5.16  Local grand total run-time reset:  

clr gtot

The  grand  total  run-time  is  a  separate  timer  that
functions in parallel with the run-time display, but is
not zeroed when the run-time display is reset to zero.
The run-time grand total may be viewed in the display
mode  by  pressing  the  

)

 and  

*

 buttons

simultaneously.

Clr gtot

   is  a  sub-menu  in  the   

LoC clr

 function

which when activated allows an operator to reset the
grand total run-time to zero while the Tachometer is in
the display mode by operating the  

)

 and  

*

 push

buttons  simultaneously  for  more  than  ten  seconds.
See section 2.2

To check or change the function select 

LoC clr

 in the

configuration menu and press 

which will reveal the

clr tot  

prompt.  Using the  

&

 or  

*

 button select

clr gtot

 and press  

(

 which will show

 

if the local

grand  total  reset  is  

on

 or  

oFF

.      If  set  as  required

operate  the  

)  

button  twice  to  return  to  the

configuration menu, or the 

&

 or 

*

 button to change

the setting followed by the  

)

 button twice to enter

the change and return to the  

LoC clr

 prompt in the

configuration menu.

Note:

 

Once reset, the grand total run-time can not be
recovered.

5.17  Grand total run-time reset from within
         the configuration menu:  

Clr

   

Gtot

The  grand total  run-time is a separate  timer that is
incremented in parallel with the run-time display, but is
not zeroed when the run-time display is reset to zero.
The grand total may be viewed in the display mode by
pressing the 

)

 and 

*

 buttons simultaneously.

The grand total can be reset to zero from within the
configuration menu using this 

Clr 

 

Gtot

 function.

To zero the grand total from within the configuration
menu select 

Clr 

 

Gtot

 and press 

(

 which will cause

the  instrument  to  display  

Clr

 

.

 

no

 with  

no

 flashing.

Press  the  

&

 or  

*

  push  button  until  

Clr

 

.

 

YE5

 is

displayed   and   then   press  

(

  which  will  result  in  a

0000

  prompt  being  displayed  with  the  first  digit

flashing.  This is a request for the instruction to be
confirmed by entering 

5urE

 using the 

&

 or 

*

 

button

to adjust the flashing digit and the 

(

 button to move

control to the next digit.  Pressing  

)

 will then reset

the grand total to zero and return the Tachometer to
the  configuration menu.

Note:

Once reset, the grand total run-time can not be
recovered.

5.18  Security code:  

CodE

Access to the instrument’s configuration menu may
be protected by a four digit security code which must
be entered to gain access.   New instruments are
configured with the default security code 

0000

 which

allows  unrestricted  access  to  all  configuration
functions.

To enter a new security code select  

CodE

 from the

configuration menu and press  

(

 which will cause

the  Tachometer  to  display  

0000

  with  one  digit

flashing.  The flashing digit may be adjusted using
the  

&

 or  

*

  push  button  and  the  

(  

button  to

transfer control to the next digit.   When all the digits
have been adjusted press  

)

 to return to the  

CodE

prompt. The revised security code will be activated
when  the  Tachometer  is  returned  to  the  display
mode.

Please contact BEKA associates sales department if
the security code is lost.

5.19  Reset configuration to factory defaults:

r5Et  Def

r5Et

 

Def 

resets the Tachometer configuration to the

factory default configurations shown in section 5.0.

To  reset  the  Tachometer  to  the  factory  default
configurations select 

r5Et def 

from the configuration

menu  and  press  

(

 

which  will

 

result  in  the

instrument  displaying  

0000

  with  the  first  digit

flashing.  To confirm the instruction  

5urE

 should be

entered.   Using  the  

&

 or  

*

  button   set   the  first

flashing digit to  

5

 and press  

(  

which will transfer

control to the second digit which should be set to 

u

.

When  

5urE

  has  been  entered  pressing  the  

)

button will reset all the configuration functions and
return the instrument to the display mode.

5.20  Pulse output

The BA514G Tachometer has an opto-isolated open
collector  pulse  output  with  following  electrical
parameters:  

Ron

=

60

 + 3V

Roff

=

1M

Vmax

=

30V dc

I max

=

10mA

The output pulse may be a synchronous duplicate of
the  input  pulse  or  the  input  frequency  may  be
divided and the pulse length extended.

19

Summary of Contents for BA514G

Page 1: ...Issue 4 9th July 2019 BA514G General Purpose Tachometer Issue 4...

Page 2: ...ed scale factor 5CALE 5 5 11 Timebase t bA5E 5 12 Display filter FiLtEr 5 13 Clip off CLP oFF 5 14 Local reset LoC clr 5 15 Local run time reset clr tot 5 16 Local grand total run time reset clr gtot...

Page 3: ...7 Alarm output status no nC 8 4 8 Hysteresis H5tr 8 4 9 Alarm delay dELA 8 4 10 Alarm silence time 5IL 8 4 11 Flash display when alarm occurs FL5H 8 4 12 Access Setpoint AC5P 8 4 13 Adjusting alarm s...

Page 4: ...4...

Page 5: ...ter The instrument can accept pulses from most types of sensor and display speed per second minute or per hour plus run time in hours on a separate display The BA514G has a single pair of input termin...

Page 6: ...ter may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 8 4 12 and 8 4 13 2 3 Displays The BA514G has two digit...

Page 7: ...t fall below the lower threshold and rise above the upper threshold Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Ma...

Page 8: ...pulse input ranges are selectable in the BA514G Tachometer configuration menu VoLt5 L and VoLt5 H The Tachometer input terminals 5 and 6 may be connected to any voltage pulse output sensor The BA514G...

Page 9: ...erconnecting cable screens The BA514G Tachometer may be pipe mounted using a BA393G pipe mounting kit or panel mounted using a BA394 or BA395 panel mounting kit All are available as accessories 4 2 In...

Page 10: ...ment is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as an acces...

Page 11: ...r that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the monitored...

Page 12: ...n or oFF See section 5 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 5 9 5CALE 5 Speed scale factor 5CALE 5 is a...

Page 13: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 14: ...14...

Page 15: ...15...

Page 16: ...lse has noisy edges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachom...

Page 17: ...shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The u...

Page 18: ...ing used it is not necessary to enter a clip off value see 5 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The...

Page 19: ...onfirmed by entering 5urE using the or button to adjust the flashing digit and the button to move control to the next digit Pressing will then reset the grand total to zero and return the Tachometer t...

Page 20: ...ulse current flows through resistor R1 The current flowing in the circuit is determined by R1 which should be chosen to limit the pulse output current to less than 10mA For a 24V supply R1 should be g...

Page 21: ...elect diVidE in the pulse output sub menu and press which will reveal the existing divisor The selected divisor can be changed by pressing the or push button followed by the button to return to diVidE...

Page 22: ...between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 second...

Page 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 24: ...ts unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the se...

Page 25: ...nfigure clip off See 5 13 Alarms do not function Alarms have been disabled following calibration change Re enable both alarms See 8 4 3 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE...

Page 26: ...single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a normally open or closed output An alarm delay a...

Page 27: ...ur5salarm is activated when the speed or run time display equals the setpoint Note 5P15 is displayed for a speed alarm and 5P1H for a run time alarm See section 8 4 5 HI LO Alarm function Defines whet...

Page 28: ...28...

Page 29: ...eturn to the Hi Lo prompt in the alarm sub menu 8 4 7 Alarm output status no nC Each single pole alarm output may be open or closed in the non alarm condition When the BA514G power supply is turned of...

Page 30: ...out having access to the configuration and alarm sub menus Protection against unauthorised or accidental adjustment is provided by a separate security access code Using the or push button select AC5P...

Page 31: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 32: ...en a Tachometer is supplied with an optional 4 20mA output the configuration menu is extended as shown in Fig 15 The 4 20mA output sub menu is accessed via the 4 20 oP function The 4 20mA output is co...

Page 33: ...s function Using the or push button select 20 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or...

Reviews: