Technical Manual 

 

 

LioN-Link PROFINET 

 

Subject to change without notice! 

 

Version 1.2 / August 2014 

 

 

Page 26 of 30 

  

8.

 

Firmware update 

 

Over the configuration page of the integrated web server a firmware update of the two microcontrollers is possible, which are 
used in this BusHead. 

 
 

Important note! 
Please observe the following description of the firmware updates exactly since otherwise the 
BusHead cannot function properly any longer. 

 

 

1.

 

Disconnect the BusHead from all connections to LioN-Link I/O-modules by unscrewing the M12 connecting plugs of 
the two lines. 

 

2.

 

Disconnect also the connection to your control unit and other PROFINET IO devices. 
Only the computer which is intended to accomplish the update should be connected to the BusHead. 

 

3.

 

Perform a power reset at the BusHead by interrupting the power supply for a short time. 
However, after starting the update it has to be ensured that the power supply cannot be interrupted any more.  
The two green LEDs U

S1

 and U

S2

 must light permanently. 

 

4.

 

Make sure that the BusHead has a static IP address, or assign an IP address using a tool that supports the DCP protocol 
of PROFINET, such as 

STEP7

 

5.

 

In your browser, change to the configuration page of the integrated web server and select the file for the firmware 
update by clicking on the button 

Search

. The file for the microcontroller SAM7 is called “0940ESL601_SAM7.bin“, the 

file name for the ERTEC controller is “0940ESL601_ERTEC.bin“. The file names may not be changed. 

 

6.

 

By clicking on the button 

"Apply!"

 the firmware file is transferred to the BusHead. Due to the size of the firmware for 

the ERTEC chip this process can take several seconds. The transmission time of the SAM7 firmware is much shorter. An 
indication of the transfer by an LED indicator does not take place. 

 

7.

 

After completing the transfer of the firmware file, the BusHead stores internally the file in the non-volatile memory. 
This process is indicated by a special LED display. During an ERTEC update only the DIA LED flashes. When updating the 
SAM7, the LED indicators US1 and US2 flash additionally. 

 

8.

 

Upon completion of the update, the red DIA LED stops flashing and the two LED indicators U

S1

 and U

S2

 switch back to 

solid green again. The browser displays the message 

"LioN-Link Firmware Update successfully completed"

 

9.

 

Upon completion of the update, a power reset of BusHead is necessary. For this purpose, the power supply has to be 
interrupted shortly. 
Caution: Before a power reset, the status of the LED indicators DIA, U

S1

 and U

S2

 has to be observed. It is 

necessary to wait until the DIA-LED is off and the LED indicators US1 and US2 are solid green again. 

 

10.

 

If an update should also be available for the second microcontroller, then the steps 5 to 9 with the appropriate file are 
to be repeated. 

 

11.

 

After completion of all updates the connection with the LioN-Link I/O-modules, the control unit and further PROFINET 
IO devices can be restored. Note that the BusHead first detects the actual configuration of LioN-Link I/O-modules 
after a power reset. 

 

Summary of Contents for Lumberg Automation 0970 ESL 601

Page 1: ...Technical Manual 0940 ESL 601...

Page 2: ...pole D coded 12 5 1 2 Power supply connector for the BusHead M12 plug 5 pole 12 5 1 3 Link system connector M12 socket 5 pole 13 5 2 Intermediate power supply feed on LioN Link I O modules 14 5 2 1 T...

Page 3: ...7 3 The monitoring page Monitoring 25 8 Firmware update 26 9 Alarm and error messages of the BusHead 27 9 1 Evaluation of alarms in STEP7 27 9 1 Reaction of the BusHead to a module breakdown pull ala...

Page 4: ...s please do not hesitate to contact us We will be glad to be at your disposal at any time Belden Deutschland GmbH Lumberg Automation Im Gewerbepark 2 58579 Schalksmuehle Germany Tel 49 0 23 55 5044 00...

Page 5: ...ferences in the residential area In this case the operator can be required to accomplish appropriate measures The proper and safe function of the product requires an appropriate transport storage inst...

Page 6: ...ledge of the relevant standards have the same level of knowledge as after a technical education due to an activity in a comparable area for several years Modifications to the hard and software of our...

Page 7: ...s is arbitrary The permissible overall length for each line may not be exceeded however Using the maximum expansion of the system an additional feed of the power supply for the system and sensors is p...

