16 / 44 EN
Free match split type air conditioner / Installation Manual
Rows of series installation
Table 6.2 The relations between H, A and L are as follows.
L
A
L H
L 1/2H
25 cm/9.8” or more
1/2H < L H
30 cm/11.8” or more
L > H
Can not be installed
L
H
A
25 cm/9.8"
or more
25 cm/9.8"
or more
150 cm/59"
or more
60 cm/23.6"
or more
300 cm/118" or more
Fig. 6.7
C
Note:
The minimum distance between the outdoor unit and walls described in the
installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in
at least two of the three directions (M, N, P) (See Fig. 6.8)
6
Outdoor unit installation