Connecting data cables
Note the following general recommendations for data cable connections in
environments with high electrical interference levels:
Keep the length of the data cables as short as possible.
Use optical data cables for the data transmission between the buildings.
When using copper cables, provide a sufficient separation between the
power supply cables and the data cables. Ideally, install the cables in
separate cable channels.
Verify that power supply cables and data cables do not run parallel over
longer distances. If reducing the inductive coupling is necessary, verify
that the power supply cables and data cables cross at a 90° angle.
Use shielded data cables for gigabit transmission via copper cables. Only
use shielded data cables to meet EMC requirements according to
EN 50121-4 and marine applications.
See “Electromagnetic compatibility (EMC)” on page 68.
Connect the data cables according to your requirements.
See “Ethernet ports” on page 26.