Page 8: ...pole interface M LioN Link special modules 0942 UEM 620 IO Link master 4xM12 S 0942 UEM 783 Motion drive control 8xM12 M 3 3 Accessories Part number Description PROFINET 0985 342 100 M Connecting cabl...

Page 9: ...ocket straight 5 pole contacts 1 3 connected A coded Field attachables 0986 EMC 102 Field attachable M12 plug for PROFINET cable straight 4 pole D coded with spring type terminals RSC 5 9 Field attach...

Page 10: ...Technical Manual LioN Link PROFINET Subject to change without notice Version 1 2 August 2014 Page 10 of 30 4 Mounting 4 1 Outer dimensions...

Page 11: ...g a flat washer according to DIN 125 has to be used Important note For the derivation of interference currents and or for the EMC stability the module provides a metal grounding sheet It is necessary...

Page 12: ...lines 24 V DC to the data lines 5 1 2 Power supply connector for the BusHead M12 plug 5 pole Colour code of the connector grey Connector Pin Signal Function PROFINET ports P1 P2 1 TD Transmit Data 2 R...

Page 13: ...in 4 Data Pin 5 Also the reverse connection of the power supply lines can lead to the destruction of the module Important note With long cable lengths an additional power supply feed is recommended se...

Page 14: ...ctronics and sensors of the I O modules can be necessary If the power supply for the I O modules is not sufficient they deliver a diagnostics message The warning threshold for the diagnostics is appro...

Page 15: ...ink line a calculation table as a Microsoft Excel sheet is available under http www beldensolutions com en Service Downloadcenter Software_Lumberg index phtml The table determines the voltage drop on...

Page 16: ...g index phtml On request the GSDML file is also mailed by the support team The name of the file is as follows GSDML v2 2 Lumberg Automation LioN Link yyyymmdd xml in which yyyymmdd expresses the relea...

Page 17: ...SL601 in the hardware catalogue Move the system to the PROFINET line of the control unit Insert now the I O modules of the LioN link system connected to the BusHead into the configuration Locate the I...

Page 18: ...g and choose the menu item Edit Object Properties In the opening dialogue window you can change the device name Check whether the displayed IP address is correct and control unit and BusHead are locat...

Page 19: ...ps determined by the IO Devices The LioN Link PROFINET BusHead supports the function of device exchange without removable media PG The topology of the network has to be configured for the use of the f...

Page 20: ...Technical Manual LioN Link PROFINET Subject to change without notice Version 1 2 August 2014 Page 20 of 30...

Page 21: ...missioning it is recommended to leave the parameter Interchanged Modules on the setting ACCEPT default setting In this mode it is possible to find the optimal installation and the most favourable wiri...

Page 22: ...box Prioritized Start up in the window Properties Interface X1 should not be selected 6 4 6 Resetting the BusHead to factory settings In STEP7 resetting the BusHead to factory settings is carried out...

Page 23: ...IP address According to the PROFINET standard all PROFINET IO devices are delivered with IP address 0 0 0 0 This means a free IP address deviating from the factory settings has to be assigned to the...

Page 24: ...nfiguration page Configuration With the selection of the menu item Configuration on the left side of the homepage you are requested to enter a user name and a password Enter Admin as the user name and...

Page 25: ...is also possible on this side The procedure is described in one of the following chapters of this manual and should be absolutely observed 7 3 The monitoring page Monitoring The page Monitoring gives...

Page 26: ...s 0940ESL601_ERTEC bin The file names may not be changed 6 By clicking on the button Apply the firmware file is transferred to the BusHead Due to the size of the firmware for the ERTEC chip this proce...

Page 27: ...iled information about the fault can be obtained in the fault OB by calling the SFB 54 RALRM Receive additional alarm information The SFB 54 therefore has to be called in every fault OB If the called...

Page 28: ...xF Number of module with diagnostics Error code 0x00 Reserved 0x01 Short circuit 0x02 Low voltage 0x03 Overvoltage 0x04 Overload 0x05 Over temperature 0x06 Broken wire 0x07 Upper limit value exceeded...

Page 29: ...ASE TX supported Manufacturer code Vendor ID 0016AH Device code Device ID 0302H Supported Ethernet protocols Ping ARP LLDP SNMP Network diagnostics DCP HTTP TCP IP Switch functionality integrated IRT...

Page 30: ...th I O modules red Incorrect configuration modules permuted red green alternating flashing Restart of line 1 and or line 2 off Line 1 and or line 2 not used no I O module connected P1 Lnk Act P2 Lnk A...

Reviews: