Installation and operating manual
EN
22 DRYPOINT
®
AC 410 – 495 | DRYPOINT
®
AC 410 – 495 MS
2.3.5.2.1.
Table 1: First level (without SET button)
Display texts
Top line
Bottom line with
dew point control
Bottom line with
time control
Comment
Current operation
Dewp. Control ↑ (↓)
Dewpoint= xx °C
-------------------
Default display (after
10 min.)
Adsorption Right
Dewpoint= xx °C
xx:xx/Rest xx:xx
Alternating right /
left
Adsorption Left
Dewpoint= xx °C
xx:xx/Rest xx:xx
Alternating right /
left
Regen. Right
xx:xx/Rest xx:xx
xx:xx/Rest xx:xx
Alternating right /
left
Regen. Left
xx:xx/Rest xx:xx
xx:xx/Rest xx:xx
Alternating right /
left
Statistics
Operating time
xxxxxx hrs.
xxxxxx hrs.
Stand-By
xxx:xx:xx hrs.
xxx:xx:xx hrs.
Oper. Time Ads.
xxxxxx hrs.
xxxxxx hrs.
Adsorbent operating
time
Action
Off-Line
Plant switches to
"off-line" mode.
Only displayed, if
this function has
been triggered
(intermittent
operation).
Service messages
Service A
replace !
replace !
Maximum service
life of wearing
parts reached (text
switches between
message and default
display).
Service B
replace !
replace !
Maximum service
life of adsorbent
reached (text
switches between
message and default
display).
Transmitter
calibrate !
Annual calibration of
dew point transmitter
due.
Alarm messages
Safety Mode
Safe mode operation
("fix mode").
Displayed, if alarm
has been triggered.
Dew point alarm
Dew point alarm
triggered.
Short
Transmitter
Short circuit at dew
point transmitter
Open
Transmitter
Transmitter circuit
open
Failure
Electrical failure