Maintenance, troubleshooting, spare parts and dismantling
DRYPOINT® RA HT 20-350 NA UL
29
FAULT
POSSIBLE REASON
– SUGGESTED MEASURE
◆
The refrigerating
compressor does not
work.
The internal heat protection of the compressor was activated
– wait 30 minutes and then retry.
Check the electric cabling.
If installed
– replace the internal heat protection and/or the start-up relay and/or the starting
capacitor and/or the operating capacitor
.
If installed
– the HPS pressure switch was activated – see the corresponding point.
If installed
– the LPS pressure switch was activated – see the corresponding point.
If installed
– the TS safety temperature switch was activated – see the corresponding point.
If installed
– the power contactor KC1 does not work, replace it.
In the event that the compressor still does not work, replace it.
◆
The fan of the
condenser does not
work
Verify the electric wiring.
PV pressure switch is faulty - replace it.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
If the fan still doesn't work, replace it.
◆
DRYPOINT RA HT 75-
350 NA
- The
Aftercooler fan doesn’t
work.
Verify the electric wiring.
If the fan still doesn't work, replace it.
◆
DewPoint too high.
The dryer doesn't start - see specific point.
The T1 DewPoint
probe doesn’t correctly detect the temperature - ensure the sensor is pushed into the
bottom of copper tube immersion well.
The refrigerating compressor doesn’t work - see specific point.
The ambient temperature is too high or the room aeration is insufficient - provide proper ventilation.
The inlet air is too hot - restore the nominal conditions.
The inlet air pressure is too low - restore the nominal conditions.
The inlet air flow rate is higher than the rate of the dryer - reduce the flow rate - restore the normal
conditions.
The condenser is dirty - clean it.
The aftercooler is dirty - clean it.
The condenser fan doesn’t work - see specific point.
The aftercooler fan doesn’t work - see specific point.
The dryer doesn’t drain the condensate - see specific point.
The hot gas by-pass valve is out of setting - contact a refrigeration engineer to restore the nominal
setting.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
◆
The air compressor
doesn’t work.
Verify the electric wiring.
Verify that the air thermo-switch is working properly
If the air compressor still doesn't work see troubleshooting of the air compressor
◆
DewPoint too low.
The fan is always ON - PV pressure switch is faulty - replace it.
The Hot Gas By-pass Valve is out of setting - contact a refrigeration engineer to restore the nominal
setting.
Ambient temperature is too low - restore de nominal condition.
◆
Excessive pressure
drop within the dryer.
The Pre-Filter (1 micron) is clogged - replace the filter element (cartridge) - Refer to the instructions in
the user’s and maintenance manual of the filter.
The dryer doesn’t drain the condensate - see specific point.
The DewPoint is too low - the condensate is frost and blocks the air - see specific point.
Check for throttling the flexible connection hoses.
◆
The dryer doesn’t
drain the condensate.
The condensate drain service valve is closed - open it.
Verify the electric wiring.
The DewPoint is too low - the condensate is frozen - see specific point.
Bekomat drainer is not operating correctly (see BEKOMAT MANUAL)
◆
The dryer continuously
drains condensate.
Bekomat drainer is dirty (see BEKOMAT MANUAL)
◆
Water within the line.
The dryer doesn't start - see specific point.
Where installed
- Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn’t drain the condensate - see specific point.
DewPoint too high - see specific point.
◆
The dryer does not
start.
Check whether or not the dryer is connected with the electric mains.
Check the electric cabling.
Summary of Contents for DRYPOINT RA HT 100-P NA UL
Page 19: ...DRYPOINT RA HT 20 350 NA UL 19 10 2 Technical data DRYPOINT RA HT 150 350 NA E 1 230 60 UL ...
Page 34: ...Appendices 34 DRYPOINT RA HT 20 350 NA UL 13 1 2 Dryers Dimensions DRYPOINT RA HT 75 NA UL ...
Page 35: ...Appendices DRYPOINT RA HT 20 350 NA UL 35 13 1 3 Dryer dimensions DRYPOINT RA HT 100 NA UL ...
Page 36: ...Appendices 36 DRYPOINT RA HT 20 350 NA UL 13 1 4 Dryer dimensions DRYPOINT RA HT 150 NA UL ...
Page 46: ...Appendices 46 DRYPOINT RA HT 20 350 NA UL 13 3 2 Electric diagram DRYPOINT RA HT 20 50 NA UL ...
Page 47: ...Appendices DRYPOINT RA HT 20 350 NA UL 47 13 3 3 Electric diagram DRYPOINT RA HT 75 100 NA UL ...
Page 48: ...Appendices 48 DRYPOINT RA HT 20 350 NA UL 13 3 4 Electric diagram DRYPOINT RA HT 150 NA UL ...
Page 51: ...Appendices ...