26
must be connected together and grounded.
Code the enclosures shall be grounded using the ‘E’ terminal on the terminal
manufactured from conductive plastic per Article 250 of the National Electrical
hubs are fitted to a BA484DF Fieldbus Display, all metallic glands or conduit hubs
In addition to the supplied bonding plate, when 2 or 3 metallic glands or conduit
The BA484DF and BA488CF Fieldbus Display enclosures are
block.
CAUTION:
9.
8.
Class II and III
Class I
Class
Any metallic or plastic cable gland or conduit hub that provides
the required environmental protection.
SSTG-1 STG-1 STAG-1
Crouse – Hinds Myler hubs
CMCXAA050 MCR050 MCX050
Permitted gland or conduit hub
MHUB-1
CHMG-50DT
Killark Glands
REMKE hub
O-Z / Gedrey hub
WH-1-G
Metallic glands and hubs must be grounded – see note 8.
When installed in a hazardous (classified) location the BA484DF Fieldbus Display
shall be fitted with cable glands / conduit hubs selected from the following table.
7.
The terminator on the Fieldbus must be FM Approved.
10.
The BA484DF should be mounted where it is shielded from direct sunlight.
11.
Cont.