to further AM230-SR.
Power consumption
must be observed.
Dimensions
Application
The type AM230-SR is intended for the
operation of air control dampers in venti-
lation and air-conditioning systems.
Mode of operation
Modulating control is effected by means of
a standard DC 0...10 V control signal.
Product features
Basic positions
When the power supply is switched on for
the first time, i.e. during the initial commis-
sioning or after pressing the pushbutton,
the actuator will run to the basic position.
The actuator then runs to the position de-
manded by the control signal.
Simple direct mounting
on the damper
spindle by universal spindle clamp. An an-
tirotation device is supplied.
Manual operation
by self-resetting push-
button when necessary (gearing disen-
gaged while the button is held depressed).
Adjustable angle of rotation
with mecha-
nical stops.
High functional reliability
(overload-proof)
needs no limit switches, halts automatically
at the end stops.
Connection
is either by means of the pre-
fitted leads included with the actuator or
directly by means of screw terminals. In the
case of direct connection the terminal box
will be opened (page 15/16).
Electrical accessories
SA1, SA2
Auxiliary switches, page 17
PA...
Feedback potentiometer, p.18
Mechanical accessories,
page 22
ZG-AM
Damper linkage kit
Mounting instructions,
page 21/22
Important:
Read the notes about the use
and torque requirements of the damper
actuators on page 3.
Dampers up to approx. 3.6 m
2
Modulating actuator (AC 230 V)
Control DC 0...10 V
Position feedback DC 2...10 V
Multi-function connection
Basic positions
Pos. reversing switch
ccw
cw
Stop left
Stop right
L
M
Y = 0
R
M
Y = 0
III
Control signal Y
DC 0...10 V @ Ri 47 k
Ω
Nominal voltage range
AC 198...264 V
Direction of rotation
selected with L / R
Torque
min. 18 Nm
(at rated voltage)
Angle of rotation
max. 95°
(adjustable 35…100% by mechanical stops)
Running time
150 s
Position indication
mechanical
Protection class
power supply:
II
(all insulated)
signal part:
(safety low voltage)
Maintenance
maintenance-free
Degree of protection
IP 54
(bottom cable entry)
EMC
CE according to 89/336/EEC, 92/31/EEC, 93/68/EEC
Low Voltage Directive
CE according to 73/23/EEC
Ambient temperature range
– 30...+ 50 °C
Non-operating temperature
– 40...+ 80 °C
Humidity test
to EN 60335-1
Sound power level
max. 45 dB (A)
Manual operation
push button, auto-return
Technical data
AM230-SR
Nominal voltage
AC 230 V 50/60 Hz
Power consumption
running: 4 W, at rest: 3.1 W
For wire sizing
5 VA (Imax 300 mA @ 2 ms)
Cable glands
1 x for motor lead 6...8 mm dia.
(PG11 included)
1 x for signals lead 8...10 mm dia.
Connecting cable
power supply: 1 m, 2 x 0.75 mm
2
signals:
1 m, 4 x 0.75 mm
2
(direct connection by screw terminals for 2 x 1.5 mm
2
wire possible)
Weight
1500 g
(
at Y = 0 V)
at switch position L resp. R
Operating range
DC 2...10 V
Function pos. feedback U5
DC 2...10 V @ max. 0.7 mA
Positioning accuracy
± 5%
w0913002
AM230-SR Damper actuator 18 Nm
ENG-93001-93226-12.02-2M
•
Printed in Switzerland
•
ZSD
•
Subject to technical changes
B