Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
max. 10 V/m
max. 10 V/m
max. 20 V/m
max. 10 V/m
IEEE 1613
80 MHz ... 1000 MHz
—
—
—
max. 35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection
±2 kV
±2 kV
±2 kV
±4 kV
EN 61000-4-4
IEEE C37.90.1
Data line
±4 kV
±4 kV
±2 kV
±4 kV
Voltage surges - DC supply connection
EN 61000-4-5
line/ground
±2 kV
±2 kV
±2 kV
±2 kV
IEEE 1613
line/ground
—
—
—
±5 kV
EN 61000-4-5
line/line
±1 kV
±1 kV
±1 kV
±1 kV
Voltage surges - data line
EN 61000-4-5
line/ground
±1 kV
±1 kV
±2 kV
±2 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
10 V
10 V
10 V
EMC interference
immunity
Standard
applications
a
Merchant Navy
b
Railway
applications
(trackside)
c
Substation
applications
d
Summary of Contents for Hirschmann GREYHOUND GMM20