EMC interference
emission
Standard
applications
a
a. EN 61131-2, CE, FCC – applies to all devices
Marine
applications
b
b. Merchant Navy – applies to devices with the certification codes VU, U9, UY, UX, UT
Railway
applications
(trackside)
c
c. EN 50121-4 – applies to devices with the certification codes VT, UT, T9, TY
Sub-station
applications
d
d. EN 61850-3, IEEE 1613 – applies to devices with the certification codes V9, VY, VU, VT
Radiated emission
EN 55032
Class A
Class A
Class A
Class A
GL Guidelines
—
EMC 1
—
—
FCC 47 CFR Part 15
Class A
Class A
Class A
Class A
EN 61000-6-4
Fulfilled
Fulfilled
Fulfilled
Fulfilled
Conducted emission
EN 55032
AC and DC supply connections
Class A
Class A
Class A
Class A
GL Guidelines
AC and DC supply connections
—
EMC 1
—
—
FCC 47 CFR Part 15
AC and DC supply connections
Class A
Class A
Class A
Class A
EN 61000-6-4
AC and DC supply connections
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EN 55032
Telecommunication connections
Class A
Class A
Class A
Class A
EN 61000-6-4
Telecommunication connections
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EMC interference
immunity
Standard
applications
a
Marine
applications
b
Railway
applications
(trackside)
c
Sub-station
applications
d
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
±4 kV
±6 kV
±6 kV
±8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
±8 kV
±8 kV
±8 kV
±15 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
10 V/m
10 V/m
20 V/m
10 V/m
IEEE 1613
80 MHz ... 1000 MHz
—
—
—
35 V/m