Step 3
Select input count mode
The two proximity detectors are
positioned so their outputs are electrically
90° apart. From this information, in the
quadrature input mode the BA568E
Counter can sense the direction and
angular movement of the wheel to which
the proximity detectors are attached.
Hence, the relative position of the cable
can be displayed by the counter.
Select
Count
from the configuration
menu and press
(
. Using the
&
or
*
button select
A rEL b
the quadrature
function and press
)
to return to the
‘Count’ prompt in the configuration menu.
Step 4
Define function of upper display
In the example the cable position (total
display) is required on the eight digit
upper display.
Select
dI5P-1
from the configuration
menu and press
(
which will reveal if
the upper display is showing
rAtE
or
totAL
. Using the
&
or
*
button select
totAL
followed by the
)
button to enter
the selection and return to the
configuration menu.
Step 5
Activate lower rate display
A rate display is required so the lower
display must be activated.
Select
di5PLAY
.
2
from the main menu
and press
(
to show the existing
setting. Using the
&
or
*
button
select
on
followed by
)
to enter the
selection and return to the configuration
menu.
Step 6
Position of decimal point
In this example the BA568E is required
to display total (position) with a resolution
of one decimal place and rate (speed)
with no decimal point.
Select
d
.
P
. from the configuration menu
and press
(
. The BA568E will show
and identify the total display with all the
digits activated. Using the
&
or
*
button position the decimal point between
the first and second least significant
digits.
Operating the
(
button will show and
identify the rate display with all the digits
activated, Using the
&
or
*
button
position the decimal point to the right of
the least significant digit i.e. not visible.
Finally press
)
to return to the
configuration menu.
Step 7
Enter the total scale factor
In this example the proximity detectors
produce fifteen pulses per one metre
movement of the cable. The position
display is required in metres so the total
(position) scale factor
5CALE
.
t
should be
set to 15.0.
Select
5CALE
.
t
from the configuration
menu and press
(
to view the current
value with one digit flashing. Use the
&
and
*
buttons to adjust each digit in
turn and the
(
button to transfer control
to the next digit and to the decimal point.
Enter 15.0 and return to the
5CALE
.
t
prompt in the configuration menu by
pressing
)
.
Step 8
Enter the rate scale factor
In this example the proximity detectors
produce fifteen pulses per one metre
movement of the cable. The rate display
is required in metres per second so the
rate (speed) scale factor
5CALE
.
r
should
be set to 15.0.
Select
5CALE
.
r
from the configuration
menu and press
(
to view the current
value with one digit flashing. Use the
&
and
*
buttons to adjust each digit in
turn and the
(
button to transfer control
to the next digit and to the decimal point.
Enter 15.0 and return to the
5CALE
.
r
prompt in the configuration menu by
pressing
)
.
Step 9
Set the display timebase
In this example the rate display (speed)
is required in metres per second.
Select
t-bA5E
from the configuration
menu and press
(
to reveal the current
setting. Using the
&
or
*
button scroll
through the three options and select
tb-1
. Return to the
t-bA5E
prompt in the
configuration menu by pressing
)
.
24