BEKA BA488CF-P PROFIBUS PA Manual Download Page 6

6

Uo

=

14.7V dc

Io

=

146.7mA dc

Po

=

0.58W

The switches and associated wiring connected to
the terminals must comply with the requirements
for 

simple apparatus

.  i.e. the switch must be

mechanically activated and  have IP20 protection,
and both the switch and the wiring must be
capable of withstanding a 500V rms insulation test
to earth for one minute.  Most industrial push
buttons and wiring satisfy these requirements.

The input safety parameters of terminals S1 to S7
are zero, therefore only switches or intrinsically
safe relays may be connected.

The total maximum permitted cable parameters for
all the cables connected to terminals S1 to S7 in a
IIC hydrogen gas must be less than:

Co

=

0.22µF

Lo

=

0.26mH

Although these parameters are not restrictive, for
reliable operation it is recommended that the
cables between the fieldbus display and the
external push buttons are less than 5m long.

3.5 Alarm outputs

Each of the six alarm outputs is a separate
galvanically isolated solid state switch.  The EC-
Type Examination Certificate specifies that under
fault conditions the voltage, current and power at
each switch output will not exceed those specified
for 

simple apparatus

 in section 5.7 of EN 60079-

11.  This allows each of the BA488CF-P alarm
outputs to be connected to any intrinsically safe
circuit protected by a certified Zener barrier or
galvanic isolator providing that the output
parameters of each circuit are less than:

Uo =

28V dc

Io

=

200mA

Po =

0.84W

The maximum equivalent capacitance and
inductance of each BA488CF-P alarm output is:

Ci

=      40nF

Li

=     20µH

To determine the maximum permissible cable
parameters, Ci and Li must be subtracted from the
maximum cable capacitance and inductance
specified by the system certificate of the circuit
connected to the switch.

3.6 Certification Label Information

The certification label is fitted in a recess on the
top outer surface of the enclosure.  It shows the
ATEX certification information, a statement that the
instrument is a FISCO Field Device, plus BEKA
associates name and location. Non European
certification information may also be included.

4.  SYSTEM DESIGN FOR HAZARDOUS
     AREAS

4.1  FISCO Systems

The BA488CF-P may be connected to any FISCO
compliant fieldbus segment providing that the
power supply or isolator powering the segment can
provide 25mA required by the BA488CF-P
PROFIBUS display.

Fig 2 shows a typical fieldbus segment.  To comply
with FISCO requirements, the power supply,
terminators, field devices and the interconnecting
cables must conform with  EN 60079 part 27.

Fig 2   FISCO fieldbus system

Summary of Contents for BA488CF-P PROFIBUS PA

Page 1: ...Issue 3 8th December 2011 BA488CF P PROFIBUS PA Intrinsically safe Panel mounting Fieldbus Display issue 3...

Page 2: ...3 4 Units 6 3 5 Alarms 6 3 5 1 Alarm Summary 6 3 5 2 Alarm Activation 6 3 5 3 Alarm Output 6 3 6 Display 6 3 6 1 Settings 6 3 6 2 Quick Access 6 3 6 3 Access Code 6 3 6 4 Status Text 6 3 6 5 Last Inpu...

Page 3: ...ieldbus variable and are configured via the instrument menus and push buttons They can not be controlled via the fieldbus The instrument has been certified intrinsically safe by European Notified Body...

Page 4: ...roll through the display screens by operating the or push buttons The number of screens available depends upon how the BA488CF P PROFIBUS display has been configured and the number of process variable...

Page 5: ...BA488CF P to be installed in all Zones and to be used with most common industrial gases WARNING installation in Zone 0 When installed in a Zone 0 potentially explosive atmosphere requiring apparatus o...

Page 6: ...tion 5 7 of EN 60079 11 This allows each of the BA488CF P alarm outputs to be connected to any intrinsically safe circuit protected by a certified Zener barrier or galvanic isolator providing that the...

Page 7: ...apparatus i e the switch must be mechanically activated and have IP20 protection and both the switch and the wiring must be capable of withstanding a 500V rms insulation test to earth for one minute...

Page 8: ...d and the instrument secured with four panel mounting clips The BA488CF P liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrume...

Page 9: ...es with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected to the potential equalising network...

Page 10: ...tered Using the or button adjust the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits hav...

Page 11: ...onfiguration at the fieldbus system host see the PROFIBUS Fieldbus Interface Guide which may be downloaded from the BEKA website This sub menu allows one of eleven standard display formats to be selec...

Page 12: ...ic characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the and push buttons Numbers upper lower case lette...

Page 13: ...light brilliance and display contrast are adjustable from this sub menu 6 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is described in sections 2 1 and 6 4 When enabled an oper...

Page 14: ...display will be terminated 6 3 11 Instrument address Enables the required three digit PROFIBUS address to be entered digit by digit using the instrument s push buttons 6 4 Quick Access Menu The Quick...

Page 15: ...15...

Page 16: ...16...

Page 17: ...3 2 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certifie...

Page 18: ...ber on the rear panel This tag number is not visible from the front of the instrument after installation 8 2 PROFIBUS Interface Guides The BEKA PROFIBUS Interface Guide which may be downloaded from th...

Page 19: ...eldbus Connection 3 3 Interface Guide 8 2 FISCO 3 3 4 1 FOUNDATION fieldbus 1 0 FM Approval Appendix 1 Gas groups 3 2 Appendix 1 2 Guarantee 7 5 IECEx Certification Appendix 2 Input Scaling 6 3 2 Inst...

Page 20: ...P comply with the requirements for a FISCO Field Device specified in IEC60079 27 The intrinsically safe circuits shown in Figs 2 and 3 of this manual may therefore be used for installations in the USA...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...the following certification code and marking For gas Ex ia IIC T4 Ta 40 C to 60 C The specified intrinsic safety parameters are identical to the ATEX parameters and confirm that terminals 1 2 comply w